VMC334 - 34 WAY THREE PHASE SERIES COMBINED METER BOARDS
INSV0156_v2
SPECIFICATIONS
Rated Operational
Voltage
415V AC maximum,
50Hz
Maximum Current 100A
Rated Insulation Voltage 1000V
Short Circuit Withstand 10kA
DIMENSIONS
Cover Assembly 900 x 402 x 77mm
Base Box Dimensions 853 x 355 x 150mm
Overall Assembled
Dimensions 900 x 402 x 171mm
Total Internal Meter
Mounting Space 310 x 320 x 139mm
Maximum Meter Depth 130mm
SAFETY
This product complies in full with AS/NZS 61439.3.
This product should be installed by a suitably
qualied person in accordance with Australian
and New Zealand wiring rules.
IP40
INSTALLATION PROCEDURE
This product is designed to be installed inside a wall
cavity with a minimum stud size of 90mm and a
minimum plaster board/wall covering of 10mm.
The metal wall enclosure must be earthed. Fold out
tags (x6) on the side walls of the enclosure can be
folded out to set the correct height onto the studs.
Door hinge pins are easily removable and the door
can be reversed so that it swings either left or right.
This product is designed to be used with
New Zealand and Australia’s MEN system.
DO NOT install a link between the neutral bars
and earth bar on circuits dedicated to RCDs.
Please ensure circuits and protective devices
are adequately identied during installation.
WARRANTY
This product is covered by a 1 Year Vynco Warranty -
proof of purchase is required. Please contact Vynco
for details of returns procedure.
NOTE: This product contains NO user serviceable parts.