Wöhrle CONVERT II User manual

Wöhrle Stromversorgungssysteme GmbH Subject to change
www.woehrle-svs.de REV 03
15.10.2021
CONVERT II
1, 2 and 3 kVA UPS
User Manual

Wöhrle Stromversorgungssysteme GmbH Subject to change
www.woehrle-svs.de REV 03
15.10.2021
Page II of 47
User Manual
CONVERT II
Table of Contents
ALegalProvisions.................................................................................................................III
BChangesRevisionTable......................................................................................................IV
1Safety Instructions and Storage / Battery Care...............................................................1
1.1 Safety Instructions.....................................................................................................1
1.2 Storage / Battery Care...............................................................................................3
2Product Introduction.........................................................................................................4
2.1 General Characteristics .............................................................................................4
2.2 Special Features........................................................................................................5
3UPS Functional Descriptions ...........................................................................................6
3.1 Front Panel Display ...................................................................................................6
3.2 Rear Panel.................................................................................................................8
3.3 Communication Port Explanation...............................................................................9
4Installation and Operation ..............................................................................................10
4.1 Unpacking................................................................................................................10
4.2 Selecting Installation Position ..................................................................................13
4.3 Operation.................................................................................................................14
5UPS System Block Diagram ...........................................................................................25
6Maintenance Guide .........................................................................................................26
6.1 Troubleshooting.......................................................................................................26
6.2 Error Codes and Their Meanings.............................................................................27
6.3 Maintenance............................................................................................................28
7Communication Software ...............................................................................................28
7.1 Hardware Setup.......................................................................................................28
7.2 Software Installation ................................................................................................28
8Optional Communication Cards.....................................................................................29
8.1R2E- (second RS-232) card.....................................................................................29
8.2 DCE (Dry Contact) card...........................................................................................30
8.3 SNMP Cards............................................................................................................31
9Specifications CONVERT II (Rack / Tower)....................................................................33
10 Battery Bank Installation ................................................................................................36
10.1 Important Safety Instructions................................................................................36
10.2 Introduction to the Front and Rear Panel..............................................................37
10.3 Installation and Operation ....................................................................................38

Wöhrle Stromversorgungssysteme GmbH Subject to change
www.woehrle-svs.de REV 03
15.10.2021
Page III of 47
User Manual
CONVERT II
A Legal Provisions
This manual and the information contained therein are the property of Wöhrle
Stromversorgungssysteme GmbH. Any partial or complete publication requires the prior
written permission of Wöhrle Stromversorgungssysteme.
In-house duplication for the exclusive purpose of product evaluation or other proper use is
permitted and does not require prior approval.
Trademark
All trademarks are recognised, even if not expressly marked as such. A missing mark does
not mean that a product or trademark is not a registered trademark.
Wöhrle Stromversorgungssysteme GmbH
Lerchenstraße 34
71144 Steinenbronn | Germany
+49 7157 73 74 0
info@woehrle-svs.de
www.woehrle-svs.de
©2018 Wöhrle Stromversorgungssysteme GmbH. All rights reserved

Wöhrle Stromversorgungssysteme GmbH Subject to change
www.woehrle-svs.de REV 03
15.10.2021
Page IV of 47
User Manual
CONVERT II
B Changes RevisionTable
Revision
Notes
REV 01
First version released
REV 02
6.2 Error Codes and Their Meanings extended
REV 03
Adjustment 10.3.6 Specification

Wöhrle Stromversorgungssysteme GmbH Subject to change
www.woehrle-svs.de REV 03
15.10.2021
Page 1 of 47
User Manual
CONVERT II
1 Safety Instructions and Storage / Battery Care
1.1 Safety Instructions
SAVE THESE INSTRUCTIONS.
This manual contains important instructions that should be followed during installation and
maintenance of the UPS and batteries.
1. Do not open the case as there are no serviceable parts inside. Opening the case will void your warranty
and introduces the risk of electric shock.
2. Do not try to repair the unit yourself. Doing so will void your warranty. Contact your local supplier for
repairs.
3. If liquids are spilt onto the UPS or foreign objects dropped into the unit the UPS could be damaged,
users could be subject to electric stock, and the warranty will become null and void.
4. Do not install the UPS in an environment with sparks, smoke, or hazardous gas.
5. This UPS is equipped with an EMI filter. To prevent potential leakage current hazards ensure that the
AC mains supply is securely grounded. Because of small leakage currents generated by the EMI filter in
the UPS it is necessary to double check that the ground wire of the UPS is properly grounded before
connecting the UPS to the AC mains
6. This UPS is designed to be installed and commissioned in a sheltered, controlled environment as
follows:
- Ensure that the UPS is installed within the proper environmental range. (0-40°C and 0-90% non-
condensing humidity). High ambient temperature reduces battery life.
- Do not install the UPS in direct sunlight. Your warranty may be void if the batteries fail
- Do not install the UPS in an inflammable or otherwise hazardous environment.
- Avoid vibration and areas subject to physical impact.
- Avoid any area with sparks.
- Dusty, corrosive, and salty environments can damage any UPS.
- Install the UPS indoors as it is not designed for installation outdoors.
7. To prevent overheating of the UPS keep all ventilation openings free from obstruction, and do not place
anything on top of the UPS. Keep the UPS rear panel 20 cm away from the wall or other obstructions.
8. Install the UPS in a ventilated area, ideally exchanging 5 m3 of air per hour, because the chemical
reaction during battery charging causes trace gas production. If the batteries suffer breakage electrical
arcing could occur in the UPS interior.
9. If the product emits a strange noise or smell please immediately stop using the product and contact your
dealer for maintenance.
10. Always switch off the UPS and disconnect the batteries when relocating the UPS. Be aware that, even
when disconnected, charged batteries present a possible electric shock hazard.
11. The UPS should be recharged every 2-3 months if unused. If this is not done then the warranty will be
null and void. When installed and being used the batteries will be automatically recharged and kept in
top condition.
12 Make sure that the AC utility outlet is correctly grounded.
13. Ensure that the input voltage of the UPS matches the utility supply voltage. Use a certified input power
cable with the correct plugs and sockets for the system voltage.
14. To ensure safety in all applications where a UPS is hard wired to the electrical supply, ensure that the
system is installed by a qualified electrical contractor.
15. The UPS has its own internal energy source (battery). Should the battery be switched on when no AC
power is available there could be voltage at the output terminals.

Wöhrle Stromversorgungssysteme GmbH Subject to change
www.woehrle-svs.de REV 03
15.10.2021
Page 2 of 47
User Manual
CONVERT II
16. Make sure that the AC utility outlet is correctly grounded
17. Install the UPS away from objects that give off excessive heat and areas that are excessively wet.
18. The battery will discharge naturally if the system is unused for a long time
19. This UPS supports electronic equipment in office, telecommunication, process-control, medical, and
security applications. Non-authorized technicians are not allowed to install the UPS in the following
areas.
a. Medical equipment directly related to human life
b. Elevators, subway systems, or any other equipment related to human safety.
c. Public systems or critical computer systems.
20. The UPS offers a CVCF (Constant Voltage Constant Frequency) setting function.
a. For correct setting and wiring please contact with your local utility agent.
b. Do not set it yourself or your warranty will be void.
21. This UPS has been designed and constructed to protect your assets from the wide range of power
aberrations experienced on utility power lines today. It is your insurance for a reliable, clean and stable
voltage supply. It is worth taking care to install the system correctly and to have it maintained correctly
by your local dealer.
22. Do not try to replacement of the battery yourself. Doing so will void your warranty. Contact your local
supplier for repairs.
23. The UPS is intended for installation in a controlled environment.
24. Install the UPS so that it is not likely to be contacted by people.
25. The maximum ambient operating temperature is 40°C or equivalent.
26. Units are considered acceptable for use in a maximum ambient 40°C
27. CAUTION - RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT TYPE. DISPOSE
OF USED BATTERIES ACCORDING TO THE INSTRUCTIONS.
28. CAUTION - Do not dispose of batteries in a fire. The batteries may explode.
29. CAUTION –Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It
may be toxic.
30. CAUTION–A battery can present a risk of electrical shock and high short circuit current. The following
precautions should be observed when working on batteries:
1) Remove watches, rings, or other metal objects.
2) Use tools with insulated handles.
3) Wear rubber gloves and boots.
4) Do not lay tools or metal parts on top of batteries.
5) Disconnect charging source prior to connecting or disconnecting battery terminals.
6) Determine if battery is inadvertently grounded. If inadvertently grounded, remove source from ground.
Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock
can be reduced if such grounds are removed during installation and maintenance (applicable to
equipment and remote battery supplies not having a grounded supply circuit).
31. External battery cabinet installation instructions, please refer to " Battery Bank Installation User's
MANUAL"

Wöhrle Stromversorgungssysteme GmbH Subject to change
www.woehrle-svs.de REV 03
15.10.2021
Page 3 of 47
User Manual
CONVERT II
1.2 Storage / Battery Care
If the UPS is unused for an extended period of time it must be stored in a moderate climate. The
batteries should be charged for 12 hours every three months by connecting the UPS to the utility
supply and switching on the input breaker located on the UPS rear panel. Repeat this procedure
every two months if the storage ambient temperature is above 25°C.

Wöhrle Stromversorgungssysteme GmbH Subject to change
www.woehrle-svs.de REV 03
15.10.2021
Page 4 of 47
User Manual
CONVERT II
2 Product Introduction
2.1 General Characteristics
1. True on-line technology continuously supplies your critical device with stable, regulated,
transient-free, pure-sine-wave AC power.
2. High-efficiency PWM sine-wave topology yields excellent overall performance.
3. The high crest factor of the inverter handles all high in-rush current loads without the need
to upgrade the power rating.
4. User-friendly plug-and-play design allows hassle-free installation.
5. Built-in maintenance-free, sealed batteries minimize the need for after-sales service.
6. To protect the unit from overloading, the UPS will automatically switch to bypass mode in
30 seconds if loading is at 105% of rated capacity. It will automatically switch back to
inverter mode once the overload condition ceases.
7. Should the output become short-circuited the UPS puts the system in stand-by mode,
provides visible and audible alarms, and cuts the output supply automatically until the short
circuit situation is resolved manually.

Wöhrle Stromversorgungssysteme GmbH Subject to change
www.woehrle-svs.de REV 03
15.10.2021
Page 5 of 47
User Manual
CONVERT II
2.2 Special Features
1. Our High Frequency Transformer-less technology and tower-convertible enclosure enables
the UPS to be integrated into even the most difficult environments with space constraints.
2. This UPS is equipped with fully digital control logic for greater functionality and enhanced
power protection. Digital signal processing (DSP) also provides the UPS with powerful
communication capability, which simplifies remote control and monitoring.
3. Our wide input voltage tolerance of 110-300 V allows under-voltage or over-voltage
correction without unnecessary battery drain and helps extend battery life.
4. Our DC-start function ensures the start-up of the UPS even during power outages.
5. Our smart battery management system extends the batteries’ life span.
6. Our Active Power Factor Correction control function constantly maintains the UPS input
power factor at > 0.98 for superb energy efficiency.
7. Our Selectable Bypass input voltage tolerance (sensitivity low/high) prevents under- or over-
voltage being supplied to the loads in Bypass mode. The selectable voltage ranges are (i)
Bypass Sensitivity Low: many selectable output voltages ±15% and (ii) Bypass Sensitivity
High: many selectable output voltages ±10%. For example, if the output voltage setting is
230 V the Bypass Sensitivity Low range is 230 V ±15%, i.e., 195.5-264.5 VAC.
8. The UPS provides numerous configurable output voltages to match various system voltages.
9. The UPS is designed to comply with various stringent international standards for
electromagnetic interference compatibility (EMC).

Wöhrle Stromversorgungssysteme GmbH Subject to change
www.woehrle-svs.de REV 03
15.10.2021
Page 6 of 47
User Manual
CONVERT II
3 UPS Functional Descriptions
3.1 Front Panel Display
3.1.1 CONVERT II < Convertible Type (Rack / Tower) > LCD panel
6 Button LCD Panel
Item
Sign
Description
LCD Display
Green LED steadily lights up to indicate that the Utility input
voltage is within the window (160Vac~288Vac); the LED
flashes flickeringly to indicate that the Utility input voltage is
within the acceptable window (120Vac~159Vac).
Green LED lights up to indicate there is an output available at
the Programmable Outlet 1 & Programmable Outlet 2.
Amber LED lights up to indicate the Bypass Input is normal.
UPS Fault LED
UPS On/Alarm Silence
UPS OFF Switch
Special functions log in/out
Go to next page
Go to previous page or change the setting of the UPS.

Wöhrle Stromversorgungssysteme GmbH Subject to change
www.woehrle-svs.de REV 03
15.10.2021
Page 7 of 47
User Manual
CONVERT II
To re-confirm the change of UPS Setting
◎Manual Bypass: Press “ON-KEY" and “Up-KEY" key simultaneously for approx. 3 seconds to transfer
from "Inverter to Bypass" (the bypass led continuously "blink" and the buzzer will beep intermediately or
"Bypass to Inverter", when the UPS is on Line Mode and the Bypass Voltage Window is Normal.
3.1.2 LCD displayer description
Item
Sign
Description
1
Bypass Input Abnormal, UPS fails to transfer to
bypass, Bypass Abnormal at ECO mode
2
Utility Input Abnormal
3
Site Wiring Fault
4
Buzzer Silent
5
UPS Overloading
6
UPS Working in specified mode*
7
UPS Fault or Abnormal Warning
8
UPS Flow Chart
9
3-Digit Measurement Display
10
Indicates the item to be measured
11
Battery Abnormal
12
Battery Low
13
Testing

Wöhrle Stromversorgungssysteme GmbH Subject to change
www.woehrle-svs.de REV 03
15.10.2021
Page 8 of 47
User Manual
CONVERT II
3.2 Rear Panel
CONVERT II 230V
1. Emergency Power Off (EPO) / Remote ON/OFF (ROO)
Dry contact signal inputs
2. USB port*
3. RS-232 port
4. Fan
5. External battery connector*
6. Slot for optional communication cards*
7. AC power connection socket
8. Utility input circuit breaker
9. Output circuit breaker for two outlets
10. AC outlets (Program Relay*)
11. AC outlet
* Remark: Optional function
1
K
2
K
3
K
2
K
3
K

Wöhrle Stromversorgungssysteme GmbH Subject to change
www.woehrle-svs.de REV 03
15.10.2021
Page 9 of 47
User Manual
CONVERT II
3.3 Communication Port Explanation
The UPS is equipped witha true RS-232 communication port as standard to provide communication
with bundled UPS monitoring software for remote monitoring of the UPS status using a PC.
In addition, there are sixoptional interface cards available to meet various communication
needs:USB, EPO, DCE(dry contact relay card), R2E, USE, and an SNMP/Web card. (Please see
Chapter 8.)
The software bundled with the UPS is compatible with many operating systems, including Windows
98 / Me / NT / 2000 / 2003 / XP / Vista / 2008 / 7 / 8 , Novell, NetWare, Unix, Linux 2.6.x, Mac OS X
v10.5 Leopard,Mac OS X v10.6 Snow Leopard please contact your local dealer for suitable software.
All communication ports including optional cards can be active and used simultaneously to monitor
the UPS status. However, only one communication interface at a time (the one with the highest
priority)can control the UPS. The priorities of these communication interfaces are as follows (highest
priority first). 1) EPO/ROO input port
2) Optional interface card
3) Optional USB
4) RS-232
3.3.1 True RS-232
The RS-232 interface must be configured as follows:
Baud Rate
2400 bps
Data Length
8 Bits
Stop Bit
1
Parity
None
Pin Assignments:
3.3.2 EPO
Pin Assignments: Function Setting:
Pin 3: RS-232 Rx
Pin 2: RS-232 Tx
Pin 5: Ground
1. EPO NC →Shutdown UPS (default)
2. EPO NO →Shutdown UPS
3. ROO NC →Start-up UPS
4. ROO NO →Start-up UPS
(this function setting by setting tool )

Wöhrle Stromversorgungssysteme GmbH Subject to change
www.woehrle-svs.de REV 03
15.10.2021
Page 10 of 47
User Manual
CONVERT II
4 Installation and Operation
Please read the Safety Instruction guide (pages 2 and 3) before installing the UPS.
4.1 Unpacking
Inspect the UPS upon receipt. The packaging is robust, but accidents and damage may still occur
during shipment. Notify the forwarder and dealer if there is damage.
The packaging is recyclable and reusable.
1. After removing the packing foam please be careful handling the UPS while it is still in the
plastic bag. The plastic is slippery, and the UPS could fall and injure your feet.
2. Check for the following standard package contents, in addition to the UPS itself.
A. User Manual
B. IEC output cables (for UPS with IEC sockets only)
C. IEC input cables (for UPS with IEC sockets only)

Wöhrle Stromversorgungssysteme GmbH Subject to change
www.woehrle-svs.de REV 03
15.10.2021
Page 11 of 47
User Manual
CONVERT II
4.1.1 Installation Instructions
Tower installation
Rack Mount installation
Step 1
Step 2

Wöhrle Stromversorgungssysteme GmbH Subject to change
www.woehrle-svs.de REV 03
15.10.2021
Page 12 of 47
User Manual
CONVERT II
Step 3

Wöhrle Stromversorgungssysteme GmbH Subject to change
www.woehrle-svs.de REV 03
15.10.2021
Page 13 of 47
User Manual
CONVERT II
4.2 Selecting Installation Position
The UPS is heavy. Select a location sturdy enough to support the UPS weight.
To ensure proper operation and long operating life, position the UPS according to the following
requirements.
1. Keep at least 20 cm (8 inches) of clearance beyond the rear panel of the UPS.
2. Do not block the air flow to the ventilation louvers of the unit.
3. Ensure that the installation site is free from excessive dust and the ambient temperature
and humidity are within the specified limits.
4. Do not place the UPS in a dusty or corrosive environment or near any flammable objects.
5. This UPS is not designed for outdoor use.

Wöhrle Stromversorgungssysteme GmbH Subject to change
www.woehrle-svs.de REV 03
15.10.2021
Page 14 of 47
User Manual
CONVERT II
4.3 Operation
4.3.1 LCD Panel
4.3.1.1 Line mode start up
1. Please ensure the outlet of power source is proper grounded.
2. Ensure the voltage rating of power source is matched with UPS spec.
3. Plug in UPS to the AC source
4. UPS will start initializing after AC input power is available 5 seconds. LED/LCD indicator
will be all lit and dim once and fan will start spinning.
Full LCD display looks as below figure:
5. Press UPS button and hold untill twice beep heard, UPS begins starting procedures
for 5 seconds. LCD display will show as below figure-A and then figure-B sequentially.
LEDs will light up to indicate that the Utility and the Bypass are normal.
And then " ",""," LED remain lit during figure-B LCD display.
A
B
When you see figure-B means the starting up procedure is finished. Please ensure UPS
recharge in line mode for at least 4 hours for fully recharged before the first backup test if it’s a
new installed unit.

Wöhrle Stromversorgungssysteme GmbH Subject to change
www.woehrle-svs.de REV 03
15.10.2021
Page 15 of 47
User Manual
CONVERT II
6. Back up test –Unplug inlet power cord or switch off power source to simulate power failure
condition. Green LED indicator will be dimmed andAmber LED " "," will be light.
Intermittent audible alarm will be heard and LCD display shows as below figure-C:
C
4.3.1.2Cold Start (DC start)
1. Ensure the internal battery is available or external battery set well connected to UPS. Press
and hold key for 3 seconds until twice beeps heard, release button and press for 3
seconds until twice beeps heard again to confirm cold start procedure. If the 2nd button
confirmation not be finished within 10 seconds after 1st twice beeps, UPS will not cold start and
shut off after 10 seconds.
2. 5 seconds after cold starting, amber LED" "," will be light, intermittent audible alarm will
be heard and LCD will show sequentially as below figure-D and figure-E
D
E

Wöhrle Stromversorgungssysteme GmbH Subject to change
www.woehrle-svs.de REV 03
15.10.2021
Page 16 of 47
User Manual
CONVERT II
4.3.1.3Operation of measurements display
1. UPS measurements can be checked after UPS started by pressing select key . The
display sequence are as below figure-F (AC input voltage)→figure-G (AC input frequency)→figure-
H (UPS output voltage)→figure-I (UPS output frequency)→figure-J (UPS loading
percentage)→figure-K (UPS output current)→figure-L (Battery voltage) →figure-M (UPS inner
temperature) and back to figure-F.
F
G
H
I
Table of contents