WAGNER TITANUS PRO-SENS User manual

Air sampling smoke detection system
Fire Detection
TITANUS
PRO·SENS
®
Technical Manual


Air sampling smoke detection system
TITANUS
PRO·SENS
®
Technical Manual
WAGNER Group GmbH
Schleswigstraße 1 - 5
D-30853 Langenhagen
Telephone +49 (0) 511 / 97383-0
Telefax +49 (0) 511 / 97383-140
E-Mail suppo[email protected]
Internet www.wagner.de
Item Number 69-30-0226
Edition 06/13
Supersedes 04/09


TITANUS
PRO·SENS
®
06/13 5
Contents
1 General 11
1.1 Introduction 11
1.2 Safety Information 11
1.3 Guarantee 12
1.4 Copyright 12
1.5 Packaging 12
1.6 Disposal 13
2 Product Description 15
2.1 Features of the TITANUS
PRO·SENS
® 15
2.2 Areas of Application 17
3 Technical Description 21
3.1 System Description 21
3.1.1 Function 22
3.2 TITANUS
PRO·SENS
® and accessories 25
3.2.1 Overview 25
3.2.2 Basic device TITANUS
PRO·SENS
® 26
3.2.3 Diagnostics 28
3.2.4 Response Indicators 29
3.2.5 Device Support 30
3.3 Pipe system 31
3.3.1 Overview of available pipe components 31
3.3.2 Air sampling points for room monitoring 33
3.3.2.1 Aspiration-reducing film sheets 33
3.3.2.2 Air flow reducer clips 34
3.3.3 Ceiling feed-through for hidden installations 35

TITANUS
PRO·SENS
®
6 06/13
3.3.4 Air filter for dusty areas 37
3.3.5 Air return for pressurised and dusty areas 40
3.3.6 Noise suppressor 41
3.3.7 Steam trap for humid areas 42
3.3.8 Detonation prevention device for endangered areas 44
4 Technical Data 47
4.1 TITANUS
PRO·SENS
® 47
4.2 Pipe system – TITANUS
PRO·SENS
® 50
5 Design 51
5.1 General 51
5.1.1 Regulations 52
5.1.2 Pipe system 53
5.1.3 Air flow monitoring 59
5.1.4 Sensitivity 60
5.1.5 Project planning limits 61
5.2 Pipe design 63
5.2.1 Project planning guidelines 63
5.2.2 Pipe accessories 64
5.2.3 Sensitivity and pipeline project design 65
5.2.3.1 Pipeline project planning with pipe accessories 65
5.2.4 Aperture diameter 69
5.3 Special project design 73
5.3.1 Project planning for individual aperture monitoring 73
5.3.1.1 I - Pipe system 73
5.3.1.2 U - Pipe system 75
5.3.1.3 M - Pipe system 77
5.3.1.4 Double U - Pipe system 79

TITANUS
PRO·SENS
®
06/13 7
5.3.2 Simplified pipe project design 81
5.3.2.1 I - Pipe system 81
5.3.2.2 U - Pipe system 82
5.3.2.3 M - Pipe system 83
5.3.2.4 Double - U - Pipe system 84
5.3.3 Project planning with branch pipes 86
5.3.4 Project planning with long intake lines > Ø 25 mm 88
5.3.5 Project planning with acceleration apertures 90
5.3.6 Project design for forced air flow 95
5.3.7 Project design with air sampling hose 99
5.3.8 Project planning with air return 100
5.4 Mains supply 102
6 Installation 105
6.1 General 105
6.2 Opening the TITANUS
PRO·SENS
® 106
6.3 Settings 107
6.3.1 Detector module 107
6.3.1.1 Setting of the response sensitivity 107
6.3.1.2 Delay period of the alarm activation 107
6.3.1.3 Activating threshold of the air flow monitoring 108
6.3.1.4 Delay period of the air flow fault 108
6.3.1.5 Fault display 109
6.3.1.6 LOGIC·
SENS
109
6.3.1.7 Function of the collective fault contact 109
6.3.1.8 Setting of the fan voltage TITANUS
PRO·SENS
® 110
6.3.1.9 Connect the fan at TITANUS
PRO·SENS
® 111
6.3.1.10 Setting of fan voltage at TITANUS
PRO·SENS
®-SL 112
6.3.1.11 Connecting the fan at TITANUS
PRO·SENS
®® -SL 113

TITANUS
PRO·SENS
®
8 06/13
6.4 Installation of the reset board 114
6.5 Mounting location 117
6.5.1 Fixing of the TITANUS
PRO·SENS
® 117
6.5.2 Connection of the air sampling pipe 120
6.6 Electrical connection 121
6.6.1 Connection to FAS, with reset button 122
6.6.2 Connection of several TITANUS
PRO·SENS
® without FAS,
with reset button
124
6.6.3 Connection to FAS, with reset board 125
6.7 Installation of the second detector module 127
6.8 Response indicator - electrical connection 129
6.9 Data Log 130
7 Installation pipe system 131
7.1 Installation general 131
7.1.1 Installation pipe system 132
7.1.2 Installation air sampling hose 133
7.2 Linear expansion of the pipe system 135
7.3 Patented aspiration apertures 137
7.4 Ceilings feed-through 139
7.4.1 Ceilings feed-through for false ceiling 139
7.4.2 Other ceilings feed-through 140
7.5 Monitoring in forced air flow systems
(ventilation or climatic applications)
142
7.5.1 Detection at air inlets/outlets 142
7.5.2 Detection in bypass systems 142
7.6 Filter 144
7.6.1 Installation of the air filter type LF-AD-x 144
7.6.2 Mounting of the special filter type SF-400/650 145

TITANUS
PRO·SENS
®
06/13 9
7.7 Air return 147
7.8 Noise suppressor 148
7.9 3-Way ball valve 150
7.10 Steam traps 152
7.10.1 Steam trap type KA-DN-25 152
7.10.2 Steam trap type KA-1 153
7.11 Detonation prevention device 154
7.12 Test adapter 156
8 Commissioning 157
8.1 Adjustment Air Flow Sensor 158
8.1.1 Adjustment independent of the air pressure 159
8.1.2 Adjustment dependent on the air pressure 160
8.2 Detector module and alarm transmission 162
8.3 Check air flow monitoring 163
8.4 Check fault signal transmission 165
8.5 Operational check of TITANUS
PRO·SENS
® 166
8.5.1 Preparations for operational check 166
8.5.2 Operational check 167
9 Maintenance 171
9.1 Visual check 171
9.2 Flash Code Table 171
9.3 Check detector module and alarm transmission 172
9.4 Check pipe system 172
9.5 Exchange of detector module 173
9.6 Changing the air filter LF-AD-x 175
9.7 Changing special air filter SF-400/650 177

TITANUS
PRO·SENS
®
10 06/13
9.8 Check of the air flow sensor adjustment 178
9.9 Check air flow monitoring 181
9.10 Check fault signal transmission 181
9.11 Maintenance intervals 181
Appendix
Air Pressure Adjustment Tables
Projection Tables
System Product List
Inspection Protocol
Glossary
Conformity certification pursuant to EU

TITANUS
PRO·SENS
® General
06/13 11
General
Introduction
This manual is for installers of air sampling smoke detection systems, in par-
ticular for engineers, technicians, and fitters etc. who have technical knowl-
edge in the field of smoke detection technology but who are possibly working
with this device for the first time.
For damage and faults resulting from the non-observance of this manual
WAGNER Group GmbH, called WAGNER in the following, does not assume
liability.
This manual refers to the air sampling smoke detection systems TITANUS
PRO·SENS
® and TITANUS
PRO·SENS
® 2. These systems may only be
used for early and very early smoke detection. As the smoke detection sys-
tems are from one series, TITANUS
PRO·SENS
® is described here. Specific
technical designs of TITANUS
PRO·SENS
® 2 are described separately.
Safety Information
The following symbols identify parts of the text in this manual which re-quire
special attention so that damage can be avoided and so that operations can
run smoothly.
WARNING
This symbol warns against actions.
which might cause damage if it is ignored.
NOTICE
This symbol warns against actions,
which could cause operational breakdowns if it is ignored.
TIP
Operational improvements can be achieved if this symbol is observed.
1
1.1
1.2

General TITANUS
PRO·SENS
®
12 06/13
Guarantee
The manual is subject to technical modification without notice and makes no
claim to completeness.
In principle our “Terms and Conditions of Supply and Assembly” apply. No
claims under the guarantee or for liability can be made for damage to per-
sons or property if they are based on one or more of the following causes:
▪ insufficient observance of the instructions about the design, assembly of
the aspirating smoke detection system, assembly of the pipe system,
commissioning and maintenance
▪ use of the aspirating smoke detection system in contravention of the in-
tended use
▪ insufficient monitoring of working parts
▪ improperly executed repairs
▪ unauthorised constructional changes to the aspirating smoke detection
system
▪ force majeure
Copyright
The copyright in this Technical Manual remains with WAGNER.
The manual is designed exclusively for the assembler and his colleagues.
Reproduction of the manual, including extracts, is not allowed. Copying or
distribution of the manual in any form is only allowed with permission in writ-
ing from WAGNER.
Packaging
The individual air sampling smoke detection systems are packed in accor-
dance with the anticipated transport conditions. Exclusively environ-mentally
friendly materials were used for the packaging.
The packaging is intended to protect the air sampling smoke detection sys-
tem from being damaged until it is installed. For that reason, it should only
be removed from its packaging shortly before installation.
The packaging material is to be disposed of in accordance with applicable
statutory provisions and local regulations.
1.3
1.4
1.5

TITANUS
PRO·SENS
® General
06/13 13
▪ Dispose of the packaging materials in an environmentally friendly man-
ner.
▪ Observe local disposal regulations.
NOTICE
Packaging materials are valuable raw materials and in many cases can be
re-used or expediently processed and recycled. Improper disposal of pack-
aging materials can harm the environment.
Disposal
If no take-back or disposal agreements have been made, disassembled
components are to be taken for recycling:
▪ Take metal parts for scrapping.
▪ Take plastic parts to be recycled.
▪ Sort the remaining components by material quality and dispose of them.
▪ Give batteries to municipal collecting points,
or send them back to WAGNER Group GmbH.
1.6


TITANUS
PRO·SENS
® Product Description
06/13 15
Product Description
Features of the TITANUS
PRO·SENS
®
TITANUS
PRO·SENS
® is the latest generation of WAGNER air sampling
smoke detection systems. Besides its use for room and equipment protec-
tion the variant can be used for monitoring climatic cabinets and climatic
ducts.
The device has a response sensitivity of up to 0.5 %/m, 0.1 %/m or 0.015
%/m light obscuration. According to the application further sensitivities can
be set. Thanks to the innovative High-Power-Light-Source technology a wide
detection range over all rated fire types is guaranteed.
If 2 detector modules are inserted in the TITANUS
PRO·SENS
®, is the dou-
ble of the monitoring area reachable.
In order to prevent false alarms, the intelligent signal processing called
LOGIC
·SENS
distinguishes between interferences and the occurrence of
real fire.
Like spot-type detectors, which are electronically monitored in order to detect
line fractures and short circuits, air sampling systems require complex and
safe air flow monitoring. The unique air flow sensor technology used in all
WAGNER air sampling smoke detection systems guarantees the detection
of faults such as pipe fractures or blockages of air sampling points.
The low-level air flow is equipped with a dynamic air flow sensor in order to
detect small and quick changes.
Air flow monitoring is temperature compensated and can be adjusted de-
pending on the air pressure.
Depending on the required pipe design the air sampling points have defined
hole diameters. For these exact airs sampling points WAGNER has devel-
oped patented aspiration-reducing film sheets with marking tape and clips
that permit an easy mounting and avoid secondary noise. Another advan-
tage is the quick and easy retrieval and check of the air sampling point di-
ameters.
The system’s air sampling points can be compared to spot-type detectors.
The monitoring areas can therefore be designed according to the relevant
valid national regulations.
The diagnostic software permits quick and reliable fault finding for mainte-
nance and service. The current device condition and any saved data can be
downloaded to a PC via a special interface.
2
2.1
Sensitivit
y
LOGIC
·SEN
S
Safe airflow monitoring
Patented detection points
Spot detector spacing
Diagnostics

Product Description TITANUS
PRO·SENS
®
16 06/13
The fan voltage can be set according to project planning by re-plugging the
plug-in jumpers.
With TITANUS
PRO·SENS
® devices, the fan voltage can be set between
6.9 V and 9 V by means of the plug-in jumpers on the main board.
The voltage with TITANUS
PRO ·SENS
® -SL devices can be set by means
of the fan control circuit boards FC-2 and FC-3.
▪ The voltage can be set to 6.5 V, 6.9 V and 9 V with the FC-2 fan control
circuit board. The FC-2 fan control circuit board is standard in all TITA-
NUS
PRO·SENS
® -SL devices.
▪ The voltage can be set to 10 V, 11 V and 12 V with the FC-3 fan control
circuit board. The FC-3 fan control circuit board available as an option for
all TITANUS
PRO·SENS
® -SL devices.
Choice of ventilator voltage

TITANUS
PRO·SENS
® Product Description
06/13 17
Areas of Application
The air sampling smoke detection system TITANUS® is a technology used
for early smoke detection and very early smoke detection for rooms and
equipment.
Air samples are drawn from the protected area via a pipe system with de-
fined air sampling points and passed to the detector module.
It is particularly suitable for areas in which spot-type detectors cannot be
used or only under certain conditions.
In particular these are areas:
▪ with high fire risk
▪ where a high detection sensibility is required
▪ with limited access and where spot-type detectors are difficult to install or
service
▪ which are air conditioned
▪ which have a greater height than admissible for spot-type detectors
▪ where spot-type detectors are undesirable for aesthetic reasons
▪ where electromagnetic fields have an impact
▪ which are exposed to high or low temperatures
▪ where filters are required due to impurities in the atmosphere
▪ which must be protected from vandalism
TITANUS® is suitable for:
Rooms such as:
▪ floor voids, ceiling voids
▪ tunnels, ducts, voids with difficult access
▪ storage areas, high-rack storage, elevator shafts
▪ museums, cultural centre
▪ deep-freeze storage
2.2
Principle
Room protection

Product Description TITANUS
PRO·SENS
®
18 06/13
Figure 1: Scheme - room monitoring with the air sampling smoke detection system
TITANUS
®
Room monitoring takes place
▪ in air-conditioned rooms for servicing etc
▪ in ventilation ducts
▪ of floor voids, ceiling voids
▪ in EDP rooms, E-distribution cabinets, transformer cells
▪ in climatic cabinets or
▪ at air conditioning ducts in the by-pass
Room monitoring
with air conditioning

TITANUS
PRO·SENS
® Product Description
06/13 19
Figure 2: Monitoring possibilities of a convection air conditioning system or climatic
duct (scheme)
non-ventilated and power-ventilated devices/cabinets such as
▪ distribution cabinets, switch cabinets
▪ telephone switching equipment
▪ measuring and control units
Equipment protection

Product Description TITANUS
PRO·SENS
®
20 06/13
Figure 3: Scheme - equipment monitoring with the air sampling smoke detection sys-
tem TITANUS
®
The air sampling system TITANUS® can also be used for earliest fire detec-
tion in rooms with special air conditioning.
Valuable goods and installations can be reliably monitored due to the sys-
tem’s high sensitivity. Therefore, TITANUS® is especially suited for the fol-
lowing areas:
▪ where early intervention is crucial due to valuable assets
▪ where systems must be operational at all times
▪ where highly sensitive detection is required (e.g. in areas where filters
keep smoke particles in the air at a minimum)
▪ with high air exchange rates