Water Depot Blaster Soft User manual

2
IMPORTANT:
Do not make any adjustments to these units, they are factory set.
Should you encounter problems with the performance of the
Blaster, then you should call for service.
Your dealer is trained in testing water and setting your machines
according to the recommendation of the manufacturer.
Failure to provide proper service when required my void your
warranty or modify the ability of the Blaster to treat your water.

3
Table of Content
Table of content...............................................................................................................3
Instructions......................................................................................................................4
Installation Fitting Assemblies .........................................................................................5
Bypass Valve Operation..................................................................................................6
Consumer Valve Programming Setup .............................................................................7
Factory settings...............................................................................................................8
User Display....................................................................................................................9
Blaster Soft Set Up........................................................................................................10
Installation Flow Diagram ..............................................................................................11
Wiring Diagram .............................................................................................................12
CD Cell Cleaning...........................................................................................................15
Wiring............................................................................................................................16
Platinum Drawings and Part Numbers...........................................................................17
Front Cover and Drive Assembly...................................................................................18
Drive Cap Assembly, Downflow Piston, Upflow Piston, Regenerant Piston and
Spacer Stack Assembly.................................................................................................19
Drive Cap Assembly, Downflow Piston, Regerant Piston and Spacer Stack Assembly .20
Injector Cap, Injector Screen, Injector, Plug and O-Ring................................................21
Refill Flow Control Assembly and Refill Port Plug..........................................................22
Drain Line – ¾”..............................................................................................................23
Water Meter, meter Plug and Mixing Valve....................................................................24
Installation Fitting Assemblies .......................................................................................25
Bypass Valve ................................................................................................................26
WS1 Wrench.................................................................................................................27
Trouble Shooting...........................................................................................................28

4
Instructions
The control valve, fittings and/or bypass are designed to accommodate minor plumbing misalignments but
are not designed to support the weight of a system or the plumbing.
Do not use Vaseline, oils, other hydrocarbon lubricants or spray silicone anywhere. A silicon lubricant
may be used on black o-rings but is not necessary. Avoid any type of lubricants, including silicone, on
red or clear lip seals.
The nuts and caps are designed to be unscrewed or tightened by hand or with the special plastic wrench.
If necessary a pliers can be used to unscrew the nut or cap. Do not use a pipe wrench to tighten or
loosen nuts or caps. Do not place screwdriver in slots on caps and/or tap with a hammer.
Do not use pipe dope or other sealant on threads. Teflon tape must be used on the threads of the 1” NPT
elbow or the ¼” NPT connection and on the threads for the drain line connection. Teflon tape is not
necessary on the nut connection or caps because of o-ring seals.
After completing any valve maintenance involving the drive assembly or the drive cap assembly and
pistons, press and hold NEXT and REGEN buttons for 3 seconds or unplug power source jack from the
printed circuit board (black wire) and plug back in. This resets the electronics and establishes the service
piston position. The display should flash all wording, then flash the software version (e.g. 154) and then
reset the valve to the service position.
All plumbing should be done in accordance with local plumbing codes. The pipe size for the drain line
should be a minimum of ½”.Backwash flow rates in excess of 7 gpm or length in excess of 20 feet require
¾” drain line.
Solder joints near the drain must be done prior to connecting the drain line flow control fitting. Leave at
least 6” between the drain line control fitting and solder joints when soldering pipes that are connected on
the drain line control fitting. Failure to do this could cause interior damage to the drain line flow control
fitting.
When assembling the installation-fitting package (inlet and outlet), connect the fitting to the plumbing
system first and then attach the nut, split ring and o-ring. Heat from soldering or solvent cements may
damage the nut, split ring or o-ring. Solder joints should be cool and solvent cements should be set before
installing the nut, split ring and o-ring. Avoid getting primer and solvent cement on any part of the o-rings,
split rings, and bypass valve or control valve.
Plug into an electrical outlet. Note: All electrical connections must be connected according to local codes.
(Be certain the outlet is uninterrupted.)
Install grounding strap on metal pipes, one end on inlet (copper) and other end to outlet (copper).
Note: No Chlorine should come into contact with the media. If chlorinating well, system must be in by-
pass position (see page #6)

5
Installation Fitting Assemblies
The installation fittings connect to the control valve or the bypass valve using nuts that ONLY REQUIRE
HAND TIGHTENING. Hand tighten nut connections between control valve and installation fittings, control
valve and bypass valve, and bypass valve and installation fittings allow for easy serviceability. Do not use
a pipe wrench to tighten nuts on installation fittings. Hand tighten only.
Split ring retainer design holds the nut on and allows load to be spread over the entire nut surface area
reducing the chance for leakage. The split ring design, incorporated into the installation fittings allows
approximately 2 degrees off axis alignment to the plumbing system. The installation fittings are designed
to accommodate minor plumbing misalignments but are not designed to support the weight of a system of
the plumbing.
When assembling the installation fitting package, connect the fitting to the plumbing system first and then
attach the nut, split ring and o-ring. Heat from soldering or solvent cements may damage the nut, split ring
or o-ring. Solder joints should be cool and solvent cements should be set before installing the nut, split
ring and o-ring. Avoid getting primer and solvent cement on any part of the o-rings. Split rings, bypass
valve or control valve. Solvent cements and primers should be used in accordance with the
manufacturer's instructions.
Slip the nut onto the fitting first, then the split ring second and the o-ring last. HAND TIGHTEN THE NUT.
If the fitting is leaking, tightening the nut will not stop the leak. Remove the nut, remove the fitting, and
check for damage or misalignment of the o-ring.
Do not use pipe dope or other sealant on threads. Teflon tape must be used on the threads of the 1" NPT
elbow and the ¼" NPT connection and on the threads for the drain line connection. Teflon tape is not
necessary on the nut connection or caps because of the o-ring seals.
Bypass Valve See page 6 for diagram and operation layout
The bypass valve easily connects to the control valve body using nuts that only require hand tightening.
Hand tighten nut connections between control valve and fittings, control valve and bypass valve, and
bypass valve and installation fittings allow for easy serviceability. The split ring retainer design holds the
nut on and allows load to be spread over the entire nut surface area reducing the chance for leakage. The
split ring design, incorporated into the bypass, allows approximately 2 degrees off axis alignment to the
plumbing system. The bypass is designed to accommodate minor plumbing misalignments but is not
designed to support the weight of a system of the plumbing.
Avoid getting primer and solvent cements on any part of the o-rings or split rings, bypass valve or control
valve. Do not use pipe dope or other sealant on threads. Teflon tape is not necessary on the caps
because of o-rings seals.
Do not use Vaseline, oils, or other unacceptable lubricants on o-rings. A silicon lubricant may be used on
black o-rings. All seals are self-lubricating E.PPM. for long life lubricating qualities.
Note: Quick connect 1" nut will fit around a ¾ " copper elbow (for ease of installation).
Important: See page 15 for installation of Air Injector and Off Air Tank.

6

7
Consumer Valve Programming Set Up
GENERAL OPERATION
When the system is operating on of
Two displays will be shown: time of
day or days until the next regeneration.
Pressing UP or DOWN will toggle
Between the two choices.
TO SET TIME OF DAY 1. Accessed by pressing SET HOUR.
In the event of a power outage, time 2. Adjust to the nearest hour using UP or
of day needs to be reset. All other DOWN. An arrow points to PM during
information will be stored in memory p.m. hours.
no matter how long the power outage. 3. Press SET HOUR to complete and return
Please complete the steps as shown to to normal operation.
The right. To access this mode, press
SET HOUR.
TO SET TIME OF 1. Accessed by pressing SET HOUR and
REGENERATION UP simultaneously for 3 seconds.
For initial set-up or to make adjustments, 2. Adjust time of regeneration hour using
Please complete the steps as shown to the UP or DOWN. An arrow points to PM
the right. Access the mode by pressing during p.m. hours. Simultaneously press
SET HOUR and UP simultaneously for SET HOUR and DOWN to return to
3 seconds. normal operation.
The user can initiate manual regeneration. The user has the option to request the manual regeneration at
the delayed regeneration time or to have the regeneration occur immediately. Simultaneously press the
UP + DOWN buttons to start regeneration at the next delayed regeneration time. If regeneration is to
occur today an arrow will point to regeneration. For immediate regeneration, simultaneously press and
hold the UP + DOWN buttons for three seconds.
When in regeneration step through the different regeneration cycles by simultaneously pressing the UP +
DOWN buttons.
User Please Note: Please do not attempt to go further into
valve programming other than time of day or regeneration
unless you have a full and comprehensive understanding of
all program features. Incorrect settings are not a warranty
issue and any service call or resetting of valve will be at the
user’s expense and may result in labor service charges.

8
Factory Setup of Blastersoft
Blastersoft setup of valve:
1) Fill cycle 9.5 lbs. of salt
2) Softening 120 minutes
3) Backwash cycle 10 Minutes
4) Brine cycle 60 minutes
5) Rinse cycle 4 minutes
6) Ozone draw cycle 30 minutes
Setting the relay: On time
First relay at: 75 minutes
Second relay (Off): 28 minutes
DAY OVERRIDE IS SET FOR 3 DAYS
Reminder:
The unit must go off every 3rd day if you want to remove Sulphur and Iron etc. You can
custom change anything you want but make sure the relay does not come on during the
Rinse Cycle or it will shut off the Ozone unit. Always add a few more minutes to the time
before Ozone and shorten the time on the second relay etc. to keep from water entering
the ozone unit or shutting off prematurely.
Black wire = COM+
Red wire = RLY
REVISED: JUNE 2015

9
User Displays
General Operation
When the system is operating one of two displays will be shown. Pressing UP or DOWN button will
alternate between the displays. One of the displays is always the current time of day (to the nearest hour).
The second display is the days remaining until next regeneration. If the days’ remaining is equal to one, a
regeneration will occur at the next preset regeneration time. The user can scroll between displays as
desired.
If the system has called for a regeneration that will occur at the present time of regeneration, the arrow will
point to Regen.
Regeneration Mode
Typically a system is set to regenerate at a time of low water usage. An example of a time with low water
usage is when a household is asleep. If there is a demand for water when the system is regenerating,
untreated water will be used.
When the system begins to regenerate, the display will change to indicate the cycle of the regeneration
process (see Table 3) that is occurring and an arrow will also point to Regen. The system will run through
the steps automatically and will reset itself provide treated water when the regeneration is completed.
Manual Regeneration
Sometimes there is need to regenerate the system, sooner than when the system calls for it, usually
referred to as a manual regeneration. There may be a period of heavy water usage because of guests or
a heavy laundry day.
To initiate a manual regeneration at the preset delayed regeneration time, simultaneously press UP-
DOWN buttons together and release. The arrow will point to the word Regen if a regeneration is expected
"tonight". To cancel the regeneration simultaneously press UP + DOWN buttons and release.
To initiate a manual regeneration immediately, simultaneously press UP + DOWN buttons together for
three seconds. The system will begin to regenerate immediately. The request cannot be cancelled. Note:
For softeners, if brine tank does not contain salt, fill with salt and wait at least two hours before
regenerating.
Set Time of Day
STEP 1U – Press SET HOUR
STEP 2U – Current: Set the clock to the closest hour by using the UP and DOWN button. An arrow points
to PM after 12. After a power outage, the time of day will need to be reset. Press SET HOUR to exit.
Power Loss
If the power goes out current timer of day will need to be reset. If the power goes out while the system is
regenerating, the cycle picks up where it was interrupted when the power returns. Note: The display will
flash if a power outage has occurred.
Error Message
If "E1," "E2" or "E3" appears on the display contact the help.
This indicates that the valve did not function properly.

10
BLASTER SOFT SET UP
NOTE: The Blaster Soft come factory set, only to be changed by trained/qualified technicians. Changes may be
necessary should the water quality change.
First Stage of Settings
Instructions
Description
1. Set time clock
As per normal operation
2. Press NEXT and DOWN
(or Minus Button) together
Board will go to the next setting
3. Press NEXT and DOWN
together a second time
Screen will flash this is the correct setting
4. Press NEXT
ALR will flash... press plus or minus button until it says OFF
5. Press NEXT
dp will flash… press plus or minus button until it says OFF
6. Press NEXT
Should read “Fill”… press plus or minus button until fill is displayed on the screen
7. Press NEXT
Should read “Backwash”… press plus or minus button until backwash is displayed on screen
8. Press NEXT
Should read “Brine Down”… press plus or minus button until Brine Down is displayed on
screen
9. Press NEXT
Should read “Rinse”… (this is just before ozone draw)press plus or minus button until Rinse
is displayed on screen
10. Press NEXT
Should read “Brine Down”… press plus or minus button until Brine Down is displayed on
screen
11. Press NEXT
Should read “End”… press Next until End is displayed on screen
12. Press NEXT
Screen will go back to clock setting
Second Stage of Settings
Instructions
Description
1. Press NEXT and DOWN
(or minus button) together
Should flash “Filtering or Softening”… press plus or minus button until Softening is displayed
on screen
2. Press NEXT
Should flash “ Fill”…Set at 9.5 lbs (or higher if iron count is high)
3. Press NEXT
Should flash “Backwash” … Set between 8 and 12 minutes
4. Press NEXT
Should flash “Brine Draw Down”… Set for 60 minutes
5. Press NEXT
Should flash “Rinse”… Set for 4 to 6 minutes
6. Press NEXT
Should flash “Brine Down”… Set for 30 up to 60 minutes
7. Press NEXT
Should flash “Capacity”… (unit size) usually set for 30,000 grains
8. Press NEXT
Should flash “Auto”… press plus or minus buttons until Auto is displayed on screen
9. Press NEXT
Should flash “Normal”… press plus or minus buttons until Normal is displayed on screen
10. Press NEXT
Should flash “Relay” … Set for “ON” (NOTE: This can be set in time or gallons, set for time)
11. Press NEXT
Screen Should flash… Set the time you want the ozone to come on, you this by adding all
the cycles together. Add fill time, backwash time, brine draw time, and rinse time. You may
need to put the unit through a manual regeneration to see each time, write them down and
add them up. For example if you have 84 minutes in time before your ozone brine draw set it
for 2 more minutes = 86 minutes
12. Press NEXT
Screen should flash… Set length of Ozone between 30 to 60 minutes
13. Press NEXT
Should flash “Call”…leave OFF
14. Press NEXT
Screen will go back to clock setting
•NOW ADJUST REGENS... EXAMPLE BAD WATER 10 Minute backwash (our example) and 60 minutes
brine… now you may want it to go off every day…or every second day…. So follow this instruction
•Press…Next and PLUS (+)… at the same time. “hardness “NA” will flash
•Press… NEXT….”regen” day will flash…. Press the plus (+) or minus (-) for the day to regen... if bad water
set it at 1… this means every day it will go off.
•Press, NEXT… back to clock setting.
NOTE: Your Blaster ozone draw time setting does not work on cycles, it works on time. This bases of design is
simple, however do not set the relay too soon, it is better to be 2 to 3 minutes longer than actual cycles add up to. If
you make it too short and the valve is in rinse the ozone will come on but won’t shut off when brine draw starts.
Lastly, when the unit has finished all the cycles and goes back to service mode the ozone will automatically shut off.

11

12

13
Example: Brine Line Installation

14
To Clean the CD Cell:
1.) Remove the CD Cell outlet tubing at the locations shown above.
2.) Disconnect the CD Cell H.V. wire from the frequency driver.
3.) Disconnect the CD Cell from its grounding clips and remove from generator.
4.) Run warm water through the inlet tubing until the water from the outlet tubing runs
clear and free or particulates.
5.) Use compressed air to completely dry the interior and exterior of the CD Cell prior to re-
installing.
6.) Re-install the CD Cell in reverse order of steps 1-4
CD Cell Inlet Port
CD Cell Outlet Port
CD Cell H.V. Wire Connection

15

16
Platinum
Drawings and
Part Numbers

17
Front Cover and Drive Assembly
Drawing No.
Order No.
Description
Quantity
1
CLK V334201
WD1HS Front Cover Assembly
1
2
CLK V310701
WD1 Motor
1
3
CLK V310601
WD1 Drive Bracket & Spring Clip
1
4a
CLK V3353HS
WD1HS PC Board No Relay
1
4b
CLK V3353HR
WD1HR PC Board w/Relay
5
CLK V3110
WD1 Drive Gear 12x36
3
6
CLK V3109
WD1 Drive Gear Cover
1
Not Shown
CLK V3186
WD1 AC ADAPTER 110V-12V
1
CLK V3186EU
WD1 AC ADAPTER 220-240V-12V EU
CLK V3186UK
WD1 AC ADAPTER 220-240V-12V UK
CLK V318601
WD1 AC ADAPTER CORD ONLY
Relay Specifications: To insure proper fit and correct operation the following relay and relay socket
manufactured by Idec or the exact equivalent should be used.
Idec Model and Description
Relay Socket
SH3B-05C 3 pole finger safe rail mount socket
Relay
RH2LB-U-AC12V 12vac, DPDT magnetic latching relay
The relay supplies 2 sets of dry contacts for user applications. The wiring of these
contacts is application specific.
Wiring For Correct On/Off Operation
PC Board Relay Terminal Block
Relay Socket
Top
#13
Center
#12 and #14
Bottom
#9

18
Drive Cap Assembly, Downflow Piston, Upflow Piston, Regenerant Piston and
Spacer Stack Assembly
Drawing No.
Order No.
Description
Quantity
1
CLK V3005
WD1 Spacer Stack Assembly
1
2
CLK V3004
Drive Cap ASY
1
3
CLK V3343
WD1HS Drive Back Plate
1
4a
CLK V3011*
WD1 Piston Downflow ASY
1
4b
CLK V301101*
WD1 Piston Upflow ASY
5
CLK V3174
WD1 Regenerant Piston
1
6
CLK V3135
O-ring 228
1
7
CLK V3180
O-ring 337
1
8
CLK V3105
O-ring 215 (Distributor Tube)
1
Not Shown
CLK V3001
WD1 Body ASY Downflow
1
CLK V300102
WD1 Mixing Valve Body ASY
CLK V3001UP
WD1 Body ASY Upflow
CLK V300102UP
WD1 Mixing Valve Body Upflow ASY
*V3011 is labeled with DN and V3011-01 is labeled with UP.
Note: The regenerant piston is not used in backwash only applications.

19
Drive Cap Assembly, Downflow Piston, Regenerant Piston and Spacer Stack
Assembly
Drawing No.
Order No.
Description
Quantity
1
CLK V3430
WD1.5 Spacer Stack Assembly
1
2
CLK V3004
Drive Cap ASY
1
3
CLK V3343
WD1HS Drive Back Plate
1
4
CLK V3407
WD1.5 Piston Downflow ASY
1
5
CLK V3174
WD1 Regenerant Piston
1
6
CLK V3135
O-ring 228
1
7
CLK V3180
O-ring 337
1
8
CLK V3358
O-ring 219 (Distributor Tube Opening 1.32")
1
CLK V3357
O-ring 218 (Distributor Tube Opening 32mm)
Not Shown
CLK V3020
WD1.25 Body ASY Downflow
(Distributor Tube Opening 1.32")
1
CLK V302001
WD1.25 Mixing Valve Body Downflow ASY
(Distributor Tube Opening 1.32")
CLK V302002
WD1.25 Body ASY Downflow
(Distributor Tube Opening 32mm)
CLK V302003
WD1.25 Mixing Valve Body Downflow ASY
(Distributor Tube Opening 32mm)
Note: The regenerant piston is not used in backwash only applications.

20
Injector Cap, Injector Screen, Injector, Plug and O-Ring
Drawing
No.
Order No. Description Quantity
1
CLK V3176
Injector Cap
1
2
CLK V3152
O-ring 135
1
3
CLK V3177
Injector Screen
1
4
CLK V30101Z
WD1 Injector ASY Z Plug
1
5
CLK V30101A
WD1 INJECTOR ASY A BLACK
1
CLK V30101B
WD1 INJECTOR ASY B BROWN
CLK V30101C
WD1 INJECTOR ASY C VIOLET
CLK V30101D
WD1 INJECTOR ASY D RED
CLK V30101E
WD1 INJECTOR ASY E WHITE
CLK V30101F
WD1 INJECTOR ASY F BLUE
CLK V30101G
WD1 INJECTOR ASY G YELLOW
CLK V30101H
WD1 INJECTOR ASY H GREEN
CLK V30101I
WD1 INJECTOR ASY I ORANGE
CLK V30101J
WD1 INJECTOR ASY J LIGHT BLUE
CLK V30101K
WD1 INJECTOR ASY K LIGHT GREEN
Not Shown
CLK V3170
O-ring 011
*
Not Shown
CLK V3171
O-ring 013
*
* The injector plug and the injector each contain one 011 (lower) and 013 (upper) o-ring.
Note: For upflow position, injector is located in the up hole and injector plug is in the
other hole. WS1HR&HS upflow bodies are identified by having the DN marking removed.
For a filter that only backwashes, injector plugs are located in both holes.
Table of contents
Popular Water Filtration System manuals by other brands

Parker
Parker Turbine 500MA instruction manual

Prince Castle
Prince Castle 107-H operating instructions

Kärcher
Kärcher WPC 600 SW manual

Chandler Systems
Chandler Systems DROP installation manual

BWT
BWT E1 NEU HWS Installation and operating instructions

Pall
Pall Profile Operating and Installation Procedures

Machinery World
Machinery World Tetra Centri A 614HGV-14C Service & Maintenance

Frymaster
Frymaster PF95LP Installation, operation & service parts manual

Everpure
Everpure Kleensteam II Single Installation and operation guide

WAM
WAM SILOTOP zero Assembly and main instructions for use and maintenance

Clear2O
Clear2O CWS100A Use and care book

B.David Company
B.David Company BDC6000BB Operating instructions manual