WaterTech REIONATOR PRO ULTRA RXU13 Manual

WHOLE HOUSE WATER CONDITIONER
with Triton Electronic Control Valve
INSTALLATION AND SERVICE MANUAL
IAPMO R&T certied to NSF/ANSI Standards 42 and 44
for meeting or exceeding industry standards of aesthetic
chlorine reduction and softening efciency.

IMPORTANT: Optimum sizing of the Reionator Pro Ultra™will result in a regeneration every 3 to 6 days.
IMPORTANT: Do not use with water that is microbiologically unsafe or of
unknown quality without adequate disinfection before or after the system.
PLUMBING CONNECTIONS
In virtually all circumstances, the Reionator Pro Ultra™ water system is at-
tached to the main incoming water line in the home (hereafter referred to
as the “main water line”) and conditions both the hot and the cold water
lines—including lines to drinking water and ice machine lines. Be sure you
are hooked up to the main water line and are feeding back into the main water
line which branches off to all other lines. Refer to the Plumbing Connection
Diagram (Figure 5, Page 5) for typical conguration.
IMPORTANT: Ensure that water entering the Reionator Pro Ultra™ is from
the main cold water line, especially if the Reionator Pro Ultra™ is not the rst
appliance in the plumbing line. Hot water entering the REIONATOR™ may
damage the resins and will void the warranty.
SYSTEM CAPACITY & REGENERATION SETTING
Refer to Table 1 to determine the volume of water that can be conditioned by
the size of the system you have installed. This capacity may be different from
ordinary softening systems, so please check the numbers.
If the valve is a timed valve, it regenerates at a predetermined number of days.
To calculate the number of days, divide the total capacity of the system (optimum
grains capacity divided by water hardness) by gallons per day (# of people times
75/gallons/person/day). For example, there are 4 people in a home and you are
installing a 32,000 grain Reionator Pro Ultra™ (which has an optimum capacity
of 16,080 according to the chart).
As an example, say you’ve tested the water and it has a hardness
of 7 grains/gallon.
Optimal grains capacity ÷ water hardness = total capacity.
No. of people x 75 gallons per day = gallons/day.
Total capacity ÷ gallons per day = No. of days to regenerate.
16,080 ÷ 7 = 2,300 gallons total capacity.
4 x 75 = 300 gallons per day water usage.
2300 - 300 gallons = 2000 gallons reserve capacity.
Reserve capacity = working capacity.
2000 ÷ 300 = 6.67 days before regeneration.
If the valve is a metered valve, which measures actual water use, then using
the above example, the setting would be about 2,000 gallons (allowing for a
reserve capacity of approximately one day of water use). 2,300 gallons (total
capacity) - 300 gallons per day (one day’s use) = 2,000 gallons.
IMPORTANT: As with any other appliance ALWAYS check your state and local
regulations regarding plumbing and electrical connections and placement of the
system before installation.
SPECIFICATIONS*
Single Tank Systems
MODEL
NUMBER
GRAINS
CAPACITY
MAXIMUM
RECOMMENDED
FLOW RATE (gpm)
CONTINUOUS FLOW
RATE (gpm)
@15 PSID
RESIN
TANK
BRINE
TANK
SYSTEM
HEIGHT
SALT
STORAGE
APPROX.
WEIGHT
RXU13 39,000 11.0 15 13” X 54” 18” X 33” 62” 200 lbs 175 lbs
* Indicates factory specications, which are not tested or validated by IAPMO R&T.
Refer to Performance Data Sheet on Page 18 for validated specications.
Operating Pressure Range = 20 to 125psi
We recommend that the system regenerate no more than two times per day per resin tank.
Installation Guide
2

3
SALT SETTING
Refer to the tables on the previous page to determine the
correct setting for the size system you are installing. This
setting may be different from ordinary softening systems, so
please check the numbers.
VALVE ASSEMBLY
The Triton control valve comes with a noryl plastic bypass valve
which simplies installation and is convenient to use should
the system need to be serviced in the future. Inlet and Outlet
connections are 3/4" or
1" pipe size.
PLACEMENT OF THE
REIONATOR PRO ULTRA™WATER SYSTEM
Install the Reionator Pro Ultra™ system into the existing cold water
supply line before the water heater and before any cold water outlet that
requires treatment. When selecting a location for the system, please keep
the following things in mind:
1. Choose a location that requires the least amount of piping. While this
is important from a cost standpoint, it is more important that the distance
between the Reionator Pro Ultra™ and the drain be as close as possible.
2. An approved 115/120 volt 60-cycle grounded receptacle should be
within reach of the 15 ft. transformer power pack.
3. Since salt or potassium chloride must be periodically added to the brine
tank, the location should be easily accessible.
4. All systems are designed to be installed in an inside and weather-
protected location. However, in a few states where climate conditions
allow, systems may be installed outside. If the system is installed outside,
it must be sheltered from rain and direct sunlight.
IMPORTANT: Damage to the Reionator Pro Ultra™ as a result of
exposure to the elements without the use of a weather cover will not be
covered under the limited lifetime warranty.
5. In some situations supplementary water treatment may be required
(sediment lter, iron removal, etc.). Make certain that adequate space is
available.
6. Outside faucets should be on the untreated hard water line in front of
the Reionator Pro Ultra™ system. Conditioned water is not needed for lawn
or garden watering. (The hose bib closest to the garage may have treated
water for washing cars.)
7. Do not locate the system where it or its connections (including the drain
and overow lines) will ever be subjected to temperatures under 40° F
(4.4°C) or over 110°F (43.3°C).
8. Select a location where the oor is level. If the oor is rough or uneven,
level it by placing the resin tank on 3/4" exterior plywood. Cut 1" larger on
all sides and then shim to level as needed.
9. Do not install any system close to a hot water heater with less than
a total run of 12 ft. of piping between the outlet of the Reionator Pro
Ultra™ system and the inlet to the heater. Water heaters can sometimes
overheat to the extent they will transmit heat back down the cold water
pipe into the Reionator Pro Ultra™ control valve. Hot water will severely
damage this equipment. (See plumbing connection diagram Fig. 5, Page 5).
Elbows, bends and straight pipe totalling 12 ft. will meet this requirement.
If necessary to place closer, install an approved check valve between the
discharge on the Reionator Pro Ultra™ and the inlet of the water heater.
Figure 3.
The Triton Control Valve
Installation

4
Installation
MOVING THE REIONATOR PRO
ULTRA™INTO POSITION
Keep the Reionator Pro Ultra™ resin tank upright and
move it into position. (The resin tank should always
be upright, even during storage and while being
transported to the site.) Level the system with shims.
Make sure the bypass valve or manifold is attached. At
this point, measure the piping required. Make sure that
the measurements allow for ttings.
BEFORE CUTTING
Shut-off the heat (gas or electricity) to the water heater.
Shut-off all water at the main supply valve. Drain the
piping by opening the highest faucet in the plumbing
system and the lowest faucet or drain plug. When the
pipes are drained, install the inlet and outlet piping to the
Reionator Pro Ultra™ control valve.
When the Reionator Pro Ultra™ is installed, move the
lever on the direct connect bypass valve to the bypass
position. On a three valve bypass system, close the inlet
and outlet valve and open the bypass valve. Water can
now be restored to the building during the rest of the
installation. Check for leaks and correct, if found.
DRAIN LINE CONNECTION
Install 1/2" I.D. plastic tubing from the hose barb located
on the right side of the main control valve to an open
drain. Do not connect the drain directly to a sewer
as this would violate sanitary codes. (See Figure
4a) If the drain line is extremely long, or discharges
above the main control valve, a back pressure may limit
the effectiveness of the injector, drawing brine during
regeneration. A siphon trap (a simple knot or taped loop)
at the outlet of the drain line is advisable to keep the drain
line full and assure correct ow during regeneration. (See
Figure 4b)
Where the drain line is elevated above the valve
and exceeds 20' in length, a 3/4" I.D. drain line is
recommended. Elbows or other ttings in the drain line
must be kept to a bare minimum. Installation should never
allow for rinsing of brine through water supply lines.
loop placed same
height as drain
connection on
Reionator Pro Ultra
™
Drain Elbow
3
air
gap
jaco
3/8
CAUTION:
Never connect drain line directly into drain,
sewer line or trap. Always allow an air gap
between the drain line and waste water to prevent
the possibility of sewage being back siphoned.
Locking
Clip
jaco
3/8
Figure 4a.
Drain Line Connection
PolyTube Insert
Drain Elbow Cap
Drain Line
Locking Clip
Figure 4b.
Drain Line Over Doorway

5
Installation
raw
water
in
raw water to
outside faucets
conditioned
water
in
check local codes
for minimum run
between Reionator Pro
unit and water heater
hot
cold
hot water heater
typical plumbing installation
Triton Bypass Valve
Important: Brass or Plastic yoke assembly (not shown)
is required to connect piping to the bypass valve
and is available in either NPT or solvent.
Figure 5.
Plumbing Connection

6
Installation
BRINE LINE CONNECTIONS
On all units, 3/8” O.D. x 1/4” I.D. brine line tubing must be
assembled at both the system control valve and the brine valve as
shown. The tubing is included in the brine tank.
Make sure the nylon insert is inside the ends of the plastic tube
when making the connection. Tighten up the compression nuts
rmly (tapered edge faces towards valve).
OVERFLOW CONNECTION
Install 1/2” I.D. tubing (not provided) to the brine tank overow tting
located on the side of the tank and run it to the drain. The brine
overow is provided in case a situation should arise causing too
much water to be added to the brine tank. This drain connection will
carry the excess to the drain and prevent ooding of the oor. No
liability will or can be assumed by the manufacturer of the Reionator
Pro Ultra™ system should ooding occur (See Figure 5).
Install the brine overow tubing even if the brine tank used with
your Reionator Pro Ultra™ includes a safety brine valve as a product
feature.

7
Installation
to
valve body
aircheck
brine
tank
Position mark on air check valve
at same level as surface of salt grating.
to
oor
drain
salt grating
air
check valve
positioning
mark
brine
well
cap
to
aircheck
overow elbow
brine well
Figure 7.
Air Check Valve Adjustment
brine line

Setting The Clock
8
Figure 8b
From the main TIME screen, press and release the
“Set Time” button. The screen should change to the
“Set Time” screen and the hour should ash.
Press and release either the or buttons until
the desired hour of the day is reached. AM or PM will
be indicated on the right side of the display.
5 6
Figure 8a

9
Figure 9a
Figure 9b
Figure 9c
Press and release the “Set Time” button to move to the
minute selection screen. The hours should stop ashing and
the minutes should begin ashing.
Press either the or buttons to change the minutes
as shown in Figure 9b.
When you’ve nished setting the time, press and release the
“Set Time” button. The minutes should stop ashing and the
valve should return to the main screen as shown in gure 9c.
5 6

Triton Control Valve
10
FUNCTION AND CYCLES OF OPERATION
This glass-lled Noryl1 fully automatic control valve is designed as the primary control center to direct and regulate all cycles
of a water softener or lter. When the Triton is set up as a softener, the Triton can be set to perform down ow or up ow
regeneration. When the Triton is set up as a lter, the Triton can be set to perform down ow regeneration or simply backwash.
The Triton can be set to regenerate on demand (consumption of a predetermined amount of water) and/or as a time clock (passage
of a particular number of days). The Triton can be set so that a softener can meet the NSF International efciency rating.
The Triton is compatible with a variety of regenerants and resin cleaners. The Triton is capable of routing the ow of water
in the necessary paths to regenerate or backwash water treatment systems. The injector regulates the ow of brine or other
regenerants. The Triton regulates the ow rates for backwashing, rinsing, and the replenishing of treated water into a regenerant
tank, when applicable.
The Triton is designed to deliver high service (27 gpm @ 15 psig) and backwash (27 gpm @ 25 psig) ow rates when the bypass
has straight ttings. The Triton uses no traditional fasteners (e.g. screws), instead clips, threaded caps and nuts and snap type
latches are used. Caps and nuts only need to be rmly hand tightened because radial seals are used. Tools required to service the
valve include one small blade screw driver, one large blade screw driver, pliers and a pair of hands. A plastic wrench is available
which eliminates the need for screwdrivers and pliers. Disassembly for servicing takes much less time than comparable products
currently on the market. Triton installation is made easy because the distributor tube can be cut ½” above to ½” below the top
of tank thread. The distributor tube is held in place by an o-ring seal and the Triton also has a bayonet lock feature for upper
distributor baskets.
The transformer power pack comes with a 15 foot power cord and is designed for use with the Triton. The transformer power pack
is for dry location use only. The Triton remembers all settings for two hours if the power goes out. After two hours, the only item
that needs to be reset is the time of day, all other values are permanently stored in the nonvolatile memory. The Triton does not
need batteries.
Table 2 shows the order of the cycles when the valve is set up as a softener. When the Triton is used as a down ow softener,
two backwashes always occur.
1 Noryl is a trademark of General Electric.
Table 2.

11
Bypass Valve Operation

12
FLUSHING, CONDITIONING AND SANITIZATION
Step 1. Make sure the system is in the “Bypass” position before turning the main water back on (see gure 12a above).
Make sure the drain line is connected securely to the control valve and is properly located over a drain.
Make sure the drain line is connected to the overow elbow (see gure 6, page 7) and is properly located over a drain.
Make sure the brine line is connected to both the air check in the brine well and the control valve. (see gure 7, page 7)
Make sure the control valve is plugged into an operating outlet with the correct voltage and is properly grounded.
Step 2: Press and Hold the REGEN button on the Triton until you hear the motor engage. This will initiate an immediate manual regeneration
of the system. Refer to the table on page 10 for Triton cycles of operation. Turn the bypass valve to Normal Operation (gure 12b
above) (you should hear water entering the system.) Wait a few minutes to ensure the control valve can draw water and does not
leak. If everything is working, press and release the REGEN button. You will hear the motor engage and move the piston into the
“Brine Dn” position. Check the brine line for leaks or suction. You should hear the valve drawing brine. Continue to skip cycles by
pressing and releasing the REGEN button (wait for the motor to stop before pressing REGEN) until you reach the “Brine Fill” position.
This ensures that water will go to the brine tank. Fill tank 3” to 4” above salt grid. Make sure enough water is in the brine tank to
dissolve the correct amount of salt for regeneration (1 gallon of water will dissolve 3 lbs. of sodium chloride). Allow the brine tank to
ll with water to air check level. If the system needs 6 lbs. of salt to regenerate, then at least 2-1/2 gallons of water must be in the
brine tank above air check in the brine well. The extra 1/2 gallon is an additional measure for evaporation or loss. (6 ÷ 3 = 2 gallons of
water plus 1/2 gallon). Fill the brine tank with salt. (We recommend potassium chloride (KCl) instead of rock salt.) Once the brine tank
is lled to this level, press REGEN once more to return the valve to service. You should hear the motor engage for a short period and
then a long period.
Figure 12a.
Bypass Operation
Figure 12b.
Normal Operation
Did you connect the drain line securely to the
Triton’s drain elbow?
Did you connect the brine line securely to the
Triton’s brine elbow?
Starting Up The System
STOP

13
Step 3: To ensure sanitary conditions in the mineral and brine tanks, place 1.5 ounces common household bleach into the brine tank. Press and
hold the REGEN button for 3 seconds to move the control valve into “1st Backwash” position. Once the motor stops, press and hold the
REGEN button to move the control valve to the “Brine Dn” position. This cycle normally takes about 60 minutes, however 10 minutes
should be sufcient to pull the chlorine from the brine tank. After 10 minutes, press and hold the REGEN button to move the control valve
to the “2nd Backwash” position. Let the valve complete this cycle and also the “Brine Rinse” and “Brine Fill” cycles which will come
next. Once the valve has completed the “Brine Fill” cycle it will automatically return to service. In step 5 you will set the valve to “Regen
Today” so that it will regen tonight at the specied time. If there is any residual chlorine, it should be removed tonight.
Step 4: Make sure that the bypass valve is completely set in the “Normal Operation” position. Let the water in the taps of the building run for
several minutes to purge the unconditioned water out of the pipes. After several minutes, take a water sample and test for hardness
from the running tap. If a hardness test reads “soft” water then the installation is correct
Step 5: Press and release the REGEN button. You should see “Regen Today” appear on the LCD screen. This will instruct the control valve to
regenerate tonight at the specied time (usually after everyone is asleep).
Step 6: Drain hot water heater and let it rell with conditioned water. We suggest draining the hot water by turning on the hot water taps in
the house. We recommend doing this just prior to bedtime.

14
Step 1. To set the hardness on your Triton control valve, press the NEXT and buttons simultaneously. You
will see the display change from the time of day to the “Set HARDNESS” screen as above. Simply press
the or to change the grains per gallon of hardness.
SETTING HARDNESS, REGENERATION DAY AND REGENERATION TIME
The Triton control valve on your Reionator Pro Ultra™ comes pre-set from the factory to perform as a typical softener
valve. However, there are certain settings that are specic to the customer’s water situation that cannot be set at
the factory. This section will guide you through these settings.
Setting Up The Triton Valve
IMPORTANT: Please be sure you know your water hardness before setting this screen. A hardness setting that is too low will result in depleted capacity
and water that is not softened. A hardness setting that is too high will result in more frequent regeneration and increased salt usage.
5
5
6

15
Step 3. From the “Set REGEN DAY” screen, press the NEXT button. You should now see the “Set REGEN TIME” screen
(shown above). Simply press the or button to change the time of day, on the regeneration day set in the
previous step you wish your REIONATOR™ to regenerate. Normally 2:00 AM is appropriate for most situations.
Step 2. From the “Set HARDNESS” screen, press the NEXT button. You should now see the “Set REGEN DAY” screen
(shown above). Simply press the or button to change the day override.
IMPORTANT: This screen is used
to set the day override to force
regeneration on the specied number of
days since last regeneration regardless
of water usage. Changing this setting is
usually not necessary.
IMPORTANT: During regeneration,
hard (raw) water will exit the system.
Be sure that the regeneration time is
set during the night when NO water
is used.
5
5
6
6

Troubleshooting
16
PROBLEM CAUSE CORRECTION
1. Reionator Pro Ultra™fails to regenerate. A. Bypass Valve in “Bypass” position. A. Move bypass to “Normal” position.
B. Valve may be disconnected B. Make sure power is supplied to the
from power. transformer power pack and that the
transformer power pack is securely
connected to the PC Board of the Triton.
C. Meter turbine is jammed or C. Check meter turbine for foreign matter
stalled. replace if necessary.
D. Defective meter. D. Replace meter.
E. Hardness is set too low. E. Check your water hardness
and follow procedure to set correct
hardness.
2. Reionator Pro Ultra™delivers hard water. A. Bypass valve is set to “Bypass.” A. Move bypass to “Normal” position.
B . N o s a l t i n b r i n e t a n k . B . A d d s a l t t o b r i n e t a n k a n d
maintain salt level above water level.
C. Injectors or screen plugged. C. Clean or replace injectors
and screen.
D. Insufcient water owing into D. Check brine tank ll time and
brine tank. clean brine line ow control if plugged.
E. Hot water tank hardness. E. Repeated ushings of the hot water
tank is required.
F. Leak at distributor tube. F. Make sure distributor tube is not cracked
and check “O” ring and tube pilot.
G. Internal valve leak. G. Replace seals and spacers and/or piston.
3. Unit uses too much salt. A. Hardness set too high. A. Check water hardness and follow
correct procedure to enter water hardness.
B. Excessive water in brine tank. B. See problem #7.
4. Loss of water pressure. A. Iron buildup in line to water A. Clean line to water conditioner.
conditioner.
B. Iron buildup in water conditioner. B. Clean control and add resin cleaner to
resin bed and increase frequency of
regeneration.
C. Inlet of control plugged due to foreign C. Remove piston and clean control.
material broken loose from pipes by
recent work done on plumbing system.
5. Loss of resin through drain line. A. Air in water system. A. Assure that well system has proper air
eliminator control and check for dry
well condition.
6. Iron in conditioned water. A. Fouled resin bed. A. Check backwash, brine draw and brine
tank ll, increase frequency of
regeneration and increase backwash time.

17
PROBLEM CAUSE CORRECTION
7A. Excessive water in brine tank. A. Plugged drain line ow control. A. Clean ow control.
7B. Salt water in service line. B. Plugged injector system. B. Clean injector and replace screen.
C. Plugged or kinked drain line. C. Clean and/or straighten
the drain line.
D. Foreign material in brine valve. D. Clean or replace brine valve.
E. Foreign material in brine line ow E. Clean brine line ow control .
control.
8. Reionator Pro Ultra™ fails to draw brine. A. Brine line ow control is plugged. A. Clean brine line ow control.
B. Injector is plugged. B. Clean or replace injectors.
C. Injector screen plugged. C. Replace screen.
D. Line pressure is too low. D. Increase line pressure (line
pressure must be at least
20 PSI at all times).
E. Connections to brine elbow and valve E. Check ttings for correct
and brine elbow in brine tank drawing assembly of nut parts. Check
air to see if nuts are snug.
F. Internal Control Leak. F. Change seals and spacers and/or
position assembly.
10. Drain ows continuously. A. Foreign material in control. A. Remove piston assembly and
inspect bore, remove foreign
material and check control in
various regeneration positions.
B. Internal control leak. B. Replace seals and/or piston
assembly.
C. Control valve jammed in brine or C. Replace seals and/or piston
backwash position. assembly.
GENERAL SERVICE HINTS FOR METER CONTROL
Problem: Softener delivers hard water
Hard water delivered from the Reionator Pro Ultra™ may indicate that the unit has exceeded it’s reserve capacity.
Correction: Check your water hardness and make sure that you have set the hardness correctly. Hardness set too low will cause
your Reionator Pro Ultra™ not to regenerate often enough.
Correction: Check to ensure a good connection from the meter to the PC board on the Triton. Check for loose or broken wires
and reconnect to the PC board if necessary.
Correction: Check the meter turbine to ensure that it rotates freely. Check for foreign matter in the meter shaft. Replace meter
if necessary.
Correction: From the time of day screen on the Triton, press the NEXT button to see the softener usage. If there is a tap or hose bib nearby
that is connected to the system, place a 5-gallon bucket underneath and ll it. Check the capacity remaining to see if it has
decreased by 5 gallons. If not, replace the meter. If replacing the meter does not solve the problem, replace the PC board.

18
INPUT VOLTAGE: 110-120VAC @ 60Hz
OPERATING VOLTAGE: 12VAC @ 60Hz
MIN WORKING PRESSURE: 20-150 psi 138-861 kPa
MIN OPERATING TEMPERATURE: 40°-110° F 4.4-43.30° C
MAX FLOW TO DRAIN DURING REGENERATION: 2.2 gpm 8.3 l/min
FOR GENERAL INSTALLATION CONDITIONS, PLEASE SEE CARE & USE GUIDE.
THE REIONATOR PRO ULTRA™ IS A DIR (DEMAND INITIATED REGENERATION) SOFTENER WHICH
COMPLIES WITH SPECIFIC PERFORMANCE
SPECIFICATIONS INTENDED TO MINIMIZE THE USE OF REGENERANT BRINE IN ITS OPERATION.
THIS WATER SOFTENER CONFORMS TO NSF/ANSI 42 FOR REDUCTION OF AESTHETIC CHLO-
RINE AND NSF/ANSI 44 FOR SOFTENING EFFICIENCY AS VERIFIED AND SUBSTANTIATED BY
TEST DATA. WHILE TESTING WAS PERFORMED UNDER LABORATORY CONDITIONS, DUE TO
VARYING WATER CONDITIONS ACTUAL PERFORMANCE MAY VARY.
THE REIONATOR PRO ULTRA HAS BEEN TESTED ACCORDING TO NSF/ANSI 42 FOR THE
REDUCTION OF THE SUBSTANCES LISTED IN THE TABLE TO THE RIGHT. THE CONCENTRA-
TION OF THE SUBSTANCE IN THE WATER ENTERING THE SYSTEM WAS REDUCED TO A
CONCENTRATION LESS THAN OR EQUAL TO THE PERMISSIBLE LIMIT FOR WATER LEAVING
THE SYSTEM AS SPECIFIED BY NSF/ANSI 42.
THE REIONATOR PRO ULTRA IS NOT INTENDED FOR USE IN TREATING WATER THAT IS MI-
CROBIOLOGICALLY UNSAFE OR OF UNKNOWN QUALITY WITHOUT ADEQUATE DISINFECTION
BEFORE AND/OR AFTER THE SYSTEM.
USAGE OF THE REIONATOR PRO ULTRA IN A MANNER OTHER THAN PRESCRIBED IN THE
MANUFACTURER’S WARRANTY WILL VOID THE REIONATOR LIMITED LIFETIME WARRANTY.
(SEE OWNER’S MANUAL FOR FULL WARRANTY INFORMATION.)
AS WITH ANY APPLIANCE, PROPER OPERATION AND MAINTENANCE IS REQUIRED
TO ENSURE TROUBLE-FREE OPERATION. PLEASE CONSULT YOUR LOCAL AUTHO-
RIZED WATERTECH DEALER FOR SERVICE.
Model *1Softening Efciency @
Stated Salt Setting
(Grains Per Pound)
2Softening Capacity @
Stated Salt Setting
(Grains Per Gallon)
Maximum Recom-
mended Hardness
(Grains Per Gallon)
Maximum Recommend-
ed Flow Rate / Service
Flow Rate (Gallons per
minute)
Maximum Flow to
Drain During
Regeneration
(Gallons per minute)
@PSID Total Bed
Depth (FT3)
RXU13 3998 @ 4.7 lbs. 18,901 @ 4.7 lbs. 45 11.0 2.2 15 2.350
Model
Aesthetic Chlorine
Reduction (Gallons)
RXU13 1180
* The efciency is only valid at the stated salt dosage and maximum service ow.
1 Softening efciency values based on NaCl as the regenerant salt.
2.Softening capacity values based on NaCl as the regenerant salt.
Specications
WaterTech recommends the use of Potassium Chloride (KCl) as a regenerant salt.
Efciency rated softeners shall have a rated
salt efciency of not less than 3350 grains
of total hardness exchange per pound of
salt, and shall not deliver more than its
listed rating.

19
Model RXU13
PRODUCT DESCRIPTION PART NUMBER
Resin Tank 13” x 54” 09-03-1354BLK-Xmid
Brine Tank 09-04-1833BKC
Brine Grid 18” 09-04-119
Brine Well Assembly 3.5” X 30” 09-04-240
Brine Overow Elbow 07-05-004
Triton Control Valve 13-V1CCDM
Replacements Parts List

06-01-020 10-03-2017
800 FREEPORT PARKWAY, #150, COPPELL, TX 75019 | 888.254.8412
www.watertech.com
Table of contents
Other WaterTech Water Dispenser manuals
Popular Water Dispenser manuals by other brands

Rasonic
Rasonic RWD-HC3400/W Operation manual

GE
GE GXMH31H00 Owner's manual and installation instructions

US Water Systems
US Water Systems Flex ECS-20 Installation and operation manual

WaterLogic
WaterLogic WL2000IT Technical manual

Philips
Philips WP3890 user manual

WaterLogic
WaterLogic WL900 installation guide

Electrolux
Electrolux ED30S instruction manual

CSI
CSI Signature Series Service manual

Hatco
Hatco ATMOSPHERIC AWD-12 Series Installation and operating manual

WaterLogic
WaterLogic WL400 Series Troubleshooting

Soleus Air
Soleus Air WA2-02-50A user manual

3M
3M Cuno CFS100WS Installation and operating instructions