All information in this drawing is
the property of The Watt Stopper
Inc. and cannot be copied or used
without the written approval of The
Watt Stopper Inc.
Installation Instructions
CI-12
360° PIR Occupancy Sensor
SPECIFICATIONS
Voltages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12VDC, +2V/-0.5V
Current Consumption. . . . . . . . . . . . . . @12VDC, 28mA Maximum
Isolated Relay Rating . . . . . . . . . . . . . . . . . 1A @24VDC or 24VAC
Time Adjustment . . . . . . . . . . . . . . . . . . . 30 seconds–30 minutes
Sensitivity Adjustment . . . . . . . . . . . . . . . . . . minimum/maximum
SENSOR ADJUSTMENT
The sensor comes factory preset and ready for operation.
If testing of operation is desired:
• Remove the sensor’s cover (twist).
• Refer to the DIP switch settings chart below for switch configurations.
• Make sure that office furniture and fixtures are in place.
1. Confirm the Override DIP switch is set to Normal (DIP switch #4 to OFF)
2. Restore power and turn on the system interfacing with the Isolated Relay.
• There is a one minute warm-up when power is initially restored to the
sensor before the sensor works properly.
3. Set Time Delay to minimum: DIP switches #1 and 2 to ON (30 seconds).
4. Set Sensitivity to maximum: DIP switch #3 to ON.
5. Replace the sensor’s cover.
6. Move away from sensor and be still. The sensor should time-out after
30 seconds and the isolated relay contacts should return to their “normal”
condition (Normally Open or Closed), see Wiring Directions diagram.
Note: If the sensor does not time-out or the isolated relay does not return to
its normal condition, move farther away or out of sight of the sensor, or see
Unwanted Sensor Activations under Troubleshooting.
7. Reset the Time Delay to the desired delay (DIP switches #1 and 2).
Santa Clara, CA 95050 USA
1(800)879-8585 1(972)578-1699
REV. DESCRIPTION REV. DATE APPROVED
1 Release to Production
2 ECO# 032096-1
3 ECO# 073098-1
WARRANTY INFORMATION
The Watt Stopper®, Inc. warranties its products to be free of defects in materials
and workmanship for a period of five years. There are no obligations or liabilities
on the part of The Watt Stopper, Inc. for consequential damages arising out of or
in connection with the use or performance of this product or other indirect
damages with respect to loss of property, revenue, or profit, or cost of removal,
installation or reinstallation.
U.S. Patents:
4,757,204
4,787,722
Des360,842
Putting a Stop to Energy Waste®
Santa Clara CA 95050 USA ☎1(800)879-8585 1(972)578-1699
86-0467-00r3 9/99
4-FOLD: 2-sided
MATERIAL: Paper, white, glossy
80# Book
FLAT (cut) SIZE: 15" W x 6" H
FOLDED SIZE: 3.75"W x 6"H
INK COLOR: Black
4-FOLD
Drawn by: HUCKABONE
Marketing:
Marketing:
Engineering:
Doc Control:
Sheet: 1 of 2 Scale: 1 : 1
the Watt Stopper Inc.
SANTA CLARA, CALIFORNIA
Title:
CI-12 Installation Instructions
Drawing #: Original Drwg. Date: 16 JUN 95 Rev #:
86-0467-00 Rev. Date: 2 SEP 99 3
PRINTING SPECIFICATIONS:
Check Our Web Site For FAQs: www.wattstopper.com
DIP Switch # 1234
Normal
Override
30 seconds
10 minutes
20 minutes
30 minutes
Minimum
Maximum
Sensitivity
Sensitivity
–
–
–
–
–
–
=ON –=OFF
1234
ON
LED
DIP Switch Control
for Time Delay,
Sensitivity, and
Override
1234
ON
DIP SWITCH SETTINGS
.=Factory Presets
.
.
.
TROUBLESHOOTING
≠CAUTION≠
USE PROPER SAFETY PRECAUTIONS WHEN
WORKING WITH OR NEAR HIGH VOLTAGE
LED does not flash with motion:
1. Determine if the lens is masked in the direction being tested (see Masking).
2. Check that the Sensitivity setting is set to maximum (DIP switch #3 to ON).
3. Check that the RED and BLACK wire connections from sensor are secure.
4. Check that 12VDC is between the RED and BLACK wire from the sensor.
• If it is present, the problem may be with the sensor.
Try another sensor (if available).
Isolated relay not functioning properly:
1. Check that Time Delay settings are correct (DIP switches #1 and 2).
2. Check Sensitivity setting. Also see Unwanted Sensor Activations, below.
3. Check that all wire connections from sensor are correct and secure.
4. Using proper precautions, check that there is voltage to the isolated relay.
5. Check that 12VDC is between the RED and BLACK wire from the sensor.
6. Use an ohmmeter to check the function of the isolated relay:
• Turn off the power connected to the isolated relay wires (if applicable).
- With motion in front of the sensor’s lens, check that the connection
between the GREEN and ORANGE wires is open.
- With motion in front of the sensor’s lens, check that the connection
between the YELLOW and ORANGE wires is closed.
• Turn Sensitivity and Time Delay to minimum, cover the sensor’s lens with
a cloth (not your hand), be still and allow the sensor to time-out.
- Check that the connection between the GREEN and ORANGE wires is closed.
- Check that the connection between the YELLOW and ORANGE wires is open.
Unwanted sensor activations (LED flashes):
Possible causes
1. People moving or walking outside of the desired coverage area, but in view
of the sensor and within it’s range (see Coverage Patterns and Placement).
2. HVAC vents with heavy air flow.
Possible solutions
1. Masking (see Masking).
2. Setting the Sensitivity to minimum if necessary (DIP switch #3).
3. Relocating the sensor.
Sensor Override:
If the sensor fails, set DIP switch #4 to Override position (DIP Switch # 4 to ON).
This overrides the sensor and sets the circuits to “on”.
✆Call 1(800)879-8585 For Technical Support✆
ORDERING INFORMATION
Catalog# Description
CI-12 12VDC Occupancy Sensor
with Extended Range Lens (Standard)
CI-12-1 12VDC Occupancy Sensor
with High Density /Reduced Range Lens
CI-24 24VAC or 24VDC Occupancy Sensor
with Extended Range Lens (Standard)
CI-24-1 24VAC or 24VDC Occupancy Sensor
with High Density /Reduced Range Lens
All information in this drawing is the property of The Watt Stopper Inc. and cannot
be copied or used without the written approval of The Watt Stopper Inc.
Drawn by: HUCKABONE
Sheet: 2 of 2
the Watt Stopper Inc.
SANTA CLARA, CALIFORNIA
Title:
CI-12 Installation Instructions
Scale: Drawing # Original Drawing Date Rev #
1 : 1 86-0467-00 16Jun95 3
DESCRIPTION
The CI-12 is a 12VDC Passive Infrared (PIR) occupancy sensor which inte-
grates with HVAC or EMS systems. The CI-12 provides isolated relay contacts
that are Normally Open or Normally Closed, based on occupancy.
PIR sensing systems are passive systems which react to changes in infrared
energy (moving body heat) within the coverage area. PIR sensors must directly
“see” motion of an occupant to detect them, so careful consideration must be
given to sensor placement.
COVERAGE PATTERNS
The CI-12 has a multi-cell, multi-tier Fresnel lens with a field of view of 360°.
The sensor has two lens pattern options. The Extended Range Lens will cover
up to 1200 sq ft and 22 feet from the sensor when mounted at 8 feet. The
High Density/Reduced Range Lens will cover up to 500 sq ft and 12 feet from
the sensor when mounted at 8 feet.
Coverage shown in the diagrams below is maximum and represents coverage
for half-step, walking motion, with no barriers or obstacles.
8 ft
22 ft 13 ft 7 ft 3 ft 0 3 ft 7 ft 13 ft 22 ft
Typical
desk-top
level
44 ft
DRAWING NOT TO SCALE
8 ft
12 ft 12 ft3 ft 3 ft5 ft 5 ft7 ft 7 ft9 ft 9 ft0
Typical
desk-top
level
24 ft
Extended Range Lens (Standard)
CI-12
High Density/Reduced Range Lens
CI-12-1
PLACEMENT
The effective coverage distances may be slightly less than the maximum sens-
ing distance (see Coverage Patterns), depending upon obstacles such as fur-
niture or partitions, and this must be considered when planning the number of
sensors and their positioning. See the list below for approximate coverage dis-
tances for different types of motion.
Approximate coverage, for a mounting height of 8 feet:
Lens option Walking motion Workstation (hand motion)
Extended Range up to 22 ft radius (1200 sq ft) 12 ft radius (500 sq ft)
High Density up to 12 ft radius (500 sq ft) 9 ft radius (300 sq ft)
The CI-12 sensor can be mounted at various heights. When you will be
mounting at heights other than 8 feet, be aware that as you decrease the
mounting height, you will decrease the range and increase the sensitivity to
smaller motions. Conversely, when you increase the height, you will increase
the range and decrease the sensitivity to smaller motions. At heights of more
than 12 -14 feet, you may start to significantly reduce sensitivity.
Often the best location to install a
CI-12 in a closed office is off-center
(see fig.1). Avoid placing a sensor
directly in line with an open door in
which it has a clear view out, as the
sensor may detect people walking by.
For open office areas with partitions it is
best to place sensors over intersections of
four workstations (see fig. 2).
Also avoid placing the sensors close to
air ducts, as rapid air currents or the
differences in temperatures may cause
false activations. For large areas of
coverage use multiple sensors.
CI-12
36'
36'
CI-12
12'
18'
fig. 1
fig. 2
Check Our Web Site For FAQs: www.wattstopper.comCheck Our Web Site For FAQs: www.wattstopper.com
A 4-S junction box can be used with a 3" mud-ring when local building codes
mandate that low voltage connections be contained in a junction box.
Otherwise a 3" mud-ring or the provided ceiling attachment ring can be used.
IMPORTANT: If the lens will be masked, the junction box or mud ring may
need to be positioned so that the mask is oriented properly when the sensor is
installed (see Masking).
Cut a hole in the ceiling tile—if using a:
• Ceiling attachment ring (provided)—cut about 2-3/4" to 3" in diameter.
• 3" mud ring—cut the hole to accommodate.
To assemble the sensor:
1. If using the ceiling attachment ring, bend the securing straps up so the sensor
housing can be inserted, and attach it to the sensor with the provided screws.
2. Attach the mask, if using, into the lens recess and onto the securing pins of
the cover.
3. Attach the cover to the rear housing—align tabs on inside of cover to
notches on outside perimeter of rear housing, place cover on sensor, and
twist clockwise to lock.
4. Insert the assembled sensor into the ceiling hole, and if using the mask,
turn the sensor so that the unmasked part of the lens is toward and centered on
the area to be covered.
5. Bend the ceiling attachment ring straps behind the hole to secure (or
attach sensor to mud ring with screws).
Ceiling
2-3/4" to 3" hole
(if using 3" mud-ring,
cut to accomodate)
Ceiling attachment ring
(bend behind ceiling
to secure)
Rear housing
Cover (with lens)
Mask secures
to pins on cover
Mask (optional)
cut for desired coverage
INSTALLATION
≠CAUTION≠
TURN POWER OFF AT CIRCUIT BREAKER BEFORE INSTALLING SENSOR
MASKING
An insert (mask) is supplied to allow elimination of coverage in unwanted areas.
The mask is cut as needed and mounted onto anchor pins in the sensor’s cover.
IMPORTANT: Do not use the mask if full coverage is desired.
IMPORTANT: Before securing the sensor in the mounting location, the
assembled sensor must be turned so the unmasked portion of the lens
faces the coverage area (the blue masked area is visible through the lens).
IMPORTANT: For an already installed sensor—If the sensor can NOT be turned,
then the mask must be cut so that when installed it will be oriented correctly
(note the location of the securing pins in the cover and note that the cover
turns as it locks into position).
Note: At the edges of the masking, there is a small area of reduced sensitivity,
illustrated as the lighter area in the examples below.
Cut mask into sections
for desired coverage,
shown right.
Mask
Reduced sensitivityCoverage area
WIRING DIRECTIONS
≠CAUTION≠
TURN POWER OFF AT CIRCUIT BREAKER BEFORE WIRING SENSOR
• Connect +12VDC Supply to the RED and Return to the BLACK wire from
the sensor.
Isolated Relay: (Rated for 1A @24VDC or 24VAC)
Connect the wires necessary to the application that requires this output.
• GREEN (Normally Closed)—Open when occupancy is detected
• ORANGE (Common) (must be used for proper operation)
• YELLOW (Normally Open)—Closed when occupancy is detected
✆Call 1(800)879-8585 For Technical Support✆ ✆ Call 1(800)879-8585 For Technical Support✆
+12VDC, +2V/-0.5V RED
Wires
12VDC Return BLACK
Isolated Relay Outputs
Normally Closed Contact GREEN
Common ORANGE
Normally Open Contact YELLOW
CI-12
Sensor
All information in this drawing
is the property of The Watt
Stopper Inc. and cannot
be copied or used without the
written approval of The Watt
Stopper Inc.
Santa Clara, CA 95050 USA
1(800)879-8585 1(972)578-1699
Installation Instructions
REV. DESCRIPTION REV. DATE APPROVED
1 Release to Production
2 ECO# 032096-1
3 ECO# 073098-1
CI-24
360° PIR Occupancy Sensor
WARRANTY INFORMATION
The Watt Stopper®, Inc. warranties its products to be free of defects in materials
and workmanship for a period of five years. There are no obligations or liabilities
on the part of The Watt Stopper, Inc. for consequential damages arising out of or
in connection with the use or performance of this product or other indirect
damages with respect to loss of property, revenue, or profit, or cost of removal,
installation or reinstallation.
SPECIFICATIONS
Voltages . . . . . . . . . . . . . . . . . . . . . . . 24VAC or 24VDC, ±10%
Current Consumption . . . . . . . . . . . . . @24VAC, 37mA Maximum
@24VDC, 30mA Maximum
Isolated Relay Rating . . . . . . . . . . . . . . . . 1A @24VDC or 24VAC
Time Adjustment . . . . . . . . . . . . . . . . . . . 30 seconds–30 minutes
Sensitivity Adjustment . . . . . . . . . . . . . . . . . . Minimum/Maximum
U.S. Patents:
4,757,204
4,787,722
Des360,842
TROUBLESHOOTING
≠CAUTION≠
USE PROPER SAFETY PRECAUTIONS WHEN
WORKING WITH OR NEAR HIGH VOLTAGE
LED does not flash with motion:
1. Determine if the lens is masked in the direction being tested (see Masking).
2. Check that the Sensitivity setting is set to maximum (DIP switch #3 to ON).
3. Check that the RED and BLACK wire connections from sensor are secure.
4. Check that 24VAC or 24VDC is between the RED and BLACK wire from the sensor.
• If it is present, the problem may be with the sensor. Try another sensor
(if available).
Isolated relay not functioning properly:
1. Check that Time Delay settings are correct (DIP switches #1 and 2).
2. Check Sensitivity setting. Also see Unwanted Sensor Activations, below.
3. Check that all wire connections from sensor are correct and secure.
4. Using proper precautions, check that there is voltage to the isolated relay.
5. Check that 24VAC or 24VDC is between the RED and BLACK wire from the sensor.
6. Use an ohmmeter to check the function of the isolated relay:
• Turn off the power connected to the isolated relay wires (if applicable).
- With motion in front of the sensor’s lens, check that the connection
between the GREEN and ORANGE wires is open.
- With motion in front of the sensor’s lens, check that the connection
between the YELLOW and ORANGE wires is closed.
• Turn Sensitivity and Time Delay to minimum, cover the sensor’s lens with
a cloth (not your hand), be still and allow the sensor to time-out.
- Check that the connection between the GREEN and ORANGE wires is closed.
- Check that the connection between the YELLOW and ORANGE wires is open.
Unwanted sensor activations (LED flashes):
Possible causes
1. People moving or walking outside of the desired coverage area, but in view
of the sensor and within it’s range (see Coverage Patterns and Placement).
2. HVAC vents with heavy air flow.
Possible solutions
1. Masking (see Masking).
2. Setting the Sensitivity to minimum if necessary (DIP switch #3).
3. Relocating the sensor.
Sensor Override:
If the sensor fails, set DIP switch #4 to Override position (DIP Switch # 4 to ON).
This overrides the sensor and sets the circuits to “on”. Putting a Stop to Energy Waste®
Santa Clara CA 95050 USA ☎1(800)879-8585 1(972)578-1699
86-0468-00r3 9/99
✆Call 1(800)879-8585 For Technical Support✆Check Our Web Site For FAQs: www.wattstopper.com
4-FOLD: 2-sided
MATERIAL: Paper, white, glossy
80# Book
FLAT (cut) SIZE: 15" W x 6" H
FOLDED SIZE: 3.75"W x 6"H
INK COLOR: Black
4-FOLD
Drawn by: HUCKABONE
Marketing:
Marketing:
Engineering:
Doc Control:
Sheet: 1 of 2 Scale: 1 : 1
the Watt Stopper Inc.
SANTA CLARA, CALIFORNIA
Title:
CI-24 Installation Instructions
Drawing #: Original Drwg. Date: 16 JUN 95 Rev #:
86-0468-00 Rev. Date: 2 SEP 99 3
PRINTING SPECIFICATIONS:
ORDERING INFORMATION
Catalog# Description
CI-24 24VAC or 24VDC Occupancy Sensor
with Extended Range Lens (Standard)
CI-24-1 24VAC or 24VDC Occupancy Sensor
with High Density /Reduced Range Lens
CI-12 12VDC Occupancy Sensor
with Extended Range Lens (Standard)
CI-12-1 12VDC Occupancy Sensor
with High Density /Reduced Range Lens
SENSOR ADJUSTMENT
The sensor comes factory preset and ready for operation.
If testing of operation is desired:
• Remove the sensor’s cover (twist).
• Refer to the DIP switch settings chart below for switch configurations.
• Make sure that office furniture and fixtures are in place.
1. Confirm the Override DIP switch is set to Normal (DIP switch #4 to OFF)
2. Restore power and turn on the system interfacing with the Isolated Relay.
• There is a one minute warm-up when power is initially restored to the
sensor before the sensor works properly.
3. Set Time Delay to minimum: DIP switches #1 and 2 to ON (30 seconds).
4. Set Sensitivity to maximum: DIP switch #3 to ON.
5. Replace the sensor’s cover.
6. Move away from sensor and be still. The sensor should time-out after
30 seconds and the isolated relay contacts should return to their “normal”
condition (Normally Open or Closed), see Wiring Directions diagram.
Note: If the sensor does not time-out or the isolated relay does not return to
its normal condition, move farther away or out of sight of the sensor, or see
Unwanted Sensor Activations under Troubleshooting.
7. Reset the Time Delay to the desired delay (DIP switches #1 and 2).
DIP Switch # 1234
Normal
Override
30 seconds
10 minutes
20 minutes
30 minutes
Minimum
Maximum
Sensitivity
–
–
–
–
–
–
=ON –=OFF
1234
ON
LED
DIP Switch Control
for Time Delay,
Sensitivity, and
Override
1234
ON
DIP SWITCH SETTINGS
.=Factory Presets
.
.
.
All information in this drawing is the property of The Watt Stopper Inc. and cannot
be copied or used without the written approval of The Watt Stopper Inc.
Drawn by: HUCKABONE
Sheet: 2 of 2
the Watt Stopper Inc.
SANTA CLARA, CALIFORNIA
Title:
CI-24 Installation Instructions
Scale: Drawing # Original Drawing Date Rev #
1 : 1 86-0468-00 16 JUN 95 3
DESCRIPTION
The CI-24 is a 24VAC or 24VDC Passive Infrared (PIR) occupancy sensor
which integrates with HVAC or EMS systems. The CI-24 provides isolated relay
contacts that are Normally Open or Normally Closed, based on occupancy.
PIR sensing systems are passive systems which react to changes in infrared
energy (moving body heat) within the coverage area. PIR sensors must directly
“see” motion of an occupant to detect them, so careful consideration must be
given to sensor placement.
COVERAGE PATTERNS
The CI-24 has a multi-cell, multi-tier Fresnel lens with a field of view of 360°.
The sensor has two lens pattern options. The Extended Range Lens will cover
up to 1200 sq ft and 22 feet from the sensor when mounted at 8 feet. The
High Density/Reduced Range Lens will cover up to 500 sq ft and 12 feet from
the sensor when mounted at 8 feet.
Coverage shown in the diagrams below is maximum and represents coverage
for half-step, walking motion, with no barriers or obstacles.
8 ft
22 ft 13 ft 7 ft 3 ft 0 3 ft 7 ft 13 ft 22 ft
Typical
desk-top
level
44 ft
DRAWING NOT TO SCALE
8 ft
12 ft 12 ft3 ft 3 ft5 ft 5 ft7 ft 7 ft9 ft 9 ft0
Typical
desk-top
level
24 ft
Extended Range Lens (Standard)
CI-24
High Density/Reduced Range Lens
CI-24-1
PLACEMENT
The effective coverage distances may be slightly less than the maximum sens-
ing distance (see Coverage Patterns), depending upon obstacles such as fur-
niture or partitions, and this must be considered when planning the number of
sensors and their positioning. See the list below for approximate coverage dis-
tances for different types of motion.
Approximate coverage, for a mounting height of 8 feet:
Lens option Walking motion Workstation (hand motion)
Extended Range up to 22 ft radius (1200 sq ft) 12ft radius (500 sq ft)
High Density up to 12 ft radius (500 sq ft) 9ft radius (300 sq ft)
The CI-24 sensor can be mounted at various heights. When you will be
mounting at heights other than 8 feet, be aware that as you decrease the
mounting height, you will decrease the range and increase the sensitivity to
smaller motions. Conversely, when you increase the height, you will increase
the range and decrease the sensitivity to smaller motions. At heights of more
than 12-14 feet, you may start to significantly reduce sensitivity.
Often the best location to install a
CI-24 in a closed office is off-center
(see fig.1). Avoid placing a sensor
directly in line with an open door in
which it has a clear view out, as the
sensor may detect people walking by.
For open office areas with partitions it is
best to place sensors over intersections of
four workstations (see fig. 2).
Also avoid placing the sensors close to
air ducts, as rapid air currents or the
differences in temperatures may cause
false activations. For large areas of coverage
use multiple sensors.
CI-24
36'
36'
CI-24
12'
18'
fig. 1
fig. 2
✆Call 1(800)879-8585 For Technical Support✆ ✆ Call 1(800)879-8585 For Technical Support✆Check Our Web Site For FAQs: www.wattstopper.com Check Our Web Site For FAQs: www.wattstopper.com
A 4-S junction box can be used with a 3" mud-ring when local building codes
mandate that low voltage connections be contained in a junction box.
Otherwise a 3" mud-ring or the provided ceiling attachment ring can be used.
IMPORTANT: If the lens will be masked, the junction box or mud ring may
need to be positioned so that the mask is oriented properly when the sensor is
installed (see Masking).
Cut a hole in the ceiling tile—if using a:
• Ceiling attachment ring (provided)—cut about 2-3/4" to 3" in diameter.
• 3" mud ring—cut the hole to accommodate.
To assemble the sensor:
1. If using the ceiling attachment ring, bend the securing straps up so the sensor
housing can be inserted, and attach it to the sensor with the provided screws.
2. Attach the mask, if using, into the lens recess and onto the securing pins of
the cover.
3. Attach the cover to the rear housing—align tabs on inside of cover to
notches on outside perimeter of rear housing, place cover on sensor, and
twist clockwise to lock.
4. Insert the assembled sensor into the ceiling hole, and if using the mask,
turn the sensor so that the unmasked part of the lens is toward and cen-
tered on the area to be covered.
5. Bend the ceiling attachment ring straps behind the hole to secure (or
attach sensor to mud ring with screws).
Ceiling
2-3/4" to 3" hole
(if using 3" mud-ring,
cut to accomodate)
Ceiling attachment ring
(bend behind ceiling
to secure)
Rear housing
Cover (with lens)
Mask secures
to pins on cover
Mask (optional)
cut for desired coverage
INSTALLATION
≠CAUTION≠
TURN POWER OFF AT CIRCUIT BREAKER BEFORE INSTALLING SENSOR
WIRING DIRECTIONS
≠CAUTION≠
TURN POWER OFF AT CIRCUIT BREAKER BEFORE WIRING SENSOR
• Connect 24VAC or +24VDC Supply to the RED and Return to the BLACK
wire from the sensor.
Isolated Relay: (Rated for 1A @24VDC or 24VAC)
Connect the wires necessary to the application that requires this output.
• GREEN (Normally Closed)—Open when occupancy is detected
• ORANGE (Common) (must be used for proper operation)
• YELLOW (Normally Open)—Closed when occupancy is detected
24VAC or +24VDC, ±10% RED
Wires
24VAC or 24VDC Return BLACK
Isolated Relay Outputs
Normally Closed Contact GREEN
Common ORANGE
Normally Open Contact YELLOW
CI-24
Sensor
MASKING
An insert (mask) is supplied to allow elimination of coverage in unwanted areas.
The mask is cut as needed and mounted onto anchor pins in the sensor’s cover.
IMPORTANT: Do not use the mask if full coverage is desired.
IMPORTANT: Before securing the sensor in the mounting location, the
assembled sensor must be turned so the unmasked portion of the lens
faces the coverage area (the blue masked area is visible through the lens).
IMPORTANT: For an already installed sensor—If the sensor can NOT be turned,
then the mask must be cut so that when installed it will be oriented correctly
(note the location of the securing pins in the cover and note that the cover
turns as it locks into position).
Note: At the edges of the masking, there is a small area of reduced sensitivity,
illustrated as the lighter area in the examples below.
Cut mask into sections
for desired coverage,
shown right.
Mask
Reduced sensitivityCoverage area

This manual suits for next models

1

Other wattstopper Accessories manuals

wattstopper DSW-301 User manual

wattstopper

wattstopper DSW-301 User manual

wattstopper LMDC-100 User manual

wattstopper

wattstopper LMDC-100 User manual

wattstopper CH-250 User manual

wattstopper

wattstopper CH-250 User manual

wattstopper DT-305 User manual

wattstopper

wattstopper DT-305 User manual

wattstopper LMLS-600 User manual

wattstopper

wattstopper LMLS-600 User manual

wattstopper UT-305 User manual

wattstopper

wattstopper UT-305 User manual

wattstopper CI-200 User manual

wattstopper

wattstopper CI-200 User manual

wattstopper CI-355 User manual

wattstopper

wattstopper CI-355 User manual

wattstopper Legrand LMPC-100 User manual

wattstopper

wattstopper Legrand LMPC-100 User manual

wattstopper FSP-211 User manual

wattstopper

wattstopper FSP-211 User manual

wattstopper WN-100 User manual

wattstopper

wattstopper WN-100 User manual

wattstopper CI-200 Series User manual

wattstopper

wattstopper CI-200 Series User manual

wattstopper LMPW-102 User manual

wattstopper

wattstopper LMPW-102 User manual

wattstopper PW-100 User manual

wattstopper

wattstopper PW-100 User manual

wattstopper DSW-301 User manual

wattstopper

wattstopper DSW-301 User manual

wattstopper PW-301 User manual

wattstopper

wattstopper PW-301 User manual

wattstopper RD‑250 User manual

wattstopper

wattstopper RD‑250 User manual

wattstopper CX-100 User manual

wattstopper

wattstopper CX-100 User manual

wattstopper PW-100 User manual

wattstopper

wattstopper PW-100 User manual

wattstopper EW-100-120 User manual

wattstopper

wattstopper EW-100-120 User manual

wattstopper LMDX-100 User manual

wattstopper

wattstopper LMDX-100 User manual

wattstopper Legrand FM-105 User manual

wattstopper

wattstopper Legrand FM-105 User manual

wattstopper DW 100 User manual

wattstopper

wattstopper DW 100 User manual

wattstopper PW-103N User manual

wattstopper

wattstopper PW-103N User manual

Popular Accessories manuals by other brands

Omron FZ2 Series user manual

Omron

Omron FZ2 Series user manual

PCB Piezotronics TLD208C02 Installation and operating manual

PCB Piezotronics

PCB Piezotronics TLD208C02 Installation and operating manual

Suunto Tank POD user guide

Suunto

Suunto Tank POD user guide

Novalynx 200-WS-03D instruction manual

Novalynx

Novalynx 200-WS-03D instruction manual

PCB Piezotronics IMI SENSORS HT640 B Series Installation and operating manual

PCB Piezotronics

PCB Piezotronics IMI SENSORS HT640 B Series Installation and operating manual

Scale House ILW operating manual

Scale House

Scale House ILW operating manual

DURKOPP ADLER 367 - INSTRUCTIONS FOR FITTING FOR KIT 0367... instructions

DURKOPP ADLER

DURKOPP ADLER 367 - INSTRUCTIONS FOR FITTING FOR KIT 0367... instructions

Batco 1355 Operation manual

Batco

Batco 1355 Operation manual

Goclever GC3DPI user manual

Goclever

Goclever GC3DPI user manual

Axminster Woodturning Stylish Twist Pen Kit manual

Axminster

Axminster Woodturning Stylish Twist Pen Kit manual

PCB Piezotronics ICP 483C30 Installation and operating manual

PCB Piezotronics

PCB Piezotronics ICP 483C30 Installation and operating manual

Comunello Automation DART SLIM Installation and user manual

Comunello Automation

Comunello Automation DART SLIM Installation and user manual

Philips GC920 user manual

Philips

Philips GC920 user manual

Niles CE-DS6 Specification sheet

Niles

Niles CE-DS6 Specification sheet

Dometic LA-03 installation instructions

Dometic

Dometic LA-03 installation instructions

Paramount Fitness Ultra UV 004-422-2025-00 Installation & operation manual

Paramount Fitness

Paramount Fitness Ultra UV 004-422-2025-00 Installation & operation manual

LEEC SL2 operating instructions

LEEC

LEEC SL2 operating instructions

KSR KUEBLER AF-ADF Mounting and operating instructions

KSR KUEBLER

KSR KUEBLER AF-ADF Mounting and operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.