UNIT DESCRIPTION AND OPERATION
The DW Dual Technology Wall Switch sensors combine advanced passive infrared
(PIR) and ultrasonic technologies into one unit. The combined technologies help
to eliminate false triggering even in difficult applications.
Selectable operating modes allow the sensor to turn a load ON, and hold it ON
as long as either or both technologies detect occupancy. After no movement is
detected for the selected time delay, the lights switch off. A “walk-through” mode
can turn lights off after only 3 minutes, if no activity is detected after 30 seconds
following an occupancy detection.
The DW-100 has one relay and one ON/OFF button. The DW-200 contains two
relays and two ON/OFF buttons to allow control of one or two loads independently.
Pressing a button toggles the state of the corresponding relay.
DW sensors contain a light level sensor. If adequate daylight is present, the
sensor holds the load OFF until light levels drop, even if the area is occupied. In
the DW-200, light level only affects the load on Relay 2. Users can overrule this
function by pressing the ON/OFF button. See Light Level Adjustment.
Turning ON the Load (ON Mode)
The relays are programmed independently for either Auto ON or Manual ON. In
either mode, the load can be turned ON or OFF using the ON/OFF button.
Manual ON
DIP 8 ON
for Relay 1
DIP 9 ON
for Relay 2
With an ON Mode DIP switch in the ON position, the occupant
must press the ON/OFF button to turn ON the load. The sensor
keeps the load ON until no motion is detected for the selected
time delay. There is a 30 second re-retrigger delay. If occupancy
re-triggers during the delay (see Trigger Mode), the sensor turns
the load back ON. After the re-trigger delay elapses the ON/OFF
button must be pressed to turn ON the load.
Auto ON
DIP 8 OFF
for Relay 1
DIP 9 OFF
for Relay 2
With an ON Mode DIP switch in the OFF position, the load turns
ON and OFF automatically based on occupancy. If the load is
turned OFF manually, Presentation Mode operation applies. This
prevents the load from turning ON automatically after it was
deliberately turned OFF. Pressing the button to turn lights ON
returns the sensor to Auto ON mode.
Model # Relay Default ON Mode DIP switch # Setting
DW-100 1 Manual ON 8 ON
DW-100-347 1 Manual ON 8 ON
DW-200 1 Auto ON 8 OFF
2 Manual ON 9 ON
Presentation Mode is a feature of the Auto ON mode. When both relays are
manually turned OFF the DW holds the lights OFF until no motion has been
detected for the duration of the Time Delay. With subsequent occupancy, the DW
turns the load ON. If both relays are ON and one relay is manually turned OFF this
relay remains OFF until both the Time Delay and retrigger delay expires for the
relay that is ON, after that time the ON Mode control settings again apply.
Call 800.879.8585 for Technical Support