WEG CFW100 - IOADR Quick guide

Infrared Remote Control and
I/O Expansion Module
Módulo de Expansión de I/O
y Control Remoto Infrarrojo
Módulo de Expansão de
I/O e Controle Remoto
Infravermelho
CFW100 - IOADR
Installation, Configuration and Operation Guide
Guía de Instalación, Configuración y Operación
Guia de Instalação, Configuração e Operação
Motors | Automation | Energy | Transmission & Distribution | Coatings


Summary / Índice
English
EspañolPortuguês
SUMMARY
1 SAFETY INFORMATION...............................5
1.1 SAFETY WARNINGS ....................................5
1.2 PRELIMINARY RECOMMENDATIONS.......5
2 GENERAL INFORMATION...........................5
3 CONTENT OF THE PACKAGE ....................5
4 INSTALLATION OF THE ACCESSORY.......6
5 CONFIGURATIONS ......................................6
6 USE OF THE ACCESSORY ........................10
APPENDIX A – FIGURES...............................29
ÍNDICE
1 INFORMACIONES DE SEGURIDAD .........13
1.1 AVISOS DE SEGURIDAD............................13
1.2 RECOMENDACIONES PRELIMINARES...13
2 INFORMACIONES GENERALES...............13
3 CONTENIDO DEL EMBALAJE ..................13
4 INSTALACIÓN DEL ACCESORIO..............14
5 CONFIGURACIONES .................................14
6 UTILIZACIÓN DEL ACCESORIO ..............18
ANEXO A – FIGURAS.....................................29
ÍNDICE
1 INFORMAÇÕES DE SEGURANÇA............21
1.1 AVISOS DE SEGURANÇA ..........................21
1.2 RECOMENDAÇÕES PRELIMINARES.......21
2 INFORMAÇÕES GERAIS ...........................21
3 CONTEÚDO DA EMBALAGEM..................21
4 INSTALAÇÃO DO ACESSÓRIO .................22
5 CONFIGURAÇÕES .....................................22
6 UTILIZAÇÃO DO ACESSÓRIO ..................26
ANEXO A – FIGURAS.....................................29


Infrared Remote Control and I/O
Expansion Module
English
CFW100 | 5
1 SAFETY INFORMATION
1.1 SAFETY WARNINGS
NOTE!
Only use the I/O expansion module and
infrared remote control (IOADR) on WEG
CFW100 series inverters with firmware
from version V2.10 up (see P023).
It is recommended to read the CFW100
user manual before installing or operating
this accessory.
This guide contains important information
for the correct understanding and proper
operation of this module.
1.2 PRELIMINARY RECOMMENDATIONS
ATTENTION!
Always disconnect the general power
supply before connecting or disconnecting
the accessories of the CFW100 frequency
inverter.
Wait for at least ten minutes for the full
discharge of the inverter.
2 GENERAL INFORMATION
This guide provides directions for the installation,
configuration and operation of the remote control and
I/O expansion module (CFW100-IOADR).
3 CONTENT OF THE PACKAGE
Upon receiving the product, check if the package
contains:
Accessory in anti-static package.
NTC Sensor with 1-meter cable.
Infrared (IR) remote control.
1.5-meter infrared receiver cable.

Infrared Remote Control and I/O
Expansion Module
English
6 | CFW100
Installation, configuration and operation guide.
4 INSTALLATION OF THE ACCESSORY
The CFW100-IOADR is easily connected to the CFW100
frequency inverter by means of the plug-and-play
concept. The procedures below must be observed for
the proper installation and start-up:
1. With the inverter powered down, remove the front
cover from the inverter (Figure A1 on page 29).
2. Fit the accessory to be installed as shown in Figure
A1 on page 29.
3. Fit the cable with the IR receiver in “P1” on the
accessory as shown in Figure A1 on page 29.
4. Power up the inverter.
5 CONFIGURATIONS
The CFW100-IOADR connections must be done to the
I/O expansion connector as per Table 1 on page 7.
The pins of the accessory connector are shown in Figure
A3 on page 30.

Infrared Remote Control and I/O
Expansion Module
English
CFW100 | 7
Table 1: Signals of the I/O expansion connector
Connector Description Specifications
6NTC NTC
Sensor
Input.
NTC 10 K B3435 K.
7GND Reference
0 V.
Not interconnected to PE.
8AI1 Analog
Input 1
(voltage).
Isolated voltage input, level:
0 to 10 Vdc.
Resolution: 10 bits.
Impedance: 100 kΩ.
Programmable functions.
Maximum voltage
accepted: 30 Vdc.
9AI1 Analog
Input 1
(current).
Isolated current input, level
(0 to 20) mA or (4 to 20) mA.
Resolution: 10 bits.
Impedance: 500 Ω.
Programmable functions.
Maximum voltage
accepted: 30 Vdc.
10 + 10 V Reference
+ 10 V for
potentio-
meter.
Power supply: + 10 Vdc.
Maximum capacity: 50 mA.
Tolerance: ±5 %.
11 DO1-RL-C Digital
Output 1
(Common
point of
relay 1).
1 relay with NO contact.
Maximum voltage: 240 Vac.
Maximum current: 0.5 A.
Minimum current: > 1 uA
Programmable functions.
12 DO1-RL-NO Digital
Output 1
(NO point
of relay 1).
13 DO2-RL-C Digital
Output 2
(Common
point of
relay 2).
14 DO2-RL-NO Digital
Output 2
(NO point
of relay 2).
15 DO3-RL-C Digital
Output 3
(Common
point of
relay 3).
16 DO3-RL-NO Digital
Output 3
(NO point
of relay 3).
Counter-
clockwise
≥5 k
Clockwise

Infrared Remote Control and I/O
Expansion Module
English
8 | CFW100
ATTENTION!
For the proper operation of the CFW100
inverter with the CFW100-IOADR module, the
parameters P308, P310, P311 and P312 must
be programmed with the factory settings.
For further details, refer to the programming
manual of the CFW100 V2.0X or up.
In order to use the analog input with voltage signal,
pin 8 of the I/O expansion connector must be used.
For current signal, pin 9 of the same connector must is
available. Related parameters must also be set as per
Table 2 on page 8.
Table 2: Configurations of connectors to select the type of
analog input signal on the CFW100-IOADR
Input Signal Connector Signal
Range
Parameter
Setting
AI1
Voltage 8 0 ... 10 V P233 = 0 or 2
Current 90 ... 20 mA P233 = 0 or 2
4 ... 20 mA P233 = 1 or 3
NOTA!
The firmware version of the CFW100-IOADR
accessory can be viewed in parameter P024
of the CFW100 inverter.
Information about parameter configuration of the
CFW100 inverter related to the CFW100-IOADR
accessory is presented in Table 3 on page 9.

Infrared Remote Control and I/O
Expansion Module
English
CFW100 | 9
Table 3: List of parameters related to the accessory
CFW100-IOADR
Param. Description Adjustable Range Factory
Setting Proper.
P013
(*)
DO3 to
DO1 Status
0 to 7 (hexa)
Bit 0 = DO1
Bit 1 = DO2
Bit 2 = DO3
ro
P027 Accessory
Config.
0 = No Accessories
1 = Reserved
2 = CFW100-IOAR
3 = CFW100-CCAN
4 = CFW100-CBLT
5 = Reserved
6 = CFW100-IOADR
ro
P275
(*)
DO1
Output
Function
0 = Not Used
1 = F* ≥ Fx
2 = F ≥ Fx
3 = F ≤ Fx
4 = F = F*
5 = Not Used
6 = Is > Ix
7 = Is < Ix
8 and 9 = Not Used
10 = Remote
11 = Run
12 = Ready
13 = Without Fault
14 = Without F070
15 = Not Used
16 = Without F021/F022
17 = Not Used
18 = Without F072
19 = 4-20 mA OK
20 = Not Used
21 = Clockwise
22 to 23 = Not used
24 = Ride-Through
25 = Pre-Charge OK
26 = With Fault
27 = Not Used
28 = SoftPLC
29 to 34 = Not Used
35 = Without Alarm
36 = Without Fault/Alarm
37 = Function 1 Application
38 = Function 2 Application
39 = Function 3 Application
40 = Function 4 Application
41 = Function 5 Application
42 = Function 6 Application
43 = Function 7 Application
44 = Function 8 Application
13 cfg
P276
(*)
DO2 Output
Function
See options of P275 0 cfg
P277
(*)
DO3 Output
Function
See options of P275 0 cfg

Infrared Remote Control and I/O
Expansion Module
English
10 | CFW100
Param. Description Adjustable Range Factory
Setting Proper.
P375
(*)
NTC
Temperature
0 to 100 °C ro
P840
(*)
Control
Key Status
2 or 802 = On/Off
6 or 806 = Arrow down
8 or 808 = Arrow up
9 or 809 = Forward/Reverse
B or 80B = Programmer
F or 80F = Special
Function 01
10 or 810 = Special
Function 02
11 or 811 = Special
Function 03
ro
P842
(*)
Quick
view 1 IR
0 to 999 2
P843
(*)
Quick
view 2 IR
0 to 999 375
NOTE!
(*) Parameters available only when the
accessory is connected.
6 USE OF THE ACCESSORY
For the proper operation of the CFW100 frequency
inverter with the CFW100-IOADR accessory, some
procedures must be observed:
1. The remote control must be directed to the cable end
(IR receiver), as shown in Figure A2 on page 30.
2. The maximum distance between the remote control
and IR receiver is eight meters.
NOTE!
Before using the infrared remote control,
remove the battery protection in the lower
part of the control.
Periodically check the need to replace the
remote control battery.
The functionalities of the remote control keys can be
seen in Table 4 on page 11. The remote control can
be seen in Figure 1 on page 11.

Infrared Remote Control and I/O
Expansion Module
English
CFW100 | 11
Figure 1: Remote Control (infrared)
Table 4: Operation of the remote control keys
Key Description
Start/Stop Motor.
Browse CFW100 display.
Browse CFW100 display.
Commute view between P842 and
P843 parameters.
Confirm / Program parameter on the
CFW100 display.
Special Function 1. (*)
Special Function 2. (*)
Special Function 3. (*)
(*) Function available when SoftPLC application is installed.
Otherwise, this key has no function.

Infrared Remote Control and I/O
Expansion Module
English
12 | CFW100
NOTE!
When the NTC sensor is not connected to the
accessory, the CFW100 frequency inverter will
show 999 °C (1830 °F) in parameter P375.
If pins 6 and 7 (accessory connector) are
short circuited, the value shown in P375 will
be 0 °C (32 °F).
ATTENTION!
Some keys of the remote control have different
functions according to the operating status
of the CFW100 frequency inverter when the
user application (P903 = 0) is installed and it
is running (P900 = 4).

Módulo de Expansión de I/O y
Control Remoto Infrarrojo
CFW100 | 13
Español
1 INFORMACIONES DE SEGURIDAD
1.1 AVISOS DE SEGURIDAD
¡NOTA!
Utilizar solamente el módulo de expansión
de I/O y control remoto infrarrojo (IOADR)
en los convertidores WEG serie CFW100
con versión de firmware a partir de V2.10
(ver P023).
Se recomienda la lectura del manual del
usuario del CFW100 antes de instalar u
operar este accesorio.
El contenido de esta guía provee
informaciones importantes para el correcto
entendimiento y el buen funcionamiento de
este módulo.
1.2 RECOMENDACIONES PRELIMINARES
¡ATENCIÓN!
Desconecte siempre la alimentación
general antes de conectar o desconectar
los accesorios del convertidor de
frecuencia CFW100.
Aguarde por lo menos 10 minutos para
garantizar la desenergización completa
del convertidor.
2 INFORMACIONES GENERALES
Esta guía orienta en la instalación, configuración y
operación del módulo de expansión de I/O y control
remoto (CFW100-IOADR).
3 CONTENIDO DEL EMBALAJE
Al recibir el producto, verifique si el embalaje contiene:
Accesorio en embalaje anti-estático.
Sensor NTC con cable de 1 m.
Control remoto infrarrojo (IR).

Módulo de Expansión de I/O y
Control Remoto Infrarrojo
14 | CFW100
Español
Cable receptor infrarrojo de 1,5 m.
Guía de instalación, configuración y operación.
4 INSTALACIÓN DEL ACCESORIO
El CFW100-IOADR es fácilmente conectado al
convertidor de frecuencia CFW100, utilizando el
concepto “plug-and-play”. Los procedimientos abajo
descritos deben ser seguidos para una correcta
instalación y puesta en funcionamiento:
1. Con el convertidor desenergizado, retire la tapa
frontal del mismo (Figura A1 en la página 29).
2. Encaje el accesorio a ser instalado, conforme es
indicado en la Figura A1 en la página 29.
3. Encaje el cable con receptor IR en “P1” en el
accesorio, como en la Figura A1 en la página 29.
4. Energice el convertidor.
5 CONFIGURACIONES
Las conexiones del accesorio CFW100-IOADR deben
ser realizadas en el conector de expansión de I/O,
conforme la Tabla 1 en la página 15. Los terminales
del conector del accesorio son presentados en la Figura
A3 en la página 30.

Módulo de Expansión de I/O y
Control Remoto Infrarrojo
CFW100 | 15
Español
Tabla 1: Señales del conector de expansión de I/O
Conector Descripción Especificaciones
6NTC Entrada
Sensor NTC.
NTC 10 K B3435 K.
7GND Referencia
0 V.
No interconectado con
el PE.
8AI1 Entrada
Analógica 1
(tensión).
Entrada aislada en tensión,
nivel: 0 a 10 Vcc.
Resolución: 10 bits.
Impedancia: 100 kΩ.
Funciones programables.
Tensión máxima admitida:
30 Vcc.
9AI1 Entrada
Analógica 1
(corriente).
Entrada aislada en
corriente, nivel (0 a 20) mA
o (4 a 20) mA.
Resolución: 10 bits.
Impedancia: 500 Ω.
Funciones programables.
Tensión máxima admitida:
30 Vcc.
10 + 10 V Referencia
+ 10 V para
potenciómetro.
Fuente de tensión: + 10 Vcc.
Capacidad máxima:
50 mA.
Tolerancia: ±5 %.
11 DO1-RL-C Salida Digital 1
(Punto común
del relé 1).
1 relé con contacto NA.
Tensión máxima: 240 Vca.
Corriente máxima: 0,5 A.
Corriente mínima: > 1 uA
Funciones programables.
12 DO1-RL-NO Salida Digital
1 (Punto NA
del relé 1).
13 DO2-RL-C Salida Digital 2
(Punto común
del relé 2).
14 DO2-RL-NO Salida Digital
2 (Punto NA
del relé 2).
15 DO3-RL-C Salida Digital 3
(Punto común
del relé 3).
16 DO3-RL-NO Salida Digital
3 (Punto NA
del relé 3).
Anti-
Horario
≥5 k
Horario
¡ATENCIÓN!
Para el correcto funcionamiento del convertidor
CFW100 con el módulo CFW100-IOADR, los
parámetros P308, P310, P311 y P312 deben
estar ajustados con los valores del estándar
de fábrica. Para más detalles, consulte el
manual de programación del CFW100 V2.0X,
o superior.

Módulo de Expansión de I/O y
Control Remoto Infrarrojo
16 | CFW100
Español
Para utilizar la entrada analógica con señal en tensión,
se debe usar el terminal 8 del conector de expansión
de I/O. Para señal en corriente, se dispone del terminal
9 del mismo conector. Se debe, también, ajustar los
parámetros relacionados, conforme la Tabla 2 en la
página 16.
Tabla 2: Configuraciones de los conectores para
selección del tipo de señal en la entrada analógica, en el
CFW100-IOADR
Entrada Señal Conector Rango de la
Señal
Ajuste de
Parámetros
AI1
Tensión 8 0 ... 10 V P233 = 0 ó 2
Corriente 90 ... 20 mA P233 = 0 ó 2
4 ... 20 mA P233 = 1 ó 3
NOTA!
La versión de firmware del accesorio
CFW100-IOADR puede ser visualizada en
el parámetro P024 del convertidor CFW100.
Las informaciones sobre la configuración de los
parámetros del convertidor CFW100, relacionadas al
accesorio CFW100-IOADR, son presentadas en la Tabla
3 en la página 17.

Módulo de Expansión de I/O y
Control Remoto Infrarrojo
CFW100 | 17
Español
Tabla 3 : Relación de parámetros asociados al accesorio
CFW100-IOADR
Parám. Descripción Rango de
Valores
Ajuste de
Fábrica Prop.
P013
(*)
Estados
DO3 a
DO1
0 a 7 (hexa)
Bit 0 = DO1
Bit 1 = DO2
Bit 2 = DO3
ro
P027 Config.
Accesorio
0 = Sin Accesorio
1 = Reservado
2 = CFW100-IOAR
3 = CFW100-CCAN
4 = CFW100-CBLT
5 = Reservado
6 = CFW100-IOADR
ro
P275
(*)
Función de
la Salida
DO1
0 = Sin Función
1 = F* ≥ Fx
2 = F ≥ Fx
3 = F ≤ Fx
4 = F = F*
5 = Sin Función
6 = Is > Ix
7 = Is < Ix
8 y 9 = Sin Función
10 = Remoto
11 = Run
12 = Ready
13 = Sin Falla
14 = Sin F070
15 = Sin Función
16 = Sin F021/F022
17 = Sin Función
18 = Sin F072
19 = 4-20 mA OK
20 = Sin Función
21 = Sent. Horario
22 a 23 = Sin Función
24 = Ride-Through
25 = Precarga OK
26 = Con Falla
27 = Sin Función
28 = SoftPLC
29 a 34 = Sin Función
35 = Sin Alarma
36 = Sin Falla/Alarma
37 = Función 1 Aplicación
38 = Función 2 Aplicación
39 = Función 3 Aplicación
40 = Función 4 Aplicación
41 = Función 5 Aplicación
42 = Función 6 Aplicación
43 = Función 7 Aplicación
44 = Función 8 Aplicación
13 cfg
P276
(*)
Función
de la
Salida DO2
Ver opciones de P275 0 cfg

Módulo de Expansión de I/O y
Control Remoto Infrarrojo
18 | CFW100
Español
Parám. Descripción Rango de
Valores
Ajuste de
Fábrica Prop.
P277
(*)
Función
de la
Salida DO3
Ver opções de P275 0 cfg
P375
(*)
Temperatura
del NTC
0 a 100 °C ro
P840
(*)
Estado
Teclas
Control
2 o 802 = On/Off
6 o 806 = Flecha para Abajo
8 o 808 = Flecha para
Arriba
9 o 809 = Directo/Reverso
B o 80B = Programador
F o 80F = Función Esp. 01
10 o 810 = Función Esp. 02
11 o 811 = Función Esp. 03
ro
P842
(*)
Visualización
Rápida 1 IR
0 a 999 2
P843
(*)
Visualización
Rápida 2 IR
0 a 999 375
¡NOTA!
(*) Parámetros disponibles solamente cuando
el accesorio esté conectado.
6 UTILIZACIÓN DEL ACCESORIO
Para el correcto funcionamiento del convertidor de
frecuencia CFW100 con accesorio CFW100-IOADR
deben ser seguidas algunas conductas de utilización:
1. El control remoto debe ser direccionado hacia
la extremidad del cable (receptor IR), como es
presentado en la Figura A2 en la página 30.
2. La distancia máxima entre el control remoto y el
receptor IR puede ser de 8 m.
¡NOTA!
Antes de utilizar el control remoto
infrarrojo, remueva la protección de la
batería, en la parte inferior del control.
Verifique periódicamente la necesidad
de sustitución de la batería del control
remoto.
Las funcionalidades de las teclas del control remoto
pueden ser observadas en la Tabla 4 en la página

Módulo de Expansión de I/O y
Control Remoto Infrarrojo
CFW100 | 19
Español
19. El control remoto puede ser visto en la Figura 1
en la página 19.
Figura 1: Control remoto (infrarrojo)
Tabla 4: Funcionamiento de las teclas del control remoto
Tecla Descripción
Arranca/Apaga Motor.
Navegación en el display del CFW100.
Navegación en el display del CFW100.
Alterna visualización entre
parámetros P842 y P843.
Confirma / Programa parámetros en el
display del CFW100.
Función Especial 1. (*)
Función Especial 2. (*)
Función Especial 3. (*)
(*) Función disponible cuando existe aplicativo SoftPLC
instalado. En caso contrario, esta tecla no posee ninguna
funcionalidad.

Módulo de Expansión de I/O y
Control Remoto Infrarrojo
20 | CFW100
Español
¡NOTA!
Cuando el sensor NTC no esté conectado
en el accesorio, el convertidor de frecuencia
CFW100 presentará 999 °C en el parámetro
P375. Si los terminales 6 y 7 (conector del
accesorio) están cortocircuitados, el valor
indicado en el P375 será de 0 °C.
¡ATENCIÓN!
Algunas teclas del control remoto tienen
funciones diferentes, de acuerdo con el
estado de funcionamiento del convertidor de
frecuencia CFW100 cuando la aplicación de
usuario (P903 = 0) está instalada y se está
ejecutando (P900 = 4).