Entering CT ratio
The current transformer ratio CT must only be adjusted beetween 1 and 1999.
Example: With installed CTs 5000 A / 5 A, CT = 1000 must be adjusted.
Enter device settings
Enter PIN (see page above)
Select CT
Enter the CT menu
Select digit (lit decimal point)
Adjust value
Adjust further digits in the same way, if necessary.
Confirm
Note: Display may be wrong with a rated current of 5 A and a set CT ratio of more than
1999.
Resetting energy counters
Enter device settings
Enter PIN (see page above)
Select CLEr
Enter the CLEr menu
Adjust confirmation: no = No, YES = Yes
Confirm
The energy counters are reset.
Display is set back from YES to no.
Technical Data
Dimensions Electrical connection
Bezel □96 mm Rated voltage 230/400 V
Bezel height 12 mm Rated current 5 A
Panel cutout □90+0.5 mm Current connection via CTs N/5 A
Weight 0.5 kg approx. Auxiliary supply 85 ... 265 V AC or
80 ... 300 V DC
Wire cross section max. 2.5 mm2
Working temperature –25 ... +70°C
For more technical data see the Data Sheet 679.D.101.xx
- Specifications subject to change without notice; date of issue 03/15 -