Weishaupt WCM-FS 2.0 User guide

Installation and operating instruction
Remote control station WCM-FS 2.0 and extension module WCM-EM 2.1 83277502 • 3/2012-10

1 User instructions ..................................................................................................................... 5
1.1 User instructions .................................................................................................. 5
1.2 User guide ............................................................................................................. 5
1.2.1 Symbols ................................................................................................................. 5
1.2.2 Target group ......................................................................................................... 5
1.3 Guarantee and Liability ....................................................................................... 5
2 Safety ............................................................................................................................................ 6
2.1 Permissible application ....................................................................................... 6
2.2 Safety measures .................................................................................................. 6
2.3 Electrical connection ........................................................................................... 6
2.4 Disposal ................................................................................................................. 6
3 Product description ............................................................................................................... 7
3.1 Type key ................................................................................................................. 7
3.2 Variations ............................................................................................................... 8
3.2.1 Control with one pump heating circuit ........................................................... 8
3.2.2 Control of multiple heating circuits .................................................................. 9
3.2.3 Control with 2 separate heating circuits in one room .............................. 10
3.2.4 DHW preparation via WCM-EM ................................................................... 11
3.2.5 Control via control centre ............................................................................... 12
3.2.6 Independent control with WCM-FS und WCM-EM ................................ 13
3.3 Technical data ................................................................................................... 14
3.3.1 Electrical data .................................................................................................... 14
3.3.2 Approval data ..................................................................................................... 14
3.3.3 Ambient conditions ........................................................................................... 14
3.4 Compatibility ...................................................................................................... 15
4 Installation ................................................................................................................................ 16
4.1 WCM-FS ............................................................................................................ 16
4.2 WCM-EM .......................................................................................................... 18
5 Electrical installation ........................................................................................................... 19
5.1 WCM-FS ............................................................................................................ 19
5.2 WCM-EM ........................................................................................................... 20
5.2.1 Open housing cover ......................................................................................... 20
5.2.2 Connect WCM-EM .......................................................................................... 20
5.2.3 Connecting WCM-EM to condensing boiler ............................................. 22
5.2.4 Wiring diagram WCM-EM as heating circuit controller .......................... 23
5.2.5 Wiring diagram WCM-EM as DHW load circuit ....................................... 24
5.2.6 Connecting the pump shut off set to the WCM-EM ................................ 24
6 Operation .................................................................................................................................. 25
6.1 Operating panel WCM-FS 2.0 ...................................................................... 25
6.2 Standard display ............................................................................................... 26
6.3 Operating display of the WCM-EM ............................................................. 27
6.4 End user level .................................................................................................... 28
6.4.1 Menu structure end user level ....................................................................... 30
Installation and operating instruction
Remote control station WCM-FS 2.0 and extension module WCM-EM 2.1
83277502 • 3/2012-10 • La 2-106

6.5 Heating engineer level ..................................................................................... 32
6.5.1 Menu structure heating engineer level ......................................................... 34
6.5.2 Menu structure heating engineer level DHW ............................................. 39
6.5.3 Menu structure heating engineer level control centre .............................. 40
6.5.4 Setting the language ........................................................................................ 42
6.5.5 Configuration of the WTC heat exchanger ................................................. 43
6.5.6 Configuration WCM-EM ................................................................................. 44
6.5.7 Set heating circuit type#1 ... 8 ...................................................................... 45
6.5.8 Set control variable#1 ... 8 ............................................................................. 47
6.5.9 Retrieving system information ........................................................................ 48
6.5.10 Set function of variable input H1 .................................................................. 50
6.5.11 Test heating circuit/DHW outputs ................................................................ 51
6.5.12 Set external sensor correction on WCM-EM ............................................. 52
6.5.13 Set minimum supply temperature ................................................................. 53
6.5.14 Set maximum supply temperature ................................................................. 54
6.5.15 Set priority of DHW loading ........................................................................... 55
6.5.16 Set boiler mixer circuit boost ......................................................................... 56
6.5.17 Set mixer parameters ....................................................................................... 57
6.5.18 Set frost protection .......................................................................................... 58
6.5.19 Set minimum pump speed .............................................................................. 59
6.5.20 Set maximum pump speed ............................................................................. 60
6.5.21 Set speed variables .......................................................................................... 61
6.5.22 Set WTC delay .................................................................................................. 62
6.5.23 SOL yield HC .................................................................................................... 63
6.5.24 Set screed program ......................................................................................... 65
6.5.25 Function specific heating ................................................................................ 70
6.5.26 Screed heating .................................................................................................. 72
6.5.27 Set night setback operation ........................................................................... 74
6.5.28 Set frost limit ...................................................................................................... 75
6.5.29 Set switch on optimisation ............................................................................. 76
6.5.30 Set type of building .......................................................................................... 77
6.5.31 Set room thermostat#1 ... 8 ........................................................................... 78
6.5.32 Set adaption#1 ... 8 ......................................................................................... 79
6.5.33 Set room factor-P ............................................................................................. 80
6.5.34 Set maximum DHW temperature .................................................................. 81
6.5.35 Set DHW switch differential .......................................................................... 82
6.5.36 Set DHW boost ................................................................................................ 83
6.5.37 Set maximum DHW load time ....................................................................... 84
6.5.38 Set Legionella protection function ................................................................ 85
6.5.39 Set Antilegionella setpoint temperature ...................................................... 87
6.5.40 Set Legionella time ........................................................................................... 88
6.5.41 Activate circulation during Legionella protection function ...................... 89
6.5.42 Set circulation time ........................................................................................... 90
6.5.43 Set circulation return temperature ................................................................ 91
6.5.44 SOL Yield DHW ............................................................................................... 92
6.5.45 Central control via control centre .................................................................. 93
6.6 Extension module menu structure ................................................................. 95
6.6.1 Extension module EM-HC (access HC without FS) ................................ 95
6.6.2 Extension module EM-DHW (access HC without FS) ............................ 96
Installation and operating instruction
Remote control station WCM-FS 2.0 and extension module WCM-EM 2.1
83277502 • 3/2012-10 • La 3-106

6.7 Reset WCM-EM ............................................................................................... 97
6.8 Reconfiguring WCM-EM for system alterations ....................................... 97
6.9 Emergency operation WCM-EM ................................................................... 97
6.10 Reset WCM-FS ................................................................................................ 98
7 Commissioning ...................................................................................................................... 99
7.1 Prerequisite ........................................................................................................ 99
7.1.1 Set address on WCM-EM .............................................................................. 99
7.2 Steps for commissioning .............................................................................. 100
7.2.1 Setting the language ...................................................................................... 100
7.2.2 Set address on the WCM-FS ...................................................................... 101
8 Troubleshooting ................................................................................................................. 102
8.1 Error codes ....................................................................................................... 102
9 Technical documentation .............................................................................................. 104
9.1 Sensor variables .............................................................................................. 104
10 Key word index ................................................................................................................... 105
Installation and operating instruction
Remote control station WCM-FS 2.0 and extension module WCM-EM 2.1
83277502 • 3/2012-10 • La 4-106

1 User instructions
1.1 User instructions
Translation of original
operating instructions
These installation and operating instructions form part of the heating system and must
be kept on site.
1.2 User guide
1.2.1 Symbols
DANGER
Immediate danger with high risk.
Non observance can lead to serious injury or death.
WARNING
Danger with medium risk.
Non observance can lead to environmental damage,
serious injury or death.
CAUTION
Danger with low risk.
Non observance can cause damage to the equipment
and injury to personnel.
Important information.
Requires direct action
Result after an action
Itemisation
Range
1.2.2 Target group
These installation and operating instructions are intended for the operator and quali-
fied personnel. They should be observed by all personnel working on the system.
Work on the system must only be carried out by personnel who have the relevant
training and instruction.
1.3 Guarantee and Liability
Guarantee and liability claims for personal and equipment damage are excluded, if
they can be attributed to one or more of the following causes:
▪Non approved application of the remote control station,
▪non observance of the operating instructions,
▪continual operation despite a fault,
▪repairs, which have been carried out incorrectly,
▪the use of non original Weishaupt parts,
▪acts of God.
Installation and operating instruction
Remote control station WCM-FS 2.0 and extension module WCM-EM 2.1
1 User instructions
83277502 • 3/2012-10 • La 5-106

2 Safety
2.1 Permissible application
The remote control station WCM-FS 2.0 and the extension module WCM-EM 2.1
are suitable for the control of a heating system with up to 8 heating circuits (one direct
heating circuit and 7 mixed heating circuits), consisting of one or more Weishaupt
condensing boilers.
The connection of a Weishaupt solar controller WCM-SOL 1.0 home is possible.
This device is not intended for use by persons (including children) with reduced
physical, sensory or mental capability or by persons lacking experience and/or knowl-
edge, unless they are supervised by a person responsible for their safety or receive
from this person instruction in how the device is used. Children should be supervised
to ensure they do not play with the device.
Any use other than that described above shall be deemed improper. Weishaupt can-
not be held responsible for any damage resulting from such use. The risk of such
misuse lies entirely with the user. Correct use also includes compliance with the in-
stallation and operating manual and all other documents, which are included in the
delivery in addition to these instructions.
The device described in these instructions conforms to the recognised level of tech-
nology and safety relevant regulations. Improper or inappropriate use could endanger
the health and safety of the user or third party and impair the device function.
2.2 Safety measures
Safety relevant fault conditions must be eliminated immediately.
2.3 Electrical connection
For all work carried out on live parts:
▪Observe the accident prevention instructions BGV A3 and adhere to local direc-
tives,
▪tools in accordance with EN 60900 should be used.
2.4 Disposal
The remote control station WCM-FS and all WCM-EM and WCM–SOL connected
must not be disposed of with household waste. Ensure the devices are disposed of
in the correct manner.
The units are subject to the Act Governing the Sales, Return and Environmentally
Sound Disposal of Electrical and Electronic Equipment (Electrical and Electronic
Equipment-WEEE). Therefore free removal is provided at communal waste collection
facilities.
Installation and operating instruction
Remote control station WCM-FS 2.0 and extension module WCM-EM 2.1
2 Safety
83277502 • 3/2012-10 • La 6-106

3 Product description
3.1 Type key
WCM Type: Weishaupt Condens Manager
-FS Model: Remote control station
2.0 Construction
WCM Type: Weishaupt Condens Manager
-EM Model: Extension module
2.1 Construction
Installation and operating instruction
Remote control station WCM-FS 2.0 and extension module WCM-EM 2.1
3 Product description
83277502 • 3/2012-10 • La 7-106

3.2 Variations
3.2.1 Control with one pump heating circuit
When controlling a pump heating circuit, the heating circuit pump is controlled by the
WCM-FS address WTC-HC#1. For the operation of the heating pump parameter P13
(MFA) or parameter P14 (VA) on the WTC must be set to parameter value 7.
In the following system example the WCM-FS is the time master and controls:
▪Heating circuit #1
▪DHW loading
WTC 45/60-A
vers. H-PEA
B1
Mains
M3
B3
M1
T
Water heater
WAS/WAT
T
Heating circuit 1
FS#1
B11 T
WCM-CPU#1
Legend:
FS#1 Remote control station WCM-FS#1
B1: External sensor
B3: DHW sensor
B11: De-couple sensor
M1: Pump heating circuit 1 on MFA
M3: Storage tank charge pump on VA
Note:
1. The remote control station FS must not be replace with a DU timer.
2. DHW preparation always has priority.
3. Set address of the WCM-FS when commissioning: WTC-HK#1
4. WTC settings: P13=7, P14=4
Installation and operating instruction
Remote control station WCM-FS 2.0 and extension module WCM-EM 2.1
3 Product description
83277502 • 3/2012-10 • La 8-106

3.2.2 Control of multiple heating circuits
Up to 7 additional heating circuits can be controlled via separate extension modules.
In the following system example the WCM-FS controls the respective heating circuit.
Only the WCM-FS with address EM-HC#2 is time master and in the system example
it controls:
▪DHW loading
▪Optional circulation pump.
Water heater
WAS/WAT
Mains
B3
M3
WTC GW
vers. H
B1
T
FS#2
B11
M7
T
M22
M42
B62
EM#2
T
T
M28
M48
B68
T
MM
Mains
Mains
up to 7 mixer circuits
Heating circuit 8
Heating circuit 2
T
modulhydraulic
EM#8
modulhydraulic
WCM-CPU#1
FS#8
Legend:
FS#2 … 8: Remote control station WCM-FS#2 … 8
EM#2 … 8: Extension module WCM-EM#2 … 8
B1: External sensor
B3: DHW sensor
B11: De-couple sensor
B62: Supply sensor heating circuit 2
B68: Supply sensor heating circuit 8
M3: Storage tank charge pump on MFA
M7: Circulation pump on VA
M22: Pump heating circuit 2
M28: Pump heating circuit 8
M42: Mixer valve heating circuit 2
M48: Mixer valve heating circuit 8
Note:
1. WTC settings: P13=4, P14=6
Installation and operating instruction
Remote control station WCM-FS 2.0 and extension module WCM-EM 2.1
3 Product description
83277502 • 3/2012-10 • La 9-106

3.2.3 Control with 2 separate heating circuits in one room
A room with 2 heating circuits is controlled via address WTC-HC#1+EM-HC#2.
Only the pump circuit can be controlled via room sensor. The heating circuit with the
lowest temperature level, e.g. underfloor heating, must be controlled by the mixer
valve.
The WCM-FS #1+2 is time master and controls the storage tank charge pump.
Mains
WC GW
vers. H
T
M22
M42
B62
EM#2
M
M
F52
Heating circuit 2
M21
Heating circuit 1
B1
T
M3
B3
T
Water heater
WAS/WAT
modulhydraulic
T
B11
FS#1+2
WCM-CPU#1
Legend:
FS#1+2: Remote control station WCM-FS
EM#2: Extension module WCM-EM
B1: External sensor
B3: DHW sensor
B11: De-couple sensor
B62: Supply sensor heating circuit 2
M21: Pump heating circuit 1 on MFA
M3: Storage tank charge pump on VA
M22: Pump heating circuit 2
M42: Mixer valve heating circuit 2
M52: Temperature sensor underfloor heating
Note:
1. WTC settings: P13=7, P14=4
Installation and operating instruction
Remote control station WCM-FS 2.0 and extension module WCM-EM 2.1
3 Product description
83277502 • 3/2012-10 • La 10-106

3.2.4 DHW preparation via WCM-EM
It is possible to control multiple independent DHW load circuits.
M7
B3
WTC-GW
vers. H
Mains
M3
T
Water heater 1
WAS/WAT
T
FS#2
B1
T
M22
M42
B62
EM#2
T
T
M27
M47
B67
EM#7
T
MM
Mains
Mains
Heating circuit 7
Heating circuit 2
B11
modulhydraulic modulhydraulic
M71
T
Water heater 2
WAS/WAT
EM#8 M31
modulhydraulic
WCM-CPU#1
Mains
M81
B31
FS#7
T
B1.1
FS#8
Legend:
FS#2: Remote control station WCM-FS funct. heating circuit 2
FS#7: Remote control station WCM-FS funct. heating circuit 7
FS#8: Remote control station WCM-FS funct. DHW load circuit
EM#2-8: Extension module WCM-EM
B1: External sensor
B1.1 Circulation sensor tank 2
B3: DHW sensor tank 1
B11: De-couple sensor
B31: DHW sensor EM#8
B62: Supply sensor heating circuit 2
B67: Supply sensor heating circuit 7
M3: Storage tank charge pump on MFA tank 1
M7: Circulation pump on VA tank 1
M22: Pump heating circuit 2
M27: Pump heating circuit 7
M31: Storage tank charge pump on EM-WW tank 2
M42: Mixer valve heating circuit 2
M47: Mixer valve heating circuit 7
M71: Circulation pump
M81: Antilegionella bypass pump (thermal disinfection)
Note:
1. WTC settings: P13=4, P14=6
Installation and operating instruction
Remote control station WCM-FS 2.0 and extension module WCM-EM 2.1
3 Product description
83277502 • 3/2012-10 • La 11-106

3.2.5 Control via control centre
A WCM-FS remote control station addressed with control centre centralises the
control of the circulation pump and DHW load pump, the synchronisation of the sys-
tem time and the type of operation set (see Ch. 6.5.45). Room sensor and presence
and absence keys have no function with when control is via control centre. The heating
controller is inactive. Using the type of operation set by the control centre, the type
of operation of all extension modules can be controlled without a remote control sta-
tion assigned.
Water heater
WAS/WAT
Mains
B3
M3
vers. H
B1
T
FS#L
B11
M7
T
M22
M42
B62
EM#2
T
T
M28
M48
B68
T
MM
Mains
Mains
up to 7 mixer circuits
Heating circuit 8
Heating circuit 2
T
modulhydraulic
EM#8
modulhydraulic
WCM-CPU#1
WTC-GW
Legend:
FS#L: Remote control station WCM-FS funct. control centre
B1: External sensor
B3: DHW sensor
B11: De-couple sensor
B62: Supply sensor heating circuit 2
B68: Supply sensor heating circuit 8
M3: Storage tank charge pump on MFA
M7: Circulation pump on VA
M22: Pump heating circuit 2
M28: Pump heating circuit 8
M42: Mixer valve heating circuit 2
M48: Mixer valve heating circuit 8
Note:
1. WTC settings: P13=4, P14=6
Installation and operating instruction
Remote control station WCM-FS 2.0 and extension module WCM-EM 2.1
3 Product description
83277502 • 3/2012-10 • La 12-106

3.2.6 Independent control with WCM-FS und WCM-EM
The system's external sensor is connected to EM#2. The external temperature value
is transmitted via eBUS to all remote control stations and extension modules con-
nected.
A zone control with a locally connected external sensor is still possible.
Mains
FS#2
B1
T
M22
M42
B62
EM#2
T
T
M27
M47
B67
EM#7
T
MM
Mains
Mains
Heating circuit 7
Heating circuit 2
modulhydraulic modulhydraulic
M71
T
Water heater
WAS/WAT
EM#8 M31
modulhydraulic
External heat exchanger
Mains
M81
B31
FS#7
T
B1.1
FS#8
Legend:
FS#2: Remote control station WCM-FS funct. heating circuit 2
FS#7: Remote control station WCM-FS funct. heating circuit 7
FS#8: Remote control station WCM-FS funct. DHW load circuit
EM#2-8: Extension module WCM-EM
B1: External sensor
B1.1: Circulation sensor EM#8
B31: DHW sensor EM#8
B62: Supply sensor heating circuit 2
B67: Supply sensor heating circuit 7
M22: Pump heating circuit 2
M27: Pump heating circuit 7
M31: Storage tank charge pump EM#8
M42: Mixer valve heating circuit 2
M47: Mixer valve heating circuit 7
M71: Circulation pump EM#8
M81: Antilegionella bypass pump (thermal disinfection)
Installation and operating instruction
Remote control station WCM-FS 2.0 and extension module WCM-EM 2.1
3 Product description
83277502 • 3/2012-10 • La 13-106

3.3 Technical data
3.3.1 Electrical data
WCM-FS WCM-EM
Supply voltage / frequency – 230 V/50 Hz
Max. consumption – 7 VA
Max. prefusing – 10 A
Internal unit fuse – 6.3 A
Type of protection – IP 22
Protection class I I
(to EN 60730)
I
(to EN 60730)
Nominal current output MFA / MM1 – max. 5 A* **
* for electronic high efficiency pumps max 1.5 Ampere. Separate relay required for
greater power consumptions.
** Power consumption of outputs MFA 1 and MM1 in total maximal 5A.
3.3.2 Approval data
Unit tested to EN 60730
3.3.3 Ambient conditions
Temperature in operation 0 °C … 50 °C
Temperature during transport / storage -25 … 70 °C
relative humidity max. 80 %, no dew point
Installation and operating instruction
Remote control station WCM-FS 2.0 and extension module WCM-EM 2.1
3 Product description
83277502 • 3/2012-10 • La 14-106

3.4 Compatibility
The WCM-FS 2.0 and WCM-EM 2.1 have functions, which were not provided by the
previous WCM systems. Therefore there may be limited functionality with other WCM
components.
The compatibility of each WCM component to one another is shown in the table
below.
WCM-FS1.0
WCM-FS2.0
WCM-EM1.0
WCM-EM2.0
WCM-EM2.1
WCM-SOL1.0
WCM-KA1.0
WCM-KA2.0
WCM-FS 1.0 C A A B B A* A*
WCM-FS 2.0 C A A A A A A
WCM-EM 1.0 A A C C B A A
WCM-EM 2.0 A A C C B A A
WCM-EM 2.1 B A C C A A A
WCM-SOL 1.0 B A B B A D D D
WCM-KA 1.0 A A A A A D D D
WCM-KA 2.0 A A A A A D D D
A Full functionality
A* Full functionality (from version WCM-FS 1.0 V196.27)
B Compatible, the older component version limits the functionality
C Can be used together in one system
D Cannot be used in multiples/combined in one system
Installation and operating instruction
Remote control station WCM-FS 2.0 and extension module WCM-EM 2.1
3 Product description
83277502 • 3/2012-10 • La 15-106

4 Installation
4.1 WCM-FS
The room sensor integrated into the remote control station must not be influenced by:
▪additional temperature control in the same room (radiator thermostats),
▪other heat sources (direct sun light, chimney etc.).
▶Install the remote control station to an inside wall on the opposite side to radiators.
Fitting the wall bracket
▶Fix wall bracket to wall.
▶Connect wiring (see Ch. 5.1).
▶Clip remote control unit into the wall bracket.
modul
control
Installation and operating instruction
Remote control station WCM-FS 2.0 and extension module WCM-EM 2.1
4 Installation
83277502 • 3/2012-10 • La 16-106

Fitting the WCM-FS to a WTC-GW/OW
The mounting set available as an accessory is required.
▶Install as instructed in the installation instructions supplied.
Fitting the WCM-FS to a WTC-GB/OB
▶Open flap on boiler control panel.
▶Clip remote control station into mounting slot.
Installation and operating instruction
Remote control station WCM-FS 2.0 and extension module WCM-EM 2.1
4 Installation
83277502 • 3/2012-10 • La 17-106

If the WCM-FS is fitted to a WTC, this is indicated in parameter Config FS with
Boiler. The display of the room temperature in line 3 of the WCM-FS is omitted. A
change in the location room<->boiler requires reconfiguration in parameter Config
FS (P335).
4.2 WCM-EM
▶Fit cap type rail to the wall using suitable fixing material.
▶Push in locking device 1.
▶Connect extension module to cap type rail.
▶Connect cables (see Ch. 5.2).
▶Close housing cover.
Füllungen
Pfeile
Die 1. Füllung: 15 % schwarz
Weitere Füllungen: 25 %, 35 %, 45 %, 55 % schwarz
Schneiden sich zwei Bauteile oder liegen sie optisch aufeinander bzw. direkt
nebeneinander, sind die Füllungen in
einer 20 %igen Abstufung zu wählen (z. B. 15 % und 35 %).
Linien:
0,125 mm - schwarz: Bauteile, Bezugslinien, Maßlinien
verdeckte Teile: Für verdeckte Teile oder nicht sichtbare Kanten
für Richtungen
(Fließrichtung Gasarmatur)
für Maße
siehe auch >Fenster< / >Pinsel<
siehe auch >F5<
Drehung, Bewegung
0,75 mm - weiß: Hintergrund für Bezugslinien und Lupenrahmen
12
12
12
12
Kreiszahlen
Lupe
Pfeile
Lupenrahmen
- Kontur: 0,25 mm
- Fläche: weiß
- Eckenradius 2 mm
Hintergrund Lupe
- Kontur: 0,75 mm
- Fläche: keine
Abstände
- Objekte in der Lupe zum Rahmen: min 1 mm
- Lupe zur Grafik und Grafikrahmen: min 2 mm
Vorgabe
Für die Lupe wird generell ein Rechteck verwendet,
also keine Kreise, Ovale oder sonstiges.
Bezugslinie; 0,125 mm, schwarz, 1 mm gestrichelt:
Stellt den örtlichen Bezug der Bauteile untereinader her.
Abstand zum Rahmen
oben & unten 2 mm
links & rechts min 2 mm oder
horizontal mittig ausrichten
Abstand Kreuzungspunkt Trenn-/Führungslinie
Führungslinie soll die Leserichtung unterstützen, daher durchziehen
Trennlinie: oben & unten oder links & rechts min 2 mm
Grafikrahmen (mit Trenn- und Führungslinie)
Maximale Grafikhöhe 240 mm
Schrift:
Text in Grafiken nach Möglichkeit vermeiden.
Ist dennoch Text in Grafiken erforderlich, gilt für:
- Display-Anzeigen die Courier New (Schriftgröße der Displaygröße entsprechend),
- Text wie Maßangaben oder “Maße in mm” die AkzidenzGroteskBQ Regular (8 pt).
Diese Schriften NICHT in Pfade umwandeln.
Speichern
Ist die Grafik entgültig fertiggestellt, vor dem Speichern diese Ebene löschen:
- Vorlagen.
- Schraubengrößen und Maße in AkzidenzGroteskBQ Regular (12 pt).
- Maße in perspektivischen Grafiken werden perspektivisch geneigt
(siehe Doku Textfeld perspektivisch neigen).
- Schraubengrößen erhalten zusätzlich einen schwarzen Rahmen 0,125 mm.
Da Kurzanleitungen für Montagen unter erschwerteren Bedingungen erstellt werden
(z. B. Montage auf Dächern), wird von den festgelegten Regeln für Grafiken abgewichen.
Schrift-Abweichungen für Kurzanleitungen
13.
6 x 80
100
300
5.
> 5 mm
Linien-Abweichungen für Kurzanleitungen
1E
1
Bezugslinie; 0,25 mm, schwarz, 1,41 mm gestrichelt:
Stellt den örtlichen Bezug für die optische
Ausrichtung her.
Installation and operating instruction
Remote control station WCM-FS 2.0 and extension module WCM-EM 2.1
4 Installation
83277502 • 3/2012-10 • La 18-106

5 Electrical installation
5.1 WCM-FS
The WCM-FS 2.0 remote control station must only be assigned to a heating circuit
with an extension module from WCM–EM 1.0.
▶Connect electrical cable to eBUS terminal 1 and 2.
▶An external room sensor can be fitted to terminals 5 and 6 if required (accessory).
Cable cross section Max. length
1.5 mm² 1260 m
0.5 mm² 420 m
siehe auch >Fenster< / >Pinsel<
siehe auch >F5<
Lupenrahmen
- Kontur: 0,25 mm
- Fläche: weiß
- Eckenradius 2 mm
Hintergrund Lupe
- Kontur: 0,75 mm
- Fläche: keine
Abstände
- Objekte in der Lupe zum Rahmen: min 1 mm
- Lupe zur Grafik und Grafikrahmen: min 2 mm
Vorgabe
Für die Lupe wird generell ein Rechteck verwendet,
also keine Kreise, Ovale oder sonstiges.
Generally, the use of screened electrical wiring is recommended.
Installation and operating instruction
Remote control station WCM-FS 2.0 and extension module WCM-EM 2.1
5 Electrical installation
83277502 • 3/2012-10 • La 19-106

5.2 WCM-EM
5.2.1 Open housing cover
▶Lightly push down lug with screwdriver.
▶Remove housing cover.
5.2.2 Connect WCM-EM
MM1
N
MM1
M FA1
LN
230V
LN
MF A1
H1
H1
N
L
MM1
N
MM1
M F
A1
LN
230V
LN
MF A1
H1
H1
N
L
MM1
N
MM1
MF
A1
LN
230V
LN
MF A1
H1
H1
N
L
MM1
N
MM1
MF
A1
LN
230V
LN
MF A1
H1
H1
N
L
MM1
N
MM1
M F
A1
LN
230V
LN
MF A1
H1
H1
N
L
Installation and operating instruction
Remote control station WCM-FS 2.0 and extension module WCM-EM 2.1
5 Electrical installation
83277502 • 3/2012-10 • La 20-106
Other manuals for WCM-FS 2.0
1
This manual suits for next models
1
Table of contents
Popular Control System manuals by other brands

Whelen Engineering Company
Whelen Engineering Company Core-C CCP9 quick start guide

HPE
HPE Edgeline EL300 Setup and configuration guide

Stulz
Stulz CompTrol 1002 manual

DKS
DKS 1812 Classic Installation & owner's manual

Fidelis
Fidelis Fidelis Network CommandPost/K2 quick start guide

Madas
Madas Madas IT262.00 manual