20 INSTRUCTIONS PERTAINING TO THE INSTALLERBAXI - 925.529.1
The boiler has been designed in full compliance with European reference standards and in particular is equipped with the following:
• Air pressure switch for forced draught model (240 Fi - 310 Fi - 1.240 Fi - 1.310 Fi)
This switch (17 - gure 20) allows the burner to switch on provided the exhaust ue duct efciency is perfect.
In the event of one of the following faults:
• the ue terminal is obstructed;
• the venturi is obstructed;
• the fan is blocked;
• the connection between the venturi and the air pressure switch is interrupted;
The boiler will stay on stand-by and the display shows error code E03 (see section 9).
• Flue thermostat for natural draught (model 240 i - 1.240 i)
This device (15 - gure 21) has a sensor positioned on the left section of the ue extraction hood and shuts off the gas ow to the
burner if the ue duct is obstructed or in the event of draught failure.
Under such conditions the boiler is blocked and the display shows E03 error (see section 9).
To relight the main burner immediately, see section 9.
It is forbidden to disenable this safety device
• Overheat safety thermostat
Thanks to a sensor (12 - g. 20 /21) placed on the heating ow, this thermostat interrupts the gas ow to the burner in case the water
contained in the primary circuit has overheated. Under such conditions the boiler is blocked and relighting will only be possible after
the cause of the anomaly has been removed.
See section 9 to RESET normal operating conditions.
It is forbidden to disenable this safety device
• Flame ionization detector
The ame sensing electrode (19 - gure 20, 16 - gure 21), placed on the right of the burner, guarantees safety of operation in case of
gas failure or incomplete interlighting of the burner. The boiler is blocked after 3 relight attempt.
See section 9 to RESET normal operating conditions.
• Hydraulic pressure sensor
This device (3 - gure 20/21) enables the main burner only to be switched on if the system pressure is over 0.5 bars.
• Pump overrun for central heating circuit
The electronically-controlled supplementary running of the pump lasts 3 minutes (F17 - Section 20), when the boiler is in the central
heating mode, after the burner has switched off due to a room thermostat or intervention.
• Pump overrun for domestic hot water circuit
The electronic control system keeps the pump operating for 30 seconds in domestic hot water mode after the D.H.W. sensor has
switched off the burner.
• Frost protection device (central heating and domestic hot water systems)
Boilers electronic management includes a “frost protection” function in the central heating system which operates the burner to reach
a heating ow temperature of 30°C when the system heating ow temperature drops below 5 °C.
This function is enabled when the boiler is connected to electrical supply, the gas supply is on and the system pressure is as requi-
red.
• Lack of water circulation (probable pump jammed)
If the water inside the primary circuit doesn’t circulate, the display shows E25 error (see section 9).
• Anti-block pump function
In the event that no heat is required, the pump will automatically start up and operate for one minute during the following 24 hours.
This function is operative when the boiler is powered.
• Three-way anti-blockage valve
In the case of no heat is request for a period of 24 hours the three way valve carries out a complete commutation.
This function is operative when the boiler is powered.
• Hydraulic safety valve (heating circuit)
This device (28 - gure 20, 25 - gure 21) is set to 3 bar and is used for the heating circuit.
The safety valve should be connected to a siphoned drain. Use as a means of draining the heating circuit is strictly prohibited.
• Antilegionella function (models 1. 240 Fi - 1. 240 i - 1.310 Fi with D.H.W. storage tank)
The antilegionella function is NOT enable.
To enable the function, set the parameter F21=01 (as described in section 20). When the function is activated, at weekly intervals
the boiler’s electronic control system brings the water inside the hot water tank to a temperature above 60°C (the function is only
operational if the water has never exceeded 60°C in the previous 7 days).
Note: domestic hot water is guaranteed even if the NTC sensor (5 - gure 20 - 21) is damaged. In this case, the temperature control is
carried out by the boiler ow temperature.
21. CONTROL AND OPERATION DEVICES