Installation Iinstructions
for your new
TKirlpool
TRASH MASHER@ COMPACTOR
BEFOREYOU USEYOURCOMPACTOR...
Be sure your compactor is properly installed in an appropriate level area and a place suitable for the size, function
and protection of the compactor.
ELECTRICALREQUIREMENTS
Observe All Governing Codes and Ordinances
A 120-Volt, 60 Hz, AC only, 15-Ampere fused electrical supply is required. (Time delay fuse or circuit breaker is recom-
mended.) It is recommended that a separate circuit serving only this applrance be provided. DO NOT use an exten-
sion cord.
RECOMMENDED GROUNDING METHOD
DO NOT, UNDER ANY CIRCUMSTANCES,
REMOVE THE POWER SUPPLY CORD
)-PRONG
GROUNDING TYPE
GROUND PRONG.
For your personal safety, this appliance must be
grounded. This appliance is equipped with a power
supply cord having a 3-prong grounding plug. To
minimize possible shock hazard, the cord must be
plugged into a mating 3-prong grounding type wall
receptacle, grounded in accordance with the
National Electrical Code and local codes and or-
dinances. If a mating wall receptacle is not available,
it is the personal responsibility and obligation of the
customer to have a properly grounded 3-prong wall
receptacle installed by a qualified electrician. See
Figure 1.
WALL RECEPTACLE
\
- POWER SUPPLY
FIGURE 1
ALTERNATE GROUNDING METHOD
(Do not use in Canada)
DO NOT, UNDER ANY CIRCUMSTANCES,
GROUND ASSEMBLY
(ATTACH TO CROUNOEO
COLD WATER PIPE)
REMOVE THE POWER SUPPLY CORD
GROUND PRONG.
&-ELECTRICALLV GROUNDED
COLD WATER PIPE
If changing and properly grounding the wall receptacle
is impossible and where local codes permit (consult
your electrical inspector), a temporary adapter may be
plugged into the existing 2-prong wall receptacle to
mate with the 3-prong power supply cord. See Figure
2. THIS, HOWEVER, IS NOT RECOMMENDED.
(REMOVE .I
If this is done, you must connect the grounding eyelet
on the adapter to the wall receptacle coverplate screw
3.PRONG -
and from this same screw you must connect a separate
GROUNDING PLUG
copper ground wire (No. 18 minimum) to a grounded t
cold water pipe.
l
See Figure 2. Do not ground to a gas
POWER SUPPLY WALL RECEPTACLE
supply pipe. Do not connect to electrical supply until
appliance is permanently grounded.
*Grounded cold water pipe must have metal contmurty to
electrical ground and not be interrupted by plasttc, rub-
ber or other Insulating connectors such as hoses, fittings,
washers or gaskets (including water meter or pump). Any
electrically insulating connector should be jumped as
shown below with a length of No. 4 copper wtre securely
clamped at both ends.
-lMPORTANT-
DO NOT REMOVE THIS INSTRUCTION SHEET UNTIL READY FOR INSTALLATION
AFTER COMPLETING THE INSTALLATION. SAVE THESE INSTRUCTIONS FOR FUTURE USE.
1
Part No. 780337 Rev. I3