White Rogers 50A55-843 User manual

TH
TR
MV
MV
GND
FP
HLO
HLI
PS
C
R
G
W
Y
EAC N
HUM N
XFMR N
LINE N
CIR N
IGN
IND
IGN N
IND N
HUM
EAC
XFMR
LINE
PARK
PARK
HEAT
COOL
IGNITOR
Y
W
G
R
THERMOSTAT
GAS
VALVE
HIGH LIMIT
(N. C.)
ROLLOUT
(N. C.)
AUX. HIGH
LIMIT (N. C.)
PRESSURE SWITCH (N. O.)
FLAME
SENSOR
PROBE
COMPRESSOR
CONTACTOR
ELECTRONIC
AIR CLEANER
HUMIDIFIER
INDUCER
CIRCULATOR
BLOWER
50A55
24 VAC
120 VAC
24 VAC CLASS II
TRANSFORMER
HOT
(LINE)
NEUTRAL
(LINE)
TH TR
Low Voltage (24 VAC)
Line Voltage (120 VAC)
LEGEND
N. C. = Normally closed switch
N. O. = Normally open switch
RO1
RO2
TYPICAL SYSTEM WIRING DIAGRAM
TWIN*TWIN*
50A55-843
in other
furnace(s)
—
TWINNING
APPLICATIONS
ONLY
50A55-843
WIRING AND
CONFIGURATION
Flame Current Requirements:
0LQLPXPFXUUHQWWRLQVXUHÀDPHGHWHFWLRQ.............1 µa DC➀
Maximum current for non-detection.....................0.1 µa DC➀
0D[LPXPDOORZDEOHOHDNDJHUHVLVWDQFH............. 100 M ohms
Flame establishing time......................0.8 seconds maximum
Flame failure response time ...............2.0 seconds maximum
➀ 0HDVXUHGZLWKD'&PLFURDPPHWHULQWKHÀDPHSUREHOHDG
50A55-843
www.white-rodgers.com 183
TECHNICAL HELP

HEAT delay-
to-fan-off:
Set switch
#3 #4
60 sec.
90 sec.
120 sec.
180 sec.*
On On
Off On
On Off
Off Off
COOL delay-
to-fan-off:
Set switch
#1
45 sec.*
90 sec.
On
Off
HEAT delay-
to-fan-on:
Set switch
#2
30 sec.*
45 sec.
On
Off
OPTION SWITCH POSITIONS
* Factory setting
The 50A55-843 is an automatic gas interrupted ignition
control that employs a microprocessor to continually monitor,
analyze, and control the proper operation of the gas burner,
inducer, and fan.
Signals interpreted during continual surveillance of the ther-
PRVWDWDQGÀDPHVHQVLQJHOHPHQWLQLWLDWHDXWRPDWLFLJQLWLRQ
RIWKHEXUQHUVHQVLQJRIWKHÀDPHDQGV\VWHP
shut-off during normal operation.
OPTION SWITCHES
The option switches on the 50A55-843 control are used to
determine the length of the cool delay-to-fan-off, heat delay-
to-fan-on and heat delay-to-fan-off periods. The following
table shows the time periods that will result from the various
switch positions.
HEAT MODE
In a typical system, a call for heat is initiated by closing the
WKHUPRVWDWFRQWDFWV7KLVVWDUWVWKH$FRQWURO¶VKHDWLQJ
VHTXHQFH7KHLQGXFHUEORZHUDQGRSWLRQDOKXPLGL¿HUDUH
energized and the ignitor is powered within one second.
This controller has an adaptive algorithm that adjusts the du-
ration of the ignitor warm-up, to extend ignitor life. Upon initial
application of power, the warm-up time is 17 seconds. The
ignitor on-time will then be increased or decreased depend-
LQJRQZKHWKHURUQRWÀDPHLVDFKLHYHG7KHZDUPXSWLPH
LVOLPLWHGWRDPD[LPXPRIVHFRQGV'XULQJWKH¿UVW
warm-up periods following power-up, the warm-up time may
not be less than 17 seconds.
8SRQDFDOOIRUKHDWLIWKHZDUPXSWLPHKDVQRWEHHQORFNHG
it will be decreased by one second. This reduction of the
LJQLWRURQWLPHZLOOFRQWLQXHXQWLOÀDPHIDLOVWREHDFKLHYHG
(resulting in a retry).
In the event of a retry, the warm-up time will be increased by
WZRVHFRQGVDQGORFNHGLQDWWKDWGXUDWLRQ2QFHWKHZDUP
XSWLPHLVORFNHGLWUHPDLQV¿[HGXQWLODQRWKHUFDOOIRUKHDW
results in a retry, in which case the warm-up time is again
LQFUHDVHGE\WZRVHFRQGVDQGUHPDLQVORFNHG
In the event of two successive retry attempts, the warm-up
WLPHZLOOEHXQORFNHGDQGVHWWRVHFRQGV,IÀDPHLVWKHQ
achieved, the warm-up time will begin adapting again with
the next call for heat. If, however, this third attempt fails to
DFKLHYHÀDPHWKHFRQWUROZLOOJRLQWRV\VWHPORFNRXW
At the end of the ignitor warm-up time, both valves in the
36E manifold gas valve are opened. Flame must be detected
within 4 seconds.
See installation instructions for more system sequence detail.
COOL MODE
In a typical system, a call for cool is initiated by closing the
thermostat contacts. This energizes the 50A55 control and
MANUAL FAN ON MODE
If the thermostat fan switch is moved to the ON position, the
circulator fan (cool speed) and optional electronic air cleaner
are energized. When the fan switch is returned to the AUTO
position, the circulator fan and electronic air cleaner (optional)
are de-energized.
SYSTEM LOCKOUT FEATURES
:KHQV\VWHPORFNRXWRFFXUVWKHJDVYDOYHLVGHHQHUJL]HG
WKHFLUFXODWRUEORZHULVHQHUJL]HGDWKHDWVSHHGDQGLIÀDPH
is sensed, the inducer blower is energized. The diagnostic
LQGLFDWRUOLJKWZLOOÀDVKRUJORZFRQWLQXRXVO\WRLQGLFDWH
system status. (System lockout will never override the
precautionary features.)
To reset the control after system lockout, do one of the
following:
1. Interrupt the call for heat or cool at the thermostat for at
OHDVWRQHVHFRQGEXWOHVVWKDQVHFRQGVLIÀDPHLV
sensed with the gas valve de-energized, interrupting the
call for heat at the thermostat will not reset the control).
2. Interrupt the 24 VAC power at the control for at least one
VHFRQG<RXPD\DOVRQHHGWRUHVHWWKHÀDPHUROORXW
sensor switch.
$IWHURQHKRXULQORFNRXWWKHFRQWUROZLOODXWRPDWLFDOO\
reset itself.
DIAGNOSTIC FEATURES
The 50A55-843 control continuously monitors its own
operation and the operation of the system. If a failure occurs,
the LED will indicate a failure code as shown below. If the
failure is internal to the control, the light will stay on
continuously. In this case, the entire control should be
UHSODFHGDVWKHFRQWUROLVQRW¿HOGUHSDLUDEOH
If the sensed failure is in the system (external to the control),
WKH/('ZLOOÀDVKLQWKHIROORZLQJÀDVKSDXVHVHTXHQFHVWR
LQGLFDWHIDLOXUHVWDWXVHDFKÀDVKZLOOODVWDSSUR[LPDWHO\
seconds, and each pause will last approximately 2 seconds).
ÀDVKWKHQSDXVH 6\VWHPORFNRXW
ÀDVKHVWKHQSDXVH 3UHVVXUHVZLWFKVWXFNFORVHG
ÀDVKHVWKHQSDXVH 3UHVVXUHVZLWFKVWXFNRSHQ
ÀDVKHVWKHQSDXVH 2SHQOLPLWVZLWFK
ÀDVKHVWKHQSDXVH 2SHQUROORXWVZLWFK
ÀDVKHVWKHQSDXVH 9ROW$&SRZHUUHYHUVHG
Improper ground
ÀDVKHVWKHQSDXVH /RZÀDPHVHQVHVLJQDO
&RQWLQXRXVÀDVKLQJ )ODPHKDVEHHQVHQVHGZKHQ
QRSDXVH QRÀDPHVKRXOGEHSUHVHQWQR
call for heat)
7KH/('ZLOODOVRÀDVKRQFHDWSRZHUXS
WIRING AND
CONFIGURATION50A55-843
Trane application - Jumper wire 151-2906 (provided with
control) must be installed on the furnace from R01 to R02 of
the 12-pin connector.
the compressor. The cool delay-to-fan-on period begins. After
the delay period ends, the optional electronic air cleaner is
energized, and the circulator fan is energized at cool speed.
$IWHUWKHWKHUPRVWDWLVVDWLV¿HGWKHFRPSUHVVRULVGH
energized and the cool mode delay-to-fan-off period begins.
After the delay-to-fan-off period ends, the circulator fan and
electronic air cleaner (optional) are de-energized.
www.white-rodgers.com
184
TECHNICAL HELP
Popular Controllers manuals by other brands

Taylex Tanks
Taylex Tanks ABS Controller Homeowner's manual

Ropex
Ropex RESISTRON RES-409 operating instructions

Solar Stik
Solar Stik DSE 3110 instruction manual

Sundstrom
Sundstrom SR 507 Training

Pentair
Pentair AQUATIC ECO-SYSTEMS SAFEGUARD UV SYSTEMS... Installation and user guide

Dell
Dell UCS-51 user guide

Mitsubishi Electric
Mitsubishi Electric MELSEC iQ-R Series user manual

Ultra Products
Ultra Products ULT40061 Specification sheet

Crestron
Crestron MPC-M10 Operations & installation guide

Rockwell
Rockwell PowerFlex 70 user manual

Jands
Jands ESP II 24 operating manual

Jesco
Jesco TOPAX DE operating instructions