Wildeboer VR1 User manual

User Manual 3.1 (2016-04) 1
Maintenance-free
VR1 volume flow controller
that operates without an auxiliary power supply,
for ventilation and air conditioning systems.
■ Adjustableonsite.
■ Outstandingcontrolaccuracy.
■ SizesDN80toDN315.
■ CasingtightnessclassCaccordingtoDINEN1751.
New option
with duct silencer
The German original version of this document shall prevail.

Subject to change
User Manual 3.1 (2016-04) 2
Maximumpossiblereductionofflownoisewithsoundatte-
nuator lengths
Size Outerdiameter L1 L[mm]
DN ∅[mm] [mm] 600 900
80 200 40 -22[dB] -
100 200 40 -22[dB] -25[dB]
125 225 40 -22[dB] -25[dB]
160 260 40 -21[dB] -24[dB]
200 300 40 -19[dB] -24[dB]
250 355 40 -18[dB] -22[dB]
315 415 40 -15[dB] -19[dB]
VR1 volume flow controller
Overview
With the basic version of the VR1 volume flow controller,
the volume flow set point isadjustedmanually.
The controllers operate without an auxiliary power supply!
The volume flow set point is preselected at an adjusting
devicewithscaleandkeptconstantatvariablepressures
toahighdegreeofaccuracy.Thecontrollersareadjusted
at the factory for the entire volume flow range.
• Thevolumeflowsetpointiseasytoadjustonsite!
• Thevolumeflowsetpointcanbepresetatthefactoryif
requested when ordering. Subsequent changes on site
canbemadewithoutproblem. ⇒see page 9
Option
VR1 volume flow controller with actuator driven adjustment
of
the volume flow set point
. Electrical auxiliary power is
requiredtocarryouttheadjustment.
Dependingonwhichactuatorisselected,twosetpointsor
anyintermediatevaluesarepossible.
Useinsystemswithvariablevolumeflows,withday/night
changeover or fully variable load-dependent operation for
example.
Option
VR1 volume flow controller with acoustic insulation for
thermal insulation and reduction of external sound radiation.
Canbeusedforcontrollerswithmanualandactuator-driven
adjustmentofthe
volume flow set point!
Allillustrationsshowvolumeflowcontrollerswithlipseals!
Option
SRC duct silencer for volume flow controller
for
reduction of flow noise in the circular ventilation
duct.

Subject to change
User Manual 3.1 (2016-04) 3
Size Vmin Vmax ∅d L AA
DN [m³/h] [m³/h] [mm] [mm] [m²]
80 50 280 79 329 0.005
100 70 380 99 329 0.008
125 120 600 124 329 0.012
160 150 900 159 329 0.020
200 250 1300 199 329 0.031
250 400 2100 249 406 0.049
315 600 3100 314 456 0.078
VR1 volume flow controller
Description,sizes,technicaldata
1 Ductcasing
2 Controldevice
3 Volumeflowsetpointadjustment
4 Settingpointerwithscale
5 Lipseal
(optional equipment)
6 Acousticinsulationwithsheetmetal
jacket(optionalequipment)
VR1 volume flow controllers are maintenance-free mechanical controllers
that operate without an auxiliary power supply to maintain volume flows in
ventilation and air conditioning systems constant.
They are installed in supply and exhaust air ventilation ducts and are not
position-sensitive.Thecasingandcontrolmechanismaremadeofgalvanized
sheetsteel.Thecentrallysupporteddamperbladewhichcontrolsthevolume
flowhasastainlesssteelbearingaxisinspecialbushings.Theadjustment
device is equipped with rotary pointer, scale and locking device. The volume
flowsetpointscanbeadjustedmanuallyorbyactuatorwithinthe volume
flow ranges Vmin to Vmax
.
The special control mechanism ensures a high degree of control accuracy
withadeviationofonlyapprox.±5%to±10%*).Accordingly,thevolumeflow
throughout the entire pressure range is kept constant.
• Sizes: DN80toDN315
• Totalvolumeflowrange: Vmin=50toVmax=3100m³/h
• Pressurerange: 50to1000Pa⇒ seepages4to7
• Casingtightness: ClassCaccordingtoDINEN1751
• Interiortemperaturerange: -20to+70°C,90°Cforashorttimeonly
•Options
• ActuatorAC230VorAC/DC24V,settingtotwovolumeflowsetpoints.
• ContinuousactuatorAC/DC24V,settingtoanydesiredvolumeflowset
point.
• Externalacousticinsulationwithsheetmetaljacket.
• Lipsealsonbothsides.
•Presetting of volume flow set point at the factory. ⇒ see page 9
• SRCductsilencer,availablein600mmand900mmlengths.
*) Largerdeviationsoccurwithlowervolume
flow rates, especially with small sizes!
Where control deviations are specified as a
percentage, the corresponding volume flow
set point specified is used as reference.
It is assumed that the incoming flows are
extensively undisrupted.
X=65mm;withactu-
ator-drivenadjustment,
X = 130 mm
L1=40mm;fromDN≥250
L1=60mm
Nomenclature⇒ seepage7
VR1 volume flow controllers
•satisfy the hygiene requirementsaccordingtoVDI6022-1,VDI3803-1,DIN1946-4,DINEN13779,SWKIVA104-01,
SWKI99-3,ÖNORMH6020andÖNORMH6021.
• are resistant to microbes, and therefore do not promote the growth of
micro-organisms (fungi, bacteria). This reduces the risk of infection for
people and also the necessary cleaning an disinfection work!
• are resistant to cleaning agents and disinfectantsandaresuitableforuse
in hospitals and similar facilities!
• come with Environmental Product DeclarationaccordingtoISO14025andEN15804:EPD-WIL-20150036-ICA1-DE.

Sound power level L
WA
[dB(A)]
Static pressure drop ΔpS [Pa]
Volume flow V [m
3
/h]
Flow velocity V
A
[m/s]
Sound power level L
WA
[dB(A)]
Static pressure drop ΔpS [Pa]
Volume flow V [m3/h]
Flow velocity VA[m/s]
Sound power level LWA [dB(A)]
Static pressure drop ΔpS [Pa]
Volume flow V [m3/h]
Flow velocity VA[m/s]
Sound power level L
WA
[dB(A)]
Static pressure drop ΔpS [Pa]
Volume flow V [m
3
/h]
Flow velocity V
A
[m/s]
Subject to change
User Manual 3.1 (2016-04) 4
VR1 volume flow controller
Soundpowerlevelintheconnectingduct(flownoise)
SizeDN80 SizeDN100
SizeDN125 SizeDN160
Nomenclature⇒seepage7

Sound power level L
WA
[dB(A)]
Static pressure drop ΔpS [Pa]
Volume flow V [m
3
/h]
Flow velocity V
A
[m/s]
Sound power level LWA [dB(A)]
Static pressure drop ΔpS [Pa]
Volume flow V [m3/h]
Flow velocity VA[m/s]
Sound power level L
WA
[dB(A)]
Static pressure drop ΔpS [Pa]
Volume flow V [m
3
/h]
Flow velocity V
A
[m/s]
Subject to change
User Manual 3.1 (2016-04)5
VR1 volume flow controller
Soundpowerlevelintheconnectingduct(flownoise)
Example:
Specified: Size DN250
Volumeflow V = 1500 m³/h
Flow velocity vA = 8.5 m/s
Staticpressuredrop DpS = 435 Pa
Result: Flownoise
Soundpowerlevel LWA = 70 dB(A)
SizeDN200 SizeDN250
SizeDN315
Nomenclature⇒seepage7
Dimensioningsoftware⇒downloadatwww.wildeboer.de
•The sound power level inside the connecting duct is calcu-
latedinthenomogramsasanA-weightedoveralllevelLWA.
TheWildeboerdimensioningsoftwarecalculatescorrespon-
dingoctavesoundpowerlevelsLW-Octforeverysizeand
alloperatingpoints;andalsowhenincorporatingadditional
SRCductsilencersintothedesign.
• WithSRCductsilencers,thesoundpowerlevelsLWA can
bereducedbyupto25dB.
• Important:Thesoundlevelsindicatedinthenomogramsare
sound power levels! The values represent the sound energy
introducedintotheductsystem.Theyshouldbeappliedfor
acoustic calculations, e.g. when adding sound attenuators.
Pleasenote:ThesoundpowerlevelsLporLpA are specified more
thanoncetogenerallyindicateattenuationsofupto16dB.When
comparing numerical values, always bear in mind the difference
betweenthesoundpowerlevelandsoundpressurelevel.Further-
more,thedegreeofattenuationonlybecomesapparentoncethe
specificducts,deflections,branchesandroomshaveactuallybeen
connected.

Sound power level L
WA
[dB(A)]
Static pressure drop ΔpS [Pa]
Volume flow V [m3/h]
Flow velocity VA[m/s]
Volume flow V [m3/h]
Flow velocity V
A
[m/s]
Static pressure drop ΔpS [Pa]
Sound power level LWA [dB(A)]
Sound power level LWA [dB(A)]
Static pressure drop ΔpS [Pa]
Volume flow V [m3/h]
Flow velocity VA[m/s]
Static pressure drop ΔpS [Pa]
Sound power level L
WA
[dB(A)]
Volume flow V [m3/h]
Flow velocity VA [m/s]
Subject to change
User Manual 3.1 (2016-04) 6
VR1 volume flow controller
Soundpowerleveloutsidetheconnectingduct(radiatednoise)
SizeDN80 SizeDN100
SizeDN125 SizeDN160
Nomenclature⇒seepage7

Sound power level L
WA
[dB(A)]
Static pressure drop ΔpS [Pa]
Volume flow V [m
3
/h]
Flow velocity V
A
[m/s]
Sound power level L
WA
[dB(A)]
Flow velocity VA[m/s]
Static pressure drop
Volume flow
Sound power level LWA [dB(A)]
Static pressure drop ΔpS [Pa]
Volume flow V [m3/h]
Flow velocity VA[m/s]
Subject to change
User Manual 3.1 (2016-04)7
VR1 volume flow controller
Soundpowerleveloutsidetheconnectingduct(radiatednoise),nomenclature
SizeDN200 SizeDN250
SizeDN315
Nomenclature
V [m³/h] Volumeflow
AA [m²] Inflowcross-section
vA [m/s] FlowvelocityinAA
DpS [Pa] Staticpressuredrop
LWA [dB(A)] A-weightedsoundpowerlevel
LW-Oct[dB] OctavesoundpowerlevelLW-Oct=LWA+DL
DL [dB] RelativesoundpowerleveltoLWA
f [Hz] Octavemidfrequency
Lp [dB] Soundpressurelevel
LpA [dB(A)] A-weightedsoundpressurelevel
Example:
Specified: Size DN250
Volumeflow V = 1500 m³/h
Flow velocity vA = 8.5 m/s
Staticpressuredrop DpS= 340 Pa
Result: Radiatednoise
Soundpowerlevel*)L
WA = 55 dB(A)
*)The mean sound pressure level in the room with the following
equipmentis:
•26 dB less with acoustic insulation
•8 dB less without acoustic insulation
thanthesoundpowerlevelsspecifiedinthenomogramsLWA.
However,theacousticinsulationcanonlyachievethestatedvaluesif
the connected circular ventilation ducts are soundproofed (insulated)
accordingly.
Thesoundpressurelevelcanbefurtherreducedbycarryingout
additional sound attenuation measures on site (suspended ceilings,
high degree of room attenuation).

Adjusting voltage
Feedback voltage
1-wire control 2-wire control
1-wire control 2-wire control
Subject to change
User Manual 3.1 (2016-04)8
VR1 volume flow controller
Technicaldataforadjustingactuators,installationinstructions
Adjusting actuator M1
Adjusting actuator M2
Adjusting actuator M3
Installation instructions
• VR1 Volume flow controllers are adjusted for the entire scaled
application area.
•To install the controller, a straight inlet section which is at least
threetimesaslongasthenominaldiameterDNandastraight
outletsectionwhichisatleast1.5timesaslongasthenominal
diameterDNisrequired.Installationdirectlydownstreamorupstre-
amofflowdisruptionpoints(bends,branches,etc.)reducesthe
control accuracy.
• Thevolumeflowsetpointisadjustedduringinstallation.Thisdoes
not affect the control accuracy.
• Thebasicversionisadjustedmanuallybysettingthepointerto
the required set point on the scale and fixing this setting.
• VR1volumeflowcontrollersandSRCductsilencersaresupplied
individually.Assemblyonsite!
• Volume flow controllers with actuator-driven adjustment enable
two-pointoperation(single-wirecontrol)incombinationwiththe
actuatorsM1(230VAC)andM2(24VAC/DC).Thecorrespon-
dingmotorlimit stops arepositionedinorder to adjustthetwo
volume flows.
Inthedeliverycondition,thetwolimitstopsoftheactuatorsare
setatthe0directionoftravelandthelargestpossibleangleof
rotation. The maximum angle of rotation corresponds to the largest
possiblevolumeflowsetpoint,andtheminimumisequivalentto
a “cutoff” at a residual leakage that is significantly lower than the
minimum volume flow as specified in the catalogue.
Thiscanbeextendedtoincludethree-point operationusingan
additional 0 circuit arrangement (two-wire control). When actuated
in this way, the actuator remains in its current position and the
VR1volumeflowcontrolleradjuststhecorrespondingsetpoint.
• Volume flowcontrollerswith actuator-drivenadjustmentin com-
bination with the actuator M3 (24VAC/DC) enable continuous
adjustmentofthesetpoint.Theactuatorisactivatedbyanadjusting
voltageY=0...10VDCandtravelstothepositionspecifiedby
theactuatingsignal;inthiscasetheoperatingrangeofthemotor
only starts at 2 V. The volume flow set point changes more or less
linearlyinrelationtotheadjustingvoltage.
Inthedeliverycondition,theactuatorissetto0directionoftravel
andtheadjustablemechanicallimitstopsaresetforthelargest
possibleangleofrotation,whichmeansthatwhenY=10Vthe
maximum angle of rotation corresponding to the maximum volume
flow set point is approached, and at 0...2 V the minimum angle of
rotationisapproached;thiscorrespondstoa“cutoff”ataresidual
leakage that is significantly lower than the minimum volume flow
set point.
ThepurposeofthefeedbackvoltageU=2…10VDCistoprovide
an electrical indication of the volume flow set point setting and
serveasasubsequentactuatingsignalforotheractuators.
• Alladjustingactuatorsareoverload-proof,donotrequirealimit
switch and stop automatically at the limit stop.
• Sotheycanbeadjustedmanually,adjustingactuatorsareequip-
pedwithaself-resettingpushbutton.
• Thedirectionoftravelofalladjustingactuatorscanbereversed
via a changeover switch on the motor.
• Intheeventofapowerfailure,themotorremainsinitscurrent
position and the controller controls the corresponding set point.
• Assemblyinstructionsareenclosedwiththevolumeflowcontrollers
andmustbeobserved!
M1 M2 M3
Supplyvoltage 230VAC 24VAC/DC 24VAC/DC
Functionarea 85to265V 19.2to28.8V 19.2to28.8V
Torque 5Nm 5Nm 5Nm
Runtimefor90° 150s 150s 150s
Connectedload 4VA 2VA 2VA
Powerconsumption 1.5W 1W 1W
Degreeofprotection IP54 IP54 IP54
Connectioncable
approx. 1 m long
0.75mm² 3-wire 3-wire 4-wire
Ambienttemperature -30to+50°C -30to+50°C -30to+50°C
Technical data for adjusting actuators

Subject to change
User Manual 3.1 (2016-04) 9
VR1 volume flow controller
Orderdata,specificationtext
VR1 - - - - - -
DN size:
80/100/125/160/200/250/315
⇒see page 3
Actuator-driven set point adjustment:
230VACtwo-point/three-pointactuator
M1
24VAC/DCtwo-point/three-pointactuator
M2
24VAC/DCcontinuousactuator
M3
⇒ seepages2,3and8
Lip seal:
withtwolipseals LD
⇒ see pages 2 and 3
Maintenance-free, circular volume flow controller for position-
independent installation in circular ventilation ducts for supply
and exhaust air ventilation and air conditioning systems. Casing
and control mechanism made of galvanized sheet steel, with acoustic
insulation, with lip seals. With centrally supported damper blade for
volume flow control, with stainless steel bearing axis in special
bushings. Adjustment device with rotary pointer, scale and locking
device for the volume flow set point, can be adjusted manually or by
actuator. Volume flow controller designed as mechanical controller
for constant volume flows without auxiliary power supply. With
special control mechanism for a high degree of control accuracy
throughout the entire control range. The volume flow set point must
be infinitely adjustable throughout the control range. The volume
flow must be kept constant at variable pressures of between 50 and
1000 Pa with a deviation of roughly ±5% to ±10%. Casing tightness
class C according to DIN EN 1751. Certificate of conformity as proof
of compliance with the hygiene requirements according to
VDI 6022-1,
VDI 3803, DIN 1946-4, DIN EN 13779, SWKI VA104-01, SWKI 99-3, ÖNORM H6020
and ÖNORM H6021
.
With Environmental Product Declaration certificate
according to ISO 14025 and EN 15804.
........ Units
Volume flow: ......... m³/h
Pressure drop: ......... Pa
Maximum sound power level
Flow noise ......... dB(A)
including SRC duct silencer
Radiated noise ......... dB(A)
Manufacturer: WILDEBOER®
Type: VR1
Size: .........
complete with fixings deliver: ..........
install: .......... ..........
........ units SRC duct silencer 600 / 900
deliver: ..........
install: .......... ..........
Orderingexample:VR1-100-LD-DS-200-SRC900
with duct silencer
- mounting on site -
SRC600
SRC900(fromsizeDN100)
Presetting
-notwithactuator-drivensetpointadjustment
-Volumeflow[m³/h]
ThenumericalvaluemustbeintherangeVmin
and Vmaxaccordingtothesizeofthecontroller!
with acoustic insulation:
DS
⇒ see pages 2 and 3
Select texts not highlighted in bold as required!

TAKE ADVANTAGE OF OUR STRENGTHS!
Leipzig Office
Telephone:
Fax: +49 (0)
-mail: [email protected].de
+49 (0) 34444-310-0
34444-310-31
E
Ulm Office
Telephone:
Fax: +49 (0)
-mail: [email protected].de
+49 (0) 7392-9692-0
7392-9692-20
E
Head Office and Factory
Telephone:
Fax: +49 (0)
-mail: info@wildeboer.de
Web site: www.wildeboer.de
+49 (0) 4951-950-0
4951-950-120
E
Q U A L I T Y P R O D U C T S
Fire Protection Noise ProtectionAir Distribution
INNOVATIVE PRACTICAL EFFICIENT
© 2000 ... 2016 WILDEBOERBAUTEILEGMBHD26826WEENER,GERMANY
Table of contents
Popular Controllers manuals by other brands

STMicroelectronics
STMicroelectronics STM32 Cortex-M3 manual

Lefflerpost
Lefflerpost ATEM2LENS user guide

Allen-Bradley
Allen-Bradley PowerFlex 7000 user manual

Emerson
Emerson SH Series installation instructions

ANDO Technik
ANDO Technik Galcon 800248 Installation and operating manual

Honeywell
Honeywell H808C manual

Altronix
Altronix Maximal3F installation guide

DIG
DIG LEIT-2 operating instructions

Speck pumpen
Speck pumpen BADU Logic 3 Installation and operating instructions

Automationdirect.com
Automationdirect.com DL05 user manual

Omnio
Omnio REGJ12/04M Brief instructions

praher
praher Aquastar Comfort Safetypack manual