manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Honeywell
  6. •
  7. Controllers
  8. •
  9. Honeywell H808C User manual

Honeywell H808C User manual

1 69-0821
J.F. • 3-94 • ©Honeywell Inc. 1994 • Form Number 69-0821
H808C
Convertible Dehumidifier Controller
Application
The H808C Dehumidifier Controller provides automatic
low voltage control of dehumidifiers in central heating
systems. The humidity controller has an spst, snap-acting,
dust-proof switch and is designed for wall or surface duct
mounting.
MODELS:
■H808C1029: Premier White™.
■H808C1037: Beige.
ELECTRICAL RATING: 50 VA at 24 Vac.
MAXIMUM AMBIENT TEMPERATURE: 125°F [52°C].
SWITCH DIFFERENTIAL: 5 percent RH, nonadjustable.
SET POINT ADJUSTMENT RANGE: 20 to 80 percent
RH; positive ON and OFF positions.
Installation
CAUTION
1. Installer must be a trained, experienced service
technician.
2. Disconnect power supply before beginning
installation.
3. Conduct a thorough checkout before leaving
installation.
WALL MOUNTING
1. Locate the humidity controller about 5 ft [1.5m]
above the floor on an inside wall.
NOTES:
a. Be sure the humidity controller is subject to average
room temperature and average relative humidity.
The maximum temperature at the location selected
must not exceed 125°F [52°C].
b. The humidity controller can be mounted directly on
the wall.
2. Drill a small hole in the wall.
3. Run low voltage wiring to the location and pull about
6 in. [152 mm] of wire through the hole.
NOTE: Plug the opening to prevent drafts from affecting
humidity controller operation.
4. Remove the humidity controller assembly by prying
with a screwdriver in the notch on the bottom of the case
(Fig. 1).
5. Position the case horizontally over the wires with the
arrows on the tabs pointing up and secure the case to the
wall using the two screws provided.
6. Connect the wires to the humidity controller assem-
bly using leadwires and wire nuts provided (see Wiring
section and Fig. 2).
7. Tuck the wires into the bottom of the case.
8. Snap the cover assembly into the case (Fig. 2).
Fig. 1—Removing humidity controller assembly
from case.
M9262
Fig. 2—Wiring connections on humidity
controller.
UP
UP
UP
QUICK-CONNECT
WIRE LEAD
WIRE
NUT
CASE
COVER
MOUNTING
HOLE (2)
HUMIDIFIER
LEADWIRE
M9263
69-0821 2
DUCT MOUNTING
1. Locate the humidity controller at least 8 in. [203 mm]
upstream of the humidifier in the return air duct.
NOTE: If mounting near an elbow area, keep the humidity
controller 6 in. [152 mm] upstream of the elbow so the
element will be affected by the normal airflow (Fig. 3)
.2. Using Fig. 4 and the instructions on the template,
drill two mounting holes (3/32 in. [2.4 mm]) and 12 sensing
holes (1/4 in. [6.4 mm] in diameter) in the duct. (The
sensing holes allow return air to reach the nylon sensing
element and operate the humidity controller.)
NOTE: If desired, cut a square hole in the duct as indicated
on the template in place of the sensing holes.
Fig. 3—Selecting a duct location for the humid-
ity controller.
BEST LOCATION
RETURN
AIR
RETURN
AIR
6 in. [152 mm]
MINIMUM
15 in. [381 mm]
MINIMUM
ALTERNATE
LOCATIONS
RETURN AIR DUCT M9277
3. Remove the protective backing from the foam gasket
included with each control and apply the foam gasket to the
template in the location indicated.
4. Remove the cover and humidity controller assembly
from the case by prying with a screwdriver in the notch in
the bottom of the case (Fig. 1).
5. Run low voltage wire from the humidity controller to
the template (Figs. 5 and 6).
6. Lay wire over one side of the foam gasket allowing
about 6 in. [152 mm] for connection to the humidity con-
troller. Wire can enter the humidity controller case from
any direction.
NOTE: Do not position wire directly under the two stand-
off projections at the back of the case. If wire is under
these projections, the case will not seat tightly against
the gasket, causing air leakage and possible improper
operation.
7. While holding wire in place, mount the case on the
duct using the two mounting screws provided.
NOTE: Tighten the screws firmly so the gasket seals the
space between the case and the duct (Fig. 4).
8. Connect the wires to the humidity controller assem-
bly using leadwires and wire nuts supplied (see Wiring
section and Fig. 2).
9. Snap cover assembly into the case.
Fig. 4—Mounting humidity controller on return
air duct.
UP
TEMPLATE
LOCATE TEMPLATE.
PEEL BACKING
FROM TEMPLATE
AND APPLY TO DUCT.
PUNCH AND DRILL
TWO 3/32 IN. [3 mm]
MOUNTING HOLES.
DRILL MINIMUM
OF TWELVE
1/4 IN. [7 mm] HOLES.
OR
DRILL OR PUNCH
CORNER HOLES AND
CUT OUT SQUARE
ON SOLID LINE.
GASKET
CASE
M9264
1
2
3
4
3 69-0821
Fig. 5—Typical parallel wiring diagram of H808C with T87F/Q539A combination for dehumidification
and mildew control.
Fig. 6—Typical series wiring diagram of H808C with T87F/Q539A combination for dehumidification and
mildew control.
TEMPERATURE
FALL
1
2
3
PROVIDE OVERLOAD PROTECTION AND DISCONNECT MEANS
AS REQUIRED.
HEATING DAMPER MOTOR, IF USED.
CLOGGED FILTER SWITCH OR COOLING PANEL CONNECTION.
1
3 2
BX O
R1
W Y
W1 Y1
G RHR
HEAT OFF FANAUTO ONCOOL
HEAT OFF COOL
FIXED
COOL
ANTICIPATOR
ADJUSTABLE
HEAT
ANTICIPATOR
HEATING
RELAY OR
VALVE COIL
COOLING
CONTACTOR
COIL
FAN RELAY
COIL
M18627
T87F/Q539A INTERNALSCHEMATIC
FILTER
LIGHT
T87F
H808C
TEMPERATURE
FALL
1
2
3
PROVIDE OVERLOAD PROTECTION AND DISCONNECT MEANS
AS REQUIRED.
HEATING DAMPER MOTOR, IF USED.
CLOGGED FILTER SWITCH OR COOLING PANEL CONNECTION.
1
3 2
BX O
R1
W Y
W1 Y1
G RHR
HEAT OFF FANAUTO ONCOOL
HEAT OFF COOL
FIXED
COOL
ANTICIPATOR
ADJUSTABLE
HEAT
ANTICIPATOR
HEATING
RELAY OR
VALVE COIL
COOLING
CONTACTOR
COIL
FAN RELAY
COIL
M18626
T87F/Q539A INTERNALSCHEMATIC
FILTER
LIGHT
T87F
H808C
69-0821 4
QUALITY IS KEY
Home and Building Control Home and Building Control Helping You Control Your World
Honeywell Inc. Honeywell Limited—Honeywell Limitée
1985 Douglas Drive North 740 Ellesmere Road
Golden Valley, MN 55422 Scarborough, Ontario
M1P 2V9
Printed in U.S.A.
Fig. 7—Typical wiring diagram for H46C,E.
DUCT MOUNT HUMIDITY CONTROLLER
If the temperature at the humidity controller location
on the return air duct is less than 80°F [27°C] ,use the
procedure for wall mounted humidity controllers.
If the air surrounding the humidity controller is greater
than 80°F [27°C], reset the recommended settings to
compensate for the higher ambient temperature. High ambi-
ent temperatures will cause the humidity controller to control
at an increased setting. To determine the compensated set
point for surface mounted humidity controllers with high
ambient temperatures, use the following procedure:
1. With a bulb type thermometer, accurately determine
the surrounding duct temperature at the humidity controller
location.
2. Decrease the recommended setting about five percent
for each 5°F [3°C] above 80°F [27°C] at the humidity
controller.
For example, if the humidity controller is set at 25 per-
cent and the temperature at the humidity controller is 90°F
[32°C], the compensated set point should be 15 percent.
(This is the 25 percent setting less 10 percent for the 10°F
[6°C] above ambient temperature.)
Checkout
Place the system in operation and observe through at
least one complete cycle to make certain that all compo-
nents are functioning properly.
WIRING
All wiring must comply with local codes and ordi-
nances. Make wiring connections according to to dehu-
midifier instructions if available; otherwise, see typical
wiring diagrams in Figs. 5 and 6.
Settings
HUMIDITY CONTROLLER ADJUSTMENT
The humidity comfort range of a living space is gener-
ally between 25 and 50 percent RH. However, as the
outdoor temperature changes, the humidity level on the
humidity controller may need to be reset to assure maxi-
mum comfort.
To reduce the relative humidity, reduce the set point ap-
proximately three percent RH every 24 hours. To increase
the relative humidity, increase the set point approximately
three percent RH every 24 hours.
WALL MOUNT HUMIDITY CONTROLLER
Set the humidity set point according to the prevailing
outdoor temperature to provide optimum relative humidity
control for most installations. Adjust the humidity level to
a particular structure using the procedure above.
HUMIDITY
RISE
L1
(HOT)
L2
POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.
1
1
M9297
H46C, E CONTROLLER
DEHUMIDIFIER
EXHAUST FAN
OR AIR
CONDITIONER

Other Honeywell Controllers manuals

Honeywell HC900 User manual

Honeywell

Honeywell HC900 User manual

Honeywell RA890G User manual

Honeywell

Honeywell RA890G User manual

Honeywell VC6613AJ1000 User manual

Honeywell

Honeywell VC6613AJ1000 User manual

Honeywell VS820 POWERPILE User guide

Honeywell

Honeywell VS820 POWERPILE User guide

Honeywell HVC0001 User manual

Honeywell

Honeywell HVC0001 User manual

Honeywell EXCEL 5000 OPEN ZAPP User manual

Honeywell

Honeywell EXCEL 5000 OPEN ZAPP User manual

Honeywell PEHA D CDH8U5 Series Installation and operation manual

Honeywell

Honeywell PEHA D CDH8U5 Series Installation and operation manual

Honeywell HR 40 User manual

Honeywell

Honeywell HR 40 User manual

Honeywell HCE80R User manual

Honeywell

Honeywell HCE80R User manual

Honeywell S9360A User manual

Honeywell

Honeywell S9360A User manual

Honeywell S9240F2051 User manual

Honeywell

Honeywell S9240F2051 User manual

Honeywell Ex-Or MLSM2000A Installation and operation manual

Honeywell

Honeywell Ex-Or MLSM2000A Installation and operation manual

Honeywell HR 80 User manual

Honeywell

Honeywell HR 80 User manual

Honeywell PRO 2000 Series Owner's manual

Honeywell

Honeywell PRO 2000 Series Owner's manual

Honeywell SLATE Series User manual

Honeywell

Honeywell SLATE Series User manual

Honeywell 1000 Series User manual

Honeywell

Honeywell 1000 Series User manual

Honeywell R4560 User manual

Honeywell

Honeywell R4560 User manual

Honeywell SMARTBOX User manual

Honeywell

Honeywell SMARTBOX User manual

Honeywell CP-UL1012S User manual

Honeywell

Honeywell CP-UL1012S User manual

Honeywell UDC120L User manual

Honeywell

Honeywell UDC120L User manual

Honeywell W7752D2007 User manual

Honeywell

Honeywell W7752D2007 User manual

Honeywell NPB-2X-RS485 User manual

Honeywell

Honeywell NPB-2X-RS485 User manual

Honeywell BC7000L1000 Manual

Honeywell

Honeywell BC7000L1000 Manual

Honeywell Zio TR70 User manual

Honeywell

Honeywell Zio TR70 User manual

Popular Controllers manuals by other brands

Trane Tracer ZN521 Installation and operation

Trane

Trane Tracer ZN521 Installation and operation

Omega Engineering DP25-TH quick start

Omega Engineering

Omega Engineering DP25-TH quick start

Azatrax TS2 installation guide

Azatrax

Azatrax TS2 installation guide

Lumascape ZDClink owner's manual

Lumascape

Lumascape ZDClink owner's manual

DAB ACTIVE DRIVER M/M 1.1 Instruction for installation and maintenance

DAB

DAB ACTIVE DRIVER M/M 1.1 Instruction for installation and maintenance

WOBIT MIC488 user manual

WOBIT

WOBIT MIC488 user manual

Holmes Hobbies TorqueMaster BR-XL user guide

Holmes Hobbies

Holmes Hobbies TorqueMaster BR-XL user guide

National Instruments RMC-8354 user manual

National Instruments

National Instruments RMC-8354 user manual

Daikin iLINQ quick start guide

Daikin

Daikin iLINQ quick start guide

Renesas RA6T2 Application note

Renesas

Renesas RA6T2 Application note

Datalogic Controller SC6000 Reference manual

Datalogic

Datalogic Controller SC6000 Reference manual

Omron E5ZN Series manual

Omron

Omron E5ZN Series manual

Kelly KBS24051 user manual

Kelly

Kelly KBS24051 user manual

Dungs FRM 100065 instructions

Dungs

Dungs FRM 100065 instructions

SMC Networks FC3W5 Series Operation manual

SMC Networks

SMC Networks FC3W5 Series Operation manual

M-system PSN1 instruction manual

M-system

M-system PSN1 instruction manual

Trio Flex-6 Nano P601 quick start guide

Trio

Trio Flex-6 Nano P601 quick start guide

Rotary SR-2835RGB quick start guide

Rotary

Rotary SR-2835RGB quick start guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.