613273-00 60710-131
ADDING THE CONTROLLER TO THE DSEGATEWAY
To ensure newly added controllers are recognised by the DSEGateway®, the
following steps must be followed. Failure to do so may result in communications
failure, indicated by a RED communications port LED.
• The DSEGateway®is factory set to accept connection via the USB port. If
this is not the port to be used, you must configure the DSEGateway®for the re-
quired port as detailed elsewhere in this document.
• Remove the DC supply from the DSEGateway®AND the connected
controller(s).
• Connect the new controller to the chosen communications port.
• Apply the DC supply to the controller being added (and any other control-
lers in the system).
• Reapply the DSE supply to the DSEGateway®Gateway.
• For a short time (approx 10 seconds), the communication ports in use il-
luminate RED.
• If correctly configured and connected, the ports will begin to flash GREEN
as data is received by the DSEGateway®.
• The LINK LED will illuminate GREEN when connection to the DSEWebNet
server is established.
This instruction sheet is provided in assisting in the installation of the
DSE890 module. For a complete DSE installation and operation manual
please go to DSE website @ www.deepseaplc.com. Document # 057-165.
Winco Inc.
Service Dept.
507-357-6831