Winext AN-303 User manual

AN-303 Temperature Humidity Sensor
0

AN-303 Temperature Humidity Sensor
1
Content
1. Introduction ......................................................................................................................2
1.1 Description ...............................................................................................................2
1.2 Features ...................................................................................................................2
1.3 Specification.............................................................................................................2
2. Structure ..........................................................................................................................4
2.1 Appearance and dimension .....................................................................................4
2.2 Packing contents......................................................................................................4
3. How to work .....................................................................................................................5
3.1 Process ....................................................................................................................5
3.2 Use .........................................................................................................................6
4. Installation........................................................................................................................7
5. Configuration....................................................................................................................8
5.1 Tool list.....................................................................Error! Bookmark not defined.
5.2 Set up ......................................................................Error! Bookmark not defined.
5.2.1 Tools................................................................Error! Bookmark not defined.
5.2.2 Install wireless configuration module driver ...Error! Bookmark not defined.
5.2.3 Parameter configuration ................................................................................12
5.3 Remote configuration.............................................................................................15
6. Communication Format .................................................................................................17
7. Caution...........................................................................................................................18

AN-303 Temperature Humidity Sensor
2
1. Introduction
1.1 Description
AN-303 is a wireless temperature and humidity unit for data gathering and monitoring.
It has a built-in temperature and humidity chip. It has small body size and high
accuracy. With stable performance, low power consumption, it is suitable for data
transmission in long distance. Based on long battery life, free wiring installation,
AN-303 temperature and humidity sensor decreases the system cost greatly.
Application
Communication room, workshop line, drug warehouses, logistics warehouse,
agricultural greenhouses, archives, museums, hvac control and etc
1.2 Features
Support LoRaWANTM
Support Temperature and humidity detecting
Built-in 8500mAh battery
Wide humidity and temperature detection range
Support Temperature high and low threshold value setting
1.3 Specification
Function
Item
Description
Hardware parameter
Temperature detecting
range
-30℃~70℃
Temperature precision
±0.5℃
Humidity detecting
range
0~99.9%RH(non-condensing)
Humidity precision
±3%RH
Antenna
Built-in LoRa antenna
Wireless
performance
Tx rate
300bps-5.4Kbps
Protocol
Support LoRaWANTM and P2P

AN-303 Temperature Humidity Sensor
3
Function
Item
Description
Hardware parameter
Temperature detecting
range
-30℃~70℃
Temperature precision
±0.5℃
Humidity detecting
range
0~99.9%RH(non-condensing)
Humidity precision
±3%RH
Antenna
Built-in LoRa antenna
Frequency
CN470-510MHz
EU863-870MHz
US902-928MHz
AS923MHz
AU915-928MHz
KR920-923MHz
RU864-870MHz
IN865-867MHz
Max Tx power
17dBm
Rx sensitivity
-140dBm(SF=12)
Electric parameter
Power consumption
36mW
Battery capacity
3.6V/8000mA
Battery
Built-in Li-SOCL2 battery
VCC
DC 3.6V
Standby electric current
<=9uA
Tx current
<=125mA
Physical parameter
IP grade
IP30
Dimension
86mm*86mm*26mm

AN-303 Temperature Humidity Sensor
4
2. Structure
2.1 Appearance and dimension
Figure: AN-303
Figure: AN-303 Dimension(mm)
2.2 Packing contents
Accessory
Qty(pc)
AN-303 Temperature Humidity
sensor
1
Installation board
1
Screw and plastic rubber
2
User manual
1

AN-303 Temperature Humidity Sensor
5
3. How to work
3.1 Process
Figure: AN-303 Workflow

AN-303 Temperature Humidity Sensor
6
Figure: AN-303 Data Workflow
3.2 Use
Turn on: Press and hold the Turn on/off button at the back of the device for about
three seconds with the green light constant on until the buzzer gives out the sound.
Then the green light goes out. And the buzzer will stop automatically after three
beeps (di, di, di), indicating that the device is started.
Join network: When the device is turned on, the buzzer will sound "di" and "di",
indicating that the device is connected to the network.
Anti-dismantle button: After the device installation finished, the anti-dismantle
button is pushed against. When it detects the anti-dismantle button is released for
three seconds, the alarm will be reported and the red light will flash. When it
detects the tamper button is pushed against for three seconds, it will report
anti-dismantle status resume.
Turn off: Hold and press Turn on/off button for three seconds with the green
light on, until a long sound of buzzer sound heard and the green light is off.
Release the button, the device is off.
Note: It needs to wait for a while to reboot the device after it turned off.

AN-303 Temperature Humidity Sensor
7
4. Installation
Please prepare installation tools. Here are tools that may be used below.
Figure: Installation Tool
Quick Install
1. Put the back board at a proper position on the wall without tilting. Mark the
position and use percussion drill to make holes there.
2. Put the plastic cover in to the holes, align the back board in the holes on the wall,
use the taping screw to secure the back board.
3. Put AN-303 above the back board with AN-303 holder corresponding to back
board clasp. When they clasp together and pull AN-303 down.
Note: It can use gelatin sponge to adhere AN-303 on the surface where cannot drill
holes such as metal and glass wall. Put one side of gelatin sponge adhere to the
surface and put its other side to back board clasp. When AN-303 holder corresponding
to back board clasp get together and pull AN-303 down, a snap sound is heard. That
means installation is completed.

AN-303 Temperature Humidity Sensor
8
5. Configuration
5.1 Precaution
For device normal operation and detection accuracy, please pay attention to the
following matters before configuration:
Before configuration, please contact our technical staff for the relevant
software and manual.
For wireless configuration, it should be done within the signal coverage area
of the wireless configuration tool
5.2 Tool list
Note: For configuration, you can use wireless configuration tool (wireless
configuration) or USB to TTL cable (cable configuration), but here we choose to tell
customer how to do wireless configuration.
Item
Description
Laptop
Installation
Wireless Configuration tool
The laptop communicates with device via
wireless configuration tool ireless
configuration tool(wireless configuration),
you should install CP210x driver for this
tool
Configuration software
Winext manage App
5.3 Wireless configuration
5.3.1 Wireless configuration tool
Configuration tools as below:

AN-303 Temperature Humidity Sensor
9
a) Install the CP210x driver for wireless configuration tool, file as below:
b) Install Winext manage App, file as below:
5.3.2 Install CP210x driver for wireless configuration tool
(1) Open CP210x driver for wireless configuration tool
(2) Select the driver program to install depending to the system type.
32-bit operating system selects “CP210xVCPInstaller_x86.exe”.
64-bit operating system selects "cp210xvcpinstaller_x64.exe".
(3) Install Wireless configuration tool driver
Here we take an example to use the 64-bit operating system to install the wireless
configuration tool driver
Click and select Next to the driver file "cp210xvcpinstaller_x64.exe".

AN-303 Temperature Humidity Sensor
10
As below:
Select Accept the License Agreement and click on Next, as below:

AN-303 Temperature Humidity Sensor
11
Wait for a while and click on Finish, as below:
Check the driver program after installation finished. Click on Computer-Attribute-
Device manager, as below:

AN-303 Temperature Humidity Sensor
12
5.3.3 Parameter setting
(1) Insert the wireless configuration tool into the laptop USB port. Start host
configuration near the device installation location.
(2) Insert the wireless configuration tool to the USB port. Click on
Computer-Attribute-Device manager and find the correct port (Enhanced COM
Port), as below:
Note: there are two ports for wireless configuration tool, only one of them is for
configuration (Enhanced COM Port)

AN-303 Temperature Humidity Sensor
13
(3) Open Winext manage APP and click on T/T sensor AN-303.
Select port and open it.
(4).Reboot AN-303. Select the DevUI in the check box and click on Lock address.

AN-303 Temperature Humidity Sensor
14
After the device locked successfully, you can edit parameters for setting up and query.
The parameters are for functions and LoRaWAN setting. For example, edit the high
temperature threshold value as 45℃, query the high temperature threshold value, it
will shows 45℃ in the Receive date box.
If you edit the high temperature threshold value as 60℃, query the high temperature threshold
value, it will shows 60℃ in the Receive date box.

AN-303 Temperature Humidity Sensor
15
Note:
After the device reboot, the device is in wireless configuration mode. Please click on Lock
address within 5 seconds. It will try to join the network in 5 sends later.
After the device locked successfully, and without operation in 15 seconds, the device
will exit from wireless configuration to network connection.
5.3 Remote configuration
Description: the remote configuration is done by AT command issued at the platform.
The port number is 220. The data format is hexadecimal with FF added in front. The
corresponding AT command needs to be converted into hexadecimal data first. The
hexadecimal data FF is added in front of the packet to send.
1. Convert the AT command into hexadecimal data step by step
a. AT command AT+REBOOT to convert 16-byte data for 41 54 2B 52 45 42 4F 4F
54 0D 0A
b. The last part of the command, 0D 0A, can be omitted
c. Add FF in front of it

AN-303 Temperature Humidity Sensor
16
FF 41 54 2B 52 45 42 4F 4F 54 0D 0A or FF 41 54 2B 52 45 42 4F 4F 54
2. Enter the device management platform, click Downlink, and fill in the data and
port number
3. After entering in the data and port number, click OK. Waiting for the node to
report, the platform will send the data to the corresponding node.

AN-303 Temperature Humidity Sensor
17
6. Communication Format
Fport: 45. Here are the frame definitions below:
No.
Definition
Description
①
Device ID
0x01 fixed value
②
Frame format
0x00: Heartbeat frame, 0x01: Data frame
③
Anti-dismantle
0x00: Not dismantle;
0x01:Dismantled
④
Temperature status
0x00: Normal
0x01: High temperature threshold alarm
0x02: Low temperature threshold alarm
⑤
⑤⑥ works as a combination of
16 bit signed number. It is 10
times of the current temperature
⑤ is high level bite
⑥
⑥ is low level bite
⑦
Humidity status
0x00: Normal
0x01: High humidity
0x02: Low humidity
⑧
⑧⑨works as a combination of 16
bit no unsigned number. It is 100
times of the current humidity
⑧ is high level bit
⑨
⑨ is low level bit
⑩
⑧⑨works as a combination of 16
bit no unsigned number. It is 100
times of the current power
⑩ is high level bite, the highest level
indicates current power status:
0: Normal 1: Low power
⑪
⑪ is low level bite

AN-303 Temperature Humidity Sensor
18
7. Caution
1. Do not be used in salt mist condition, acid condition, alkaline condition or organic
solvents condition.
2. Avoid to use in dusty environment.
3. Do not expose to sunlight or strong ultraviolet radiation for a long time, which may
impact on performance.
4. It is prohibited to use in the condition with high concentration of chemical pollution,
which will cause its induction layer damage.
5. Put it in well ventilated condition and not to place it too close to the wall.
6. Please pay attention to signal attenuation when the device needs to carry out
long-distance transmission.
7. Please read this manual carefully and keep it for further reference.
Shenzhen Winext Technology Co., Ltd.
Address: 5th Floor, Building B50, Zhongchuang Industrial Park, Liuxian Rd, Taoyuan
Street, Nanshan District, Shenzhen 518055, China
Tel:(+86) 0755-23990916
Web: www.winext.cn
http://winext.en.alibaba.com
-------------------------------------------------------------------------------------------------------
This is a product manual as an installation, operation and use file. Specifications subject to change are without
notice. For more information, please call us or contact the sales staff.
Table of contents
Popular Temperature Controllers manuals by other brands

Ekinex
Ekinex EK-EQ2-TP- Series Applications manual

RKC INSTRUMENT
RKC INSTRUMENT RZ100 instruction manual

HeaterMate
HeaterMate TH81OT instruction manual

Ropex
Ropex CIRUS UPT-6010 operating instructions

S+S Regeltechnik
S+S Regeltechnik THERMASREG Frija I Series Operating Instructions, Mounting & Installation

Procool