Page - 4
Z-WAVE CONFIGURATION TABLE
Parameter Description Length
(Bytes) R/W Default
Value Valid Values
1 Time between Battery Reports (hours) 1 R/W 0 0 = Do not send periodically; Range: 1–127 hours
2 Send BASIC SET ON above this temperature (See #20) 1 R/W 121 121 = Disabled; Range: 15 – 120° F
3 Send BASIC SET ON below this temperature (See #20) 1 R/W 121 121 = Disabled; Range: 15 – 120° F
4 Send BASIC SET OFF above this temperature (See #20) 1 R/W 121 121 = Disabled; Range: 15 – 120° F
5 Send BASIC SET OFF below this temperature (See #20) 1 R/W 121 121 = Disabled; Range: 15 – 120° F
6 Send multiple attempts for all BASIC SET commands 1 R/W 0 0 = Disabled; 1-5 = Number of extra attempts sent every
minute after first send
7 Temperature Units 1 R/W 1 0 = Celsius; 1 = Fahrenheit
8 Association Group1 – Temperature delta auto send threshold 1 R/W 10 Range: 1 – 200; Parameter is in tenths of degrees.
9 Association Group1 – Periodic temperature send interval 1 R/W 0 0 = Disabled; Range: 1-120 minutes
10 Association Group2 – Temperature delta auto send threshold 1 R/W 10 0 = Disabled; Range: 1 – 50; Parameter is in tenths of
degrees.
11 Association Group2 – Periodic temperature send interval 1 R/W 0 0 = Disabled; Range: 1-120 minutes
12 Send BASIC SET ON above this humidity (See #20) 1 R/W 0 0 = Disabled; Range: 1–100%
13 Send BASIC SET ON below this humidity (See #20) 1 R/W 0 0 = Disabled; Range: 1-100%
14 Send BASIC SET OFF above this humidity (See #20) 1 R/W 0 0 = Disabled; Range: 1-100%
15 Send BASIC SET OFF below this humidity (See #20) 1 R/W 0 0 = Disabled; Range: 1-100%
16 Association Group1 – Humidity delta auto send threshold 1 R/W 5 Range: 1-50%
17 Association Group1 – Periodic humidity send interval 1 R/W 0 0 = Disabled; Range: 1-120 minutes
18 Association Group3 – Humidity delta auto send threshold 1 R/W 5 0 = Disabled; Range: 1-30%
19 Association Group3 – Periodic humidity send interval 1 R/W 0 0 = Disabled Range: 1-120 minutes
20 BASIC SET options for temperature and humidity 1 R/W 1
Configuration Register Combinations:
1 = Enable Registers 2, 5, 12 15
2 = Enable Registers 2, 5, 13, 14
3 = Enable Registers 3, 4, 12, 15
4 = Enable Registers 3, 4, 13, 14
21 Temperature Offset 1 R/W 0 Range: -7 to 7° F
22 Humidity Offset 1 R/W 0 Range: -7% to 7%
23 Humidity Filter Time Constant 1 R/W 30 Range: 0 - 60 minutes 0 = Disabled
ASSOCIATION GROUP INFORMATION TABLE
GROUP PROFILE COMMAND CLASSES GROUP NAME MAX DEVICES
1 Lifeline Battery Report, Multilevel Sensor Report, Device Reset
Locally Notification Lifeline 1
2 Sensor Multilevel Sensor Report Temperature Reports 5
3 Sensor Multilevel Sensor Report Humidity Reports 5
4 Sensor Basic Set Temperature Driven Basic Sets 5
5 Sensor Basic Set Humidity Driven Basic Sets 5
6 Sensor Battery Report Battery Reports 5
FCC/IC NOTICES
FCC ID: WIBTZW020 - This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference,
and (2) This device must accept any interference received, including interference that may cause undesired operation.This equipment has been tested and found to comply with
the limits for Class B Digital Device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential
installation. This equipment generates and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference
to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or
television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures.
• Reorient or relocate the receiving antenna
• Increase the separation between the equipment and receiver
• Connect the equipment into an outlet on a circuit different from that to which the receiver is connected
• Consult the dealer or an experienced radio/TV technician for help
Any changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.
IC ID: 9374A-W020 - This device complies with Industry Canada license-exempt RSS standard(s). Operation is subject to the following two conditions: (1) this device may not cause
interference, and (2) this device must accept any interference, including interference that may cause undesired operation of the device.
Le présent appareil est conforme aux CNR d’Industrie Canada applicables aux appareils radio exempts de licence. L’exploitation est autorisée aux deux conditions suivantes : (1) l’appareil ne
doit pas produire de brouillage, et (2) l’utilisateur de l’appareil doit accepter tout brouillage radioélectrique subi, même si le brouillage est susceptible d’encompromettre le fonctionnement.
U.S.A. / Canada
(877) 288-7707
About Trane and American Standard Heating and Air Conditioning
Trane and American Standard create comfortable, energy efficient
indoor environments for residential applications. For more information,
please visit www.trane.com or www.americanstandardair.com
Representative-only illustrations included in this document.
The manufacturer has a policy of continuous data
improvement and it reserves the right to change design
and specifications without notice. We are committed to
using environmentally conscious print practices.
All trademarks referenced are the trademarks of their
respective owners. Z-Wave is a trademark of Z-Wave
Alliance. © 2021
18-HD83D1-5B-EN 26 Aug 2021
Supersedes 18-HD83D1-5A-EN (August 2020)
*
* Configurable through third party Z-Wave systems.