Ekinex EK-EQ2-TP- Series Instructions for use

Application manual
KNX room temperature controller
EK-EQ2-TP

Application manual
KNX room temperature controller EK-EQ2-TP
Release 3.00 - Updating: 27/06/2017 Application Manual
© SBS S.p.A. - All rights reserved Page 2
Index
Foreword.............................................................................................................................................................6
1General information .......................................................................................................................................6
1.1 Function .................................................................................................................................................6
1.2 Main funcional features..........................................................................................................................6
1.3 Technical data ........................................................................................................................................7
1.4 Design ....................................................................................................................................................7
1.5 Delivery ..................................................................................................................................................8
1.6 Accessories............................................................................................................................................8
1.7 Marks and certification ...........................................................................................................................8
2Installation......................................................................................................................................................9
2.1 Connection.............................................................................................................................................9
2.1.1 Connection of the bus line..............................................................................................................9
2.1.2 Connection of the inputs ................................................................................................................9
3Configuration and commissioning ...............................................................................................................11
3.1 Configuration........................................................................................................................................11
3.1.1 Tree structure of the application program ....................................................................................11
3.1.2 Languages of the application program.........................................................................................12
3.2 Commissioning ....................................................................................................................................13
3.2.1 Displaying physical address and firmware release ......................................................................13
4User interface ..............................................................................................................................................15
4.1 LCD-display .........................................................................................................................................15
4.1.1 Information displaying ..................................................................................................................15
4.1.2 Segment test ................................................................................................................................16
4.1.3 Backlight.......................................................................................................................................17
4.2 Rockers................................................................................................................................................17
5Sensors........................................................................................................................................................18
5.1 Temperature sensor .............................................................................................................................18
5.2 Relative humidity sensor......................................................................................................................18
6Input variables .............................................................................................................................................19
7Application program for ETS .......................................................................................................................20
7.1 About EK-EQ2-TP................................................................................................................................20
7.1.1 General.........................................................................................................................................21
7.1.2 Parameters...................................................................................................................................21
7.2 Internal sensors ...................................................................................................................................23
7.2.1 Parameters...................................................................................................................................23
7.2.2 Temperature sensor .....................................................................................................................23
7.2.2.1 Parameters and communication objects................................................................... 23
7.2.3 Relative humidity sensor ..............................................................................................................25
7.2.3.1 Parameters and communication objects................................................................... 25
7.3 Inputs ...................................................................................................................................................27

Application manual
KNX room temperature controller EK-EQ2-TP
Release 3.00 - Updating: 27/06/2017 Application Manual
© SBS S.p.A. - All rights reserved Page 3
7.3.1 Input X ..........................................................................................................................................27
7.3.2 Parameters and communication objects......................................................................................27
7.4 External sensors (from bus).................................................................................................................31
7.4.1 Parameters and communication objects......................................................................................31
7.5 Weighted temperature value................................................................................................................34
7.5.1 Parameters and communication objects......................................................................................34
7.6 LCD-display .........................................................................................................................................36
7.6.1 Parameters...................................................................................................................................36
7.7 Leds .....................................................................................................................................................38
7.7.1 Parameters and communication objects......................................................................................38
7.8 Temperature control .............................................................................................................................40
7.8.1 Settings ........................................................................................................................................40
7.8.1.1 Parameters and communication objects................................................................... 40
7.8.1.2 Heating/cooling switchover ....................................................................................... 43
7.8.1.3 Valve protection function ........................................................................................... 44
7.8.1.4 Remote Setpoint modification ................................................................................... 44
7.8.1.5 Remote operative mode modification ....................................................................... 45
7.8.2 Heating .........................................................................................................................................47
7.8.2.1 Parameters and communication objects................................................................... 47
7.8.3 Cooling .........................................................................................................................................52
7.8.3.1 Parameters and communication objects................................................................... 52
7.8.4 Main and auxiliary ventilation .......................................................................................................57
7.8.4.1 Parameters and communication objects................................................................... 57
7.8.4.2 Delayed fan start (“hot-start”) function ...................................................................... 60
7.8.4.3 Antistratification function ........................................................................................... 60
7.8.4.4 2-stage configuration with fan-coils as auxiliary stage.............................................. 60
7.8.4.5 Remote fan speed modification................................................................................. 61
7.8.5 Scenes .........................................................................................................................................63
7.8.5.1 Parameters and communication objects................................................................... 63
7.9 Relative humidity control......................................................................................................................65
7.9.1 Dehumidification...........................................................................................................................65
7.9.1.1 Parameters and communication objects................................................................... 65
7.9.2 Humidification...............................................................................................................................67
7.9.2.1 Parameters and communication objects................................................................... 67
7.10 Comfort ................................................................................................................................................68
7.10.1 Comfort area ................................................................................................................................68
7.10.1.1 Parameters and communication objects................................................................... 68
7.10.2 Calculated psychrometric values .................................................................................................69
7.10.2.1 Parameters and communication objects................................................................... 69
7.11 Energy saving ......................................................................................................................................71

Application manual
KNX room temperature controller EK-EQ2-TP
Release 3.00 - Updating: 27/06/2017 Application Manual
© SBS S.p.A. - All rights reserved Page 4
7.11.1 Window contacts ..........................................................................................................................71
7.11.1.1 Parameters and communication objects................................................................... 71
7.11.2 Presence sensors ........................................................................................................................72
7.11.2.1 Parameters and communication objects................................................................... 72
7.11.3 Card holder...................................................................................................................................73
7.11.3.1 Parameters and communication objects................................................................... 73
7.12 Additional warnings..............................................................................................................................75
7.13 Logic functions .....................................................................................................................................76
7.13.1 Parameters and communication objects......................................................................................76
8List of communication objects .....................................................................................................................78
9Regulation algorithms..................................................................................................................................81
9.1.1.1 Two-point control with hysteresis .............................................................................. 81
9.1.1.2 Continuous Proportional-Integral control .................................................................. 83
9.1.1.3 PWM Proportional-Integral control ............................................................................ 84
9.1.1.4 Fan-coil with ON-OFF fan speed control .................................................................. 86
9.1.1.5 Fan-coil with continuous speed control ..................................................................... 88
9.1.1.6 2 points control with hysteresis for auxiliary stage.................................................... 90
9.1.1.7 Auxiliary stage with fan-coil....................................................................................... 90
10 Diagnostics ..................................................................................................................................................92
11 Warnings......................................................................................................................................................93
12 Other information.........................................................................................................................................93

Application manual
KNX room temperature controller EK-EQ2-TP
Release 3.00 - Updating: 27/06/2017 Application Manual
© SBS S.p.A. - All rights reserved Page 5
Revision
Updating
Date
3.00
ETS application version: VER 3.00.
Modified and/or added features:
Communication object 101 Building protection HVAC mode active
Communication object 102 Fan manual speed percentage
Communication object 103 Fan manual speed off status
Brightness sensor and corresponding functionalities removed
27/06/2017
2.00
ETS application version: VER 2.00.
Modified and/or added features:
Heating/cooling status out and Heating/cooling status in communication objects (more enhanced
management)
Communication objects for operating modes’ remote control, setpoint temperature and auto/manual
mode of fan
Logic functions AND, OR, EXOR, 4 inputs, 8 channels
20/06/2016
1.00
Emission
02/04/2015
The latest revision of the application manual is available at www.ekinex.com. For previous revisions, contact
the technical support at sup[email protected].

Application manual
KNX room temperature controller EK-EQ2-TP
Release 3.00 - Updating: 27/06/2017 Application Manual
© SBS S.p.A. - All rights reserved Page 6
Foreword
The present document describes the ekinex® KNX room temperature controller with LC-display (EK-EQ2-TP
version).
1 General information
The device described in the present document works as an electronic digital temperature controller for a
room or a zone (consisting e.g. in a group of rooms or a whole floor) of a building and is part of the
secundary regulation for heating and cooling. The room temperature controller has been developed
according to the KNX standard for use in systems of control of homes and buildings.
Through the integrated sensors, the device can measure directly in the room the temperature and relative
humidity values that can be used for control and regulation tasks of heating, cooling and ventilation. Via the
bus the device can furthermore receive temperature, relative humidity and CO2-concentration values from
other bus devices. The integrated display visualizes a series of information concerning the room controller
function. The device is provided with two rockers that can be used for controlling the thermostat function.
The two physical inputs may be configured independently as analogic or digital and allow to extend the basic
functions, optimizing comfort, safety and energy savings depending on the user or building needs. The
device can furthermore report whether the room or zone is in a thermal comfort field configurable according
to the building use, the activities done and other specific factors.
1.1 Function
The main function of the device is to control the temperature of the air mass of the room by means of the
actual temperature (Teff), measured by the device itself or received by the bus, and of the setpoint
temperature (Tset) set by the user; comparing the two values and a series of parameters set before the
commissioning, the regulation algorithm of the device calculates the control variable value that is converted
to a telegram and transmitted on the bus toward KNX actuators (such as binary outputs, fan-coli controllers,
valve drives, etc.) able to control the operation of heating and cooling terminal units.
1.2 Main funcional features
The main functions carried out by the device are:
•temperature and relative humidity measuring through the integrated sensors with possibility of
sending the values on the bus;
•2-points (on/off) or proportional (PWM or continuous) room temperature regulation;
•ventilation control with continuous or 3-speed regulation;
•relative humidity control both in humidification and dehumidification;
•seasonal modes: heating and cooling with local or via bus switch-over;
•operating modes: comfort, standby, economy and building protection with separate setpoint values
for heating and cooling;
•manual or automatic control of a fan-coil unit with 2-pipes or 4-pipes connection
•automatic switching of the operating mode when presence/absence of people or window opening is
detected;
•weighted average of two temperature values;

Application manual
KNX room temperature controller EK-EQ2-TP
Release 3.00 - Updating: 27/06/2017 Application Manual
© SBS S.p.A. - All rights reserved Page 7
•temperature displaying (measured, setpoint, perceived and outdoor values in °C or °F), relative
humidity (measured and setpoint values in %) and CO2-concentration (in ‰, received from bus),
alarms and errors (with alphanumeric codification);
•signaling opening windows;
•calculation of psychrometric values (dew-point temperature and perceived temperature) with
possibility of sending the values on the bus;
•limitation of the surface temperature for floor heating radiant panels;
•anticondensation protection for floor and ceiling cooling radiant panels;
•antistratification function;
•delayed fan start (“hot-start” function) time-scheduled or depending on the conveying fluid
temperature measured at the coil battery;
•sending on the bus of the condition internal or external from the area of comfort (configurable).
1.3 Technical data
Feature
Valore
Device
KNX S-mode bus device
Communication
according KNX TP1 standard
Use
dry internal rooms
Environmental conditions
• Operating temperature: - 5 ... + 45°C
• Storage temperature: - 25 ... + 55°C
• Transport temperature: - 25 ... + 70°C
• Relative hunidity: 95% not condensating
Power supply
SELV 30 Vdc from bus KNX (auxiliary power supply not necessary)
Current consumption from bus
< 13 mA
Elementi di comando
2-fold pushbutton for direct access to 4 funzioni indipendenti mediante pressione breve (< 5 s)
e indiretto ad altre funzioni mediante pressione prolungata (> 5 s)
Programming elements
1 pushbutton and 1 LED (red) on the front side
Display elements
1 backlighted LC-display, 8 LED (4 for each rocker)
Temperature sensor
1 integrated NTC-type
R.H. sensor
1 integrated
Accessories
2 square (40x40 mm) rockers and a square frame of the flank or form series (to be ordered
separately) - ‘NF (No Frame versions) do not require any frame
Installation
On round or square wall-mounting box with disatnce between fixing holes of 60 mm
Connection
• bus: black/red KNX terminal block
• inputs: screw terminal blocks
Protection degree
IP20
Dimensions (WxHxD)
82 x 75 x 35 mm
1.4 Design
The device is realised for wall-mounting on round or square wall box with distance between fixing holes of 60
mm. The programming pushbutton and the programming led are on the front side under the rockers. On the
rear side of the housing there is the 4-pole terminal block for the connection of the 2 inputs and the terminal
block for the connection of the bus.

Application manual
KNX room temperature controller EK-EQ2-TP
Release 3.00 - Updating: 27/06/2017 Application Manual
© SBS S.p.A. - All rights reserved Page 8
Device: front and side sights
1.5 Delivery
The delivery includes a device, the terminal block for the connection of the bus, the screws (2 pairs) and the
metallic support for mounting on the wall box. The packaging inlcludes also the device instructions.
1.6 Accessories
The device is completed with a set of two square 40x40 mm rockers and a square frame of the form (EK-
FOQ-...) or flank (EK-FLQ-...) series that have to be ordered separately. The ‘NF (No Frame) version does
not require any frame (see also the following table). Temperature sensors and other devices to be connected
to the inputs must be ordered separately.
Code
Version
LED colours
Device housing
Accessories
EK-EQ2-TP
with frame
blue / green
black plastic
set rockers EK-TSQ-G...-EP2 and square
frame of form (EK-FOQ-...)
or flank (EK-FLQ-...) series
EK-EQ2-TP-RW
white / red
EK-EQ2-TP-BG-NF
‘NF (without
frame)
blue / green
set rockers EK-TSQ-G...-EP2
EK-EQ2-TP-RW-NF
white / red
EK-EQ2-TP-BG-NFW
blue / green
white plastic
EK-EQ2-TP-RW-NFW
white / red
Accessories of the device: set of rockers and frames
1.7 Marks and certification
The KNX mark on the ekinex device ensures interoperability with the KNX devices of SBS and other
manufacturers installed on the same system bus system. The compliance with the applicable European
directives is indicated by the presence of the CE mark.

Application manual
KNX room temperature controller EK-EQ2-TP
Release 3.00 - Updating: 27/06/2017 Application Manual
© SBS S.p.A. - All rights reserved Page 9
2 Installation
The device has degree of protection IP20, and is therefore suitable for use in dry interior rooms. The
installation of the device requires the following steps:
a) fix the metallic support with the screws supplied on a wall box with distance between fixing holes of
60 mm. It is recommended to install the device at a height of 150 cm;
b) if required, snap a square frame of the form or flank series, inserting it from the rear of the device;
c) connect the sensors or the contacts required to the 4-poles screw terminal block on the rear of the
device;
d) insert the terminal for the bus (red/black), previously connected to the bus cable, in its slot on the
rear side. At this point it is recommended to carry out the commissioning of the device or at least the
download of the physical address;
e) install the device on the metallic support through the spring system, tightening then the two screws
f) requires also to tighten the screws included in the delivery. For mounting the device follow also the
indication TOP (arrow tip pointing up) on the rear side of the device;.
g) snap the two rockers onto the device for the operation of the room temperature controller.
The device can only be mounted on a round or square wall flush mounting box with 60 mm distance between
fixing holes. If necessary, the metallic support for mounting on the wall box can also be ordered separately.
2.1 Connection
For the operation the device has to be connected to the bus line and addressed, configured and
commissioned with ETS (Engineering Tool Software). The connection of one or two sensors to the inputs is
optional and must be defined by the planner of the bus system.
2.1.1 Connection of the bus line
The connection of the KNX bus line is made with the terminal block (red/black) included in delivery and
inserted into the slot of the housing.
Characteristics of the KNX terminal block
•spring clamping of conductors
•4 seats for conductors for each polarity
•terminal suitable for KNX bus cable with single-wire conductors and diameter between 0.6 and 0.8
mm
•recommended wire stripping approx. 5 mm
•color codification: red = + (positive) bus conductor, black = − (negative) bus conductor
2.1.2 Connection of the inputs
The connection of the inputs is made with the screw terminals located at the rear side of the device. The
maximum cable length is 10 m. For the connection use a cable of max section 1,5 mm². The connection
cable must have sufficient length to allow the extraction of the device from the wall-mounting box.
Characteristics of the terminal blocks for the inputs
•screw clamping of conductors
•maximum cross section of conductor 1 mm² (multiwire)
•recommended wire stripping approx. 5 mm

Application manual
KNX room temperature controller EK-EQ2-TP
Release 3.00 - Updating: 27/06/2017 Application Manual
© SBS S.p.A. - All rights reserved Page 10
•torque max 0.2 Nm
Connection of the device of the bus line
KNX
bus
+
–

Application manual
KNX room temperature controller EK-EQ2-TP
Release 3.00 - Updating: 27/06/2017 Application Manual
© SBS S.p.A. - All rights reserved Page 11
3 Configuration and commissioning
The configuration and commissioning are carried out with the ETS (Engineering Tool Software) tool and the
ekinex® application program provided free of charge by SBS; you do not need any additional software neither
plug-in tool. For further information on ETS see also www.knx.org.
3.1 Configuration
The device functionality is defined by the settings done via software. The configuration requires necessarily
ETS4 (or later releases) and the ekinex® APEKEQ2TP##.knxprod (## = release) application program that
can be downloaded from the website www.ekinex.com. The application program allows the configuration of
all working parameters for the device. The device-specific application program has to be loaded into ETS or,
as alternative, the whole ekinex® product database can be loaded; at this point, all the instances of the
selected device type can be added to the project.
Application program for ETS APEKEQ2TP##.knxprod (## = version)
3.1.1 Tree structure of the application program
At its opening, the tree structure of the program includes the following main items:

Application manual
KNX room temperature controller EK-EQ2-TP
Release 3.00 - Updating: 27/06/2017 Application Manual
© SBS S.p.A. - All rights reserved Page 12
About EK-EQ2-TP
General
Internal sensors
Inputs
External sensors (from bus)
LCD display
Led
Temperature control
Relative humidity control
Comfort
Energy saving
Other items may appear depending on the choices done for the parameters in the several folders.
3.1.2 Languages of the application program
The application program is available in four languages: English, Italian, German and French. The language
displayed can be changed in ETS choosing "Settings / Presentation language".

Application manual
KNX room temperature controller EK-EQ2-TP
Release 3.00 - Updating: 27/06/2017 Application Manual
© SBS S.p.A. - All rights reserved Page 13
3.2 Commissioning
For the commissioning the device is provided on the front side (in the area usually occupied by the rockers)
with:
•a red LED (1) for indication of the active operating mode (LED on = programming, LED off = normal
operation);
•a pushbutton (2) for switching between the normal and programming operating mode.
Device programming: led (1) and pushbutton (2)
For commissioning the device the following activities are required:
•make the electrical connections;
•turn on the bus power supply;
•switch the device operation to the programming mode by pressing the
programming pushbutton located on the front side of the housing. In this
mode of operation, the programming LED is turned on;
•download into the device the physical address and the configuration with the
ETS® program.
When downloading the application program the display shows "PrOg" and the
flashing symbol of the clock. At the end of the download the operation of the device
automatically returns to normal mode; in this mode the programming LED is turned
off. Now the bus device is programmed and ready for use.
3.2.1 Displaying physical address and firmware release
Once the first addressing is done, you can check anytime the physical address and the firmware release
directly on the device display. In order to display it, press for more than 3 seconds the – (minus) symbol on
the lower rocker and the symbol on the upper rocker. All segments of the display are turned off;
displaying a physical address only the 3 large digits and the small one are active. The information displayed
in sequence are: the area number (A), the line number (L), the device number (d) and the firmware release
(F). To scroll through the three elements of the physical address press + or –.
1
2

Application manual
KNX room temperature controller EK-EQ2-TP
Release 3.00 - Updating: 27/06/2017 Application Manual
© SBS S.p.A. - All rights reserved Page 14
Example of displaying the physical address 10.5.43 (device nr. 43, installed on the line 5 of the area 10) and the firmware release 001
To exit from the physical address displaying press shortly (< 3 seconds) the symbol on the lower
rocker. If you elapse of time interval set in parameter “Time to exit change without saving” without pressing
any rocker, the device returns automatically to the previously displayed information.

Application manual
KNX room temperature controller EK-EQ2-TP
Release 3.00 - Updating: 27/06/2017 Application Manual
© SBS S.p.A. - All rights reserved Page 15
4 User interface
The user interface of the room temperature controller includes a LC-display, a pushbutton with two rockers
and a series of freely programmable LEDs (4 for each rocker). The colour of the LEDs depend on the device
version.
User interface: LC-display (1), rockers (2), LEDs (3) with lightguide
The symbols on the rockers recall the function carried out:
+temperature (or other parameters) increase;
‒temperature (or other parameters) decrease;
information sequence, operating mode change, ventilation control, seasonal change-over.
Through a combined pressure of various symbols other functions can be carried out.
4.1 LCD-display
The device is provided with a LC-display (1) with adjustable backlight that occupies a vertical area of approx.
40 x80 mm (WxH) in the left half of the device.
4.1.1 Information displaying
Depending on the configuration done with ETS, the connections and the availability of information (local or
received from the bus), the series of symbols allow to display:
room actual temperature (it may be the temperature calculated using a weighted average of two
values);
outdoor temperature, preceded by a ‒ (minus) sign in case of outdoor temperature below 0°C;
relative humidity (in %, without decimals);
perceived temperature (estimated with the measured values of temperature and relative humidity);
temperature setpoint (for the actual operating mode);
concentration of CO2 (in ‰);
alarm and error condition (A01, A02… E01, E02…);
window opening;
2
1
3

Application manual
KNX room temperature controller EK-EQ2-TP
Release 3.00 - Updating: 27/06/2017 Application Manual
© SBS S.p.A. - All rights reserved Page 16
operating mode (comfort / standby / economy / building protection);
seasonal mode (heating / cooling);
device status calling / not calling (or setpoint reached / not reached);
operation in manual mode (M);
operation as slave device (clock);
fan status (1-2-3-automatic-off), when present;
device physical address assigned by ETS.
Display symbols
Digits (for numeric values display)
Economy operating mode (night)
Celsius degrees
Standby operating mode
Fahrenheit degrees
Comfort operating mode
Percentage (relative humidity)
Heating mode active (device not calling
or setpoint reached)
Per mille (only for CO2
concentration)
Heating mode active (device calling or
setpoint not reached)
Alarm
Manual operation (M)
Window opening
Slave (operation subordinated to a
supervising KNX device)
Carbon-dioxide (CO2)
Cooling mode active (device not calling
or setpoint reached)
Indoor temperature
Cooling mode active (device calling or
setpoint not reached)
Outdoor temperature
OFF (fan-coil switched off)
Relative humidity
Automatic fan-coil operation (example:
speed 3)
SET
Manual fan-coil operation (example:
speed 2)
Building protection operating mode
(off)
Symbols that can be activated on the LC-display
4.1.2 Segment test
The segment test allows you to check at any time the proper functionality of the display. In order to do the
test, press simultaneously + (plus) on the upper rocker and the symbol on the lower rocker for more

Application manual
KNX room temperature controller EK-EQ2-TP
Release 3.00 - Updating: 27/06/2017 Application Manual
© SBS S.p.A. - All rights reserved Page 17
than 3 seconds. All symbols are activated simultaneously; then all the symbols are turned off. In the test
phase keep available the instructions or the user guide.
If you elapse the time set in the parameter "Time to exit change without saving" (General folder) without
pressing a button, the device will return to the previous situation.
4.1.3 Backlight
The backlight intensity of the LC-display is adjustable. The first setting is done when configuring the device
using ETS, but the intensity can be changed later at any time.
To access the change press simultaneously + (plus) and (bothon the upper rocker) for more than 3
seconds. All symbols are turned off except the digits and the percentage symbol. The actual value (as a
percentage) of backlight intensity is displayed. At each pressing of + or – the intensity is increased or
decreased by 5%. To confirm the selected intensity press shortly (< 3 seconds) the symbol either on
the upper rocker. Three rapid flashes of the digits indicate that the new value was saved. If you elapse of
time interval set in the "Time to exit change without saving " (General folder) without pressing any rocker, the
device returns to the previous situation.
4.2 Rockers
The pushbutton with two rockers integrated in the device controls the functions of the thermostat. The set of
two rockers has to be ordered separately; the symbols on the rockers of the set are pre-defined and cannot
be changed. The areas marked by the symbols + (plus) and – (minus) allow you to change a setting (e.g. the
temperature setpoint), while those marked by the symbol ●●●● allow you to display a sequence of
information, to change the operating mode, to control the ventilation, to do the seasonal change-over
(heating to cooling and vice versa) or to confirm a setting change.
The part number of the set EK-TSQ-Gxx-EP2 must be completed with the part (xx) that identifies the
material, color and finishing; for the exact code please refer also to the latest edition of the ekinex product
catalog or the website www.ekinex.com.
Rockers use
Upper rocker
Lower rocker
Functions for room temperature
controlling
+ and
and ‒

Application manual
KNX room temperature controller EK-EQ2-TP
Release 3.00 - Updating: 27/06/2017 Application Manual
© SBS S.p.A. - All rights reserved Page 18
5 Sensors
The room temperature controller is equipped with three sensors:
•temperature (1);
•relative humidity (2).
Position of the sensors: temperature (1), relative humidity (2).
The temperature sensor (not to be seen in the drawing) is located under the plastic half-shell for the rockers’ mounting.
5.1 Temperature sensor
The integrated temperature sensor allows the measureming of the room temperature in the range from 0 °C
to +40 °C with a resolution of 0.1 °C. To keep into account significant environmental interferences such as
the proximity to heatsources, the installation on an outer wall, the chimney effect due to rising warm air
through the corrugated tube connected to the wall-mounting box, the measured value can be corrected by
means of a offset of ± 5 °C or, preferably, can be used a weighted average between two values of
temperature chosen from the following ones: value measured by the integrated sensor, value measured by a
temperature sensor connected to one of the inputs of the device, value received via bus from another KNX
device (such as ekinex pushbuttons).
5.2 Relative humidity sensor
The integrated relative humidity sensor allows the measuring of the relative humidity value in the room. The
measured value allows you to make an advanced room thermoregulation and enlarge the opportunities for a
safe operation of certain types of terminal equipments used for cooling. The measured value can also be
sent on the bus via the 114 (1 byte) and the 115 (2 bytes) Communication Objects.By means of a calculation
performed by the thermostat, on the bus can also be sent psychrometric values obtained from the combined
measurement of temperature and humidity, such as the dew-point temperature, as well as the index of
perceived temperature (only in summer mode).
2
1

Application manual
KNX room temperature controller EK-EQ2-TP
Release 3.00 - Updating: 27/06/2017 Application Manual
© SBS S.p.A. - All rights reserved Page 19
6 Input variables
The data that the device usesin its control algorithms and /or to be displayed may come from:
•the internal sensors;
•sensors or digital signals connected to the two physical inputs of the device;
•the KNX bus through standard Communication Objects.
The processed data can also be transmitted on the KNX bus as Communication Objects.The classification of
the input variables is shown in the following table.
Data
Coming from
Description
Room temperature
Internal sensor
Analogic value for thermoregulation functions
Room relative humidity
Analogic value for thermoregulation functions
Window state (open/close)
Input 1 or 2 (device
terminals)
configurated
[DI] window contact sensor
Card holder state (badge in/out)
[DI] card holder contact sensor
Presence of condensation
[DI] anticondensation sensor
Conveying fluid temperature at the exchange coil
[AI] coil battery temperaure sensor
Room temperature (for weighted average value)
[AI] room temperature sensor
Room temperature (other measurement height)
[AI] antistratification temperature sensor
Floor surface temperature
[AI] floor surface temperature sensor
Outdoor temperature
[AI] outdoor temperature sensor
Further temperature value
[AI] generic (NTC) temperature sensor
Room temperature
KNX bus (through
communication
objects)
Object 34 (2 bytes)
Room relative humidity
Objects 35 (2 bytes) and 36 (1 byte)
Antistratification temperature
Object 37 (2 bytes)
Outdoor temperature
Object 38 (2 bytes)
CO2 concentration (air quality)
Object 39 (2 bytes)
Conveying fluid temperature at the exchange coil
Object 40 (2 bytes)
Floor surface temperature
Object 41 (2 bytes)
Conveying fluid flow temperature
Object 42 (2 bytes)
Presence of condensation
Object 46 (1 bit)
Window state (open/close)
Objects 43 and 44 (1 bit)
Presence of people in the room
Objects 32 and 33 (1 bit)
Card holder state (badge in/out)
Object 45 (1 bit)
Input variables from internal sensors, physical inputs and standard communication objects.
The device does not have outputs for direct switching or control of heating/cooling terminals or for status or
values signalling. The output variables include exclusively communication objects that are sent on the bus,
received and processed by KNX actuators (general-purpose or dedicated to HVAC applications).

Application manual
KNX room temperature controller EK-EQ2-TP
Release 3.00 - Updating: 27/06/2017 Application Manual
© SBS S.p.A. - All rights reserved Page 20
7 Application program for ETS
In the following chapters there is the list of folder, parameters and communication objects of the application
program. Some specific functions of the thermostat are described in more detail in the dedicated paragraphs.
The tree structure of the application program as imported into ETS (or by pressing the "Default Parameters"
button of ETS) is the following:
About EK-EQ2-TP
General
Temperature sensor
Internal sensors
Inputs
External sensors ( from bus)
LCD display
Led
Settings
Heating
Temperature control
Relative humidity control
Comfort
Windows contacts
Presence sensors
Card holder
Energy saving
Other folders may appear depending on the choices done for the parameters of the folders represented in
the main tree structure.
7.1 About EK-EQ2-TP
The folder About EK-EQ2-TP is for information purposes only and does not contain parameters to be set.
The information given is:
© Copyright SBS S.p.A. 2016
Application software for ETS4
Version 2.00 (or later)
KNX room temperature controller with LC-display and humidity sensor
SBS S.p.A.
Via Circonvallazione s/n
I-28010 Miasino (NO) Italy
Other manuals for EK-EQ2-TP- Series
1
Table of contents
Other Ekinex Temperature Controllers manuals
Popular Temperature Controllers manuals by other brands

Aprilaire
Aprilaire 8051 installation instructions

Galvin Engineering
Galvin Engineering CliniMix 100.91.10.20 Installation guidelines

M&C
M&C TRN operating manual

Rio Grande
Rio Grande Sentry Express manual

Sterling
Sterling Sterltronic S-Series Service and instruction manual

Auber Instruments
Auber Instruments SYL-1512A instruction manual