WRC W5-JEM1 User manual

For all manuals and other product data visit www.WRCakron.com/resources
© Western Reserve Controls, Inc. | 1485 Exeter Dr. Akron, Ohio 44306 | 330-733-6662 | sales@wrcakron.com
PUB005-20190314-A01
Wiring & Installation Instructions
W5-JEM1
EtherNet/IP to RS-232/485
Serial Device Gateway
Cost-optimized, multi-protocol, ASCII gateway
perfect for RS-232/485 Serial Device Integration
Document PUB005-20190314-A01
Rev 1.00
March 2019
Copyright © 2019 WRC
Western Reserve Controls, Inc.
1485 Exeter Road
Akron, OH 44306
330-733-6662 (Phone)
www.wrcakron.com/w5-jem1 (W5-JEM1 Specs)
www.wrcakron.com (Web)

Western Reserve Controls
W5-JEM1 Wiring & Installation
Revision 1.0
2
PUB005-20190314-A01
1 General Specifications
1.1 Table of Specifications
EtherNet/IP Device Profile:
Generic Device Type 0x2B (2B hex)
EtherNet/IP:Conformance:
Conforms to the ODVA EtherNet/IP Specification Version 1.23
Ethernet Link Speed:
10/100 MBits
IP Address selection:
Static IP configured via web browser (Factory Default: 192.168.1.10)
Power Supply:
5.0 –28.0 Vdc
1A user replaceable fuse (spare fuse included)
Maximum Power:
2.4W, 100mA @ 24Vdc supply, 480mA @ 5Vdc supply
Minimum RPI:
4ms*
Serial Port Isolation
1000V DC Isolation
Size:
W5-JEM1-DH2: 2.000”x2.575”x 4.950” without connectors attached
Operating Temp:
-40 to +70 C
Humidity:
0-95% RH, non-condensing
RoHS:
Yes (RoHS 2)
CE Mark:
No
* Faster RPI values may be supported by certain PLC controllers.

Western Reserve Controls
W5-JEM1 Wiring & Installation
Revision 1.0
3
PUB005-20190314-A01
Hardware Installation and Set-Up
1.2 Installation
Follow the steps below:
1. In most cases it is recommended to set the device’s IP address prior to installation. See W5-JEM1
User Manual for complete instructions.
a. Note: factory default IP address is 192.168.1.10 for all units
2. Mount unit onto DIN rail
3. Wire up power (24VDC typical), common, and chassis ground to the power connector. See
“Connector Pinouts” for a diagram.
a. If there is no chassis ground connection, or the power supply is connected to chassis
ground, jumper the chassis ground connection to the common connection
4. Connect the device to the controlling PLC with an Ethernet cable
a. The device may be connected directly or through an ethernet switch
5. Connect the W5-JEM1 to the serial device using a compatible serial cable
a. This device requires serial cables with a special pinout. See section 1.8 “Serial Wiring
Diagrams” and section 1.7 “Connector Pinouts” for further information.
6. Apply power, device is ready for use with PLC.
7. Also see W5-JEM1 User Manual for an explanation of how to use the W5-JEM1 with a PLC
1.3 Power Supply
The device is intended to be used with standard 24V DC industrial power supplies. However, any voltage
between 5V and 28V may be supplied to the device assuming sufficient current is provided.
1.4 Network Connection
The device must be connected to the controlling PLC either directly with a cable or through your local
network Ethernet switch.
Figure 1. Several possible ethernet network configurations

Western Reserve Controls
W5-JEM1 Wiring & Installation
Revision 1.0
4
PUB005-20190314-A01
1.5 LED Indicators
Table 1. Overview of LED Indicators
LED Name
Description
RX
Indicates when data is being received
on the serial line
TX
Indicates when data us being transmitted
by the W5-JEM1 onto the serial line
MS
Indicates if the module is okay or if there
is an error. See Table 2 below.
NS
Indicates the network status.
See Table 3 below.
Table 2. Module Status LED (labeled MS)
LED State
Module Status
Meaning
Off
No Power
Device is not powered.
Green
Device Operational
W5-JEM1 is operating normally.
Flashing Red
Minor Fault
Recoverable fault.
Solid Red
Critical Fault
Device will automatically reboot to clear a
critical fault after 30 seconds.
Table 3. EtherNet/IP Network Status LED (labeled NS)
LED State
Network Status
Meaning
OFF
No Power
W5-JEM1 has no power
Flashing Green
Online, not connected
W5-JEM1 is online but is not connected to a
PLC.
Green
Online, connected
W5-JEM1 is operating normally and is
connected to a PLC
Flashing Red
Connection time-out
One or more connections are timed out.

Western Reserve Controls
W5-JEM1 Wiring & Installation
Revision 1.0
5
PUB005-20190314-A01
1.6 Product Drawing and Dimensions
Shown below are the overall dimensions of the product when installed on a piece of standard DIN rail. This
drawing does not include the overall height or length added by the Power, Serial, or Ethernet cables or their
respective connectors.
Side View Top View
1.7 Connector Pinouts
Figure 2. Power Connector Pinout
Table 4. Power Connector Pinout
Pin
Name
Description
1
GND
Chassis Ground
2
V- (COM)
Power Common
3
V+
Power In, 5V-28V
Figure 3. Male DE-9 Serial Connector Pinout

Western Reserve Controls
W5-JEM1 Wiring & Installation
Revision 1.0
6
PUB005-20190314-A01
1.8 Serial Wiring Diagrams
The serial port can be operated as RS-232, RS-422, or RS-485 connection. Selection between RS-232,
422 or 485 is made by using the correct cable for the desired RS specification.
ATTENTION: You must use a cable that matches the specifications shown in the table below.
Table 5. D-sub Connector Pins
DE-9 Pin #
RS-232
RS-422
RS-485
1
Do Not Connect
Transmit Data –
Transmit/Receive Data –
2
Receive Data
Do Not Connect
Do Not Connect
3
Transmit Data
Do Not Connect
Do Not Connect
4
Do Not Connect
Receive Data –
Do Not Connect
5
Common
Common
Common
6
Do Not Connect
Receive Data +
Do Not Connect
7
Request To Send
Request to Send*
Request to Send*
8
Clear To Send
Clear to Send*
Clear to Send*
9
Do Not Connect
Transmit Data +
Transmit/Receive Data +
*RTS and CTS are not supported in RS-422 and RS-485. These connections must be connected together at the JEM1 Device
Note: Pay attention to distance limitations based upon RS standards and baud rate.
Figure 4. RS-232 Wiring Diagram –Module to
DTE Device (Hardware Handshaking Disabled).
Figure 5. RS-232 Wiring Diagram –Module to
Printer (Hardware Handshaking Enabled,
Standard Printer Adapter Cable.).

Western Reserve Controls
W5-JEM1 Wiring & Installation
Revision 1.0
7
PUB005-20190314-A01
Figure 6. RS-422 Wiring Diagram
Figure 7. RS-485 Wiring Diagram
1.9 Models and Part Numbers
WRC Order Number
Description
W5-JEM1-DH2
DIN Mount Serial to EtherNet/IP Gateway
END OF DOCUMENT