WTI MPC Series User manual

WTI Part No. 13762
Rev. B
MPC Series
Managed Power Controllers
Models Covered:
MPC-8H-1
MPC-8H-2
MPC-16H-1
MPC-16H-2
MPC-20V-1
MPC-20V-2
MPC-REMOTE
User's Guide

i
Warnings and Cautions:
Installation Instructions
Secure Racking
If Secure Racked units are installed in a closed or multi-unit rack assembly, they may
require further evaluation by Certification Agencies. The following items must be
considered.
1. The ambient within the rack may be greater than room ambient. Installation
should be such that the amount of air flow required for safe operation is not
compromised. The maximum temperature for the equipment in this environment is
45°C. Consideration should be given to the maximum rated ambient.
2. Installation should be such that a hazardous stability condition is not achieved due
to uneven loading.
Input Supply
Check nameplate ratings to assure there is no overloading of supply circuits that could
have an effect on overcurrent protection and supply wiring.
Grounding
Reliable earthing of this equipment must be maintained. Particular attention should
be given to supply connections when connecting to power strips, rather than direct
connections to the branch circuit.
No Serviceable Parts Inside; Authorized Service Personnel Only
Do not attempt to repair or service this device yourself. Internal components must be
serviced by authorized personnel only.
• Shock Hazard - Do Not Enter
• Lithium Battery
CAUTION: Danger of explosion if battery is incorrectly replaced. Replace
only with same or equivalent type recommended by the manufacturer.
Discard used batteries according to the manufacturer's instructions.

ii
Warnings and Cautions
Disconnect Power
If any of the following events are noted, immediately disconnect the unit from the outlet
and contact qualified service personnel:
1. If the power cord becomes frayed or damaged.
2. If liquid has been spilled into the device or if the device has been exposed to rain
or water.
Two Power Supply Cables
Note that this unit features two separate power circuits, and that a power supply cable is
required for each power circuit. Before attempting to service or remove this unit, please
make certain that both power supply cables are disconnected from the power source.
15-Amp “Starter” Cables
MPC-8H-1 units, MPC-16H-1 units and MPC-20V-1 units are shipped with two 125 VAC,
15 Amp “Starter” Cables. These Starter Cables will allow you to connect the MPC to
power for bench testing and initial start up and are adequate for applications that only
require 15 Amps. For 20-Amp power switching applications, please refer to the WTI
Power Cable guide supplied with the unit, or use appropriate 20-Amp cables.

iii
Agency Approvals
FCC Part 15 Regulation
This equipment has been tested and found to comply with the limits for a Class A digital
device, pursuant to part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference when the equipment is operated
in a commercial environment. This equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in accordance with the instruction
manual, may cause harmful interference to radio communications. Operation of this
equipment in a residential area is likely to cause harmful interference in which case the
user will be required to correct the interference at his own expense.
This device complies with part 15 of the FCC Rules. Operation is subject to the following
two conditions: (1) This device may not cause harmful interference, and (2) this device
must accept any interference received, including interference that may cause undesired
operation
WARNING: Changes or modifications to this unit not expressly approved by
the party responsible for compliance could void the user’s authority to operate
the equipment
EMC, Safety, and R&TTE Directive Compliance
The CE mark is affixed to this product to confirm compliance with the following
European Community Directives:
• Council Directive 89/336/EEC of 3 May 1989 on the approximation of the laws
of Member States relating to electromagnetic compatibility;
and
• Council Directive 73/23/EEC of 19 February 1973 on the harmonization of
the laws of Member States relating to electrical equipment designed for use
within certain voltage limits;
and
• Council Directive 1999/5/EC of 9 March on radio equipment and
telecommunications terminal equipment and the mutual recognition of their
conformity.
Industry Canada
This Class A digital apparatus complies with Canadian ICES-003.
Cet appareil numérique de la classe A est conforme à la norme NMB-003 du Canada.
This product meets the applicable Industry Canada technical specifications
The Ringer Equivalence Number is an indication of the maximum number of devices
allowed to be connected to a telephone interface. The termination on an interface may
consist of any combination of devices subject only to the requirement that the sum of
the RENs of all the devices does not exceed five.

iv
Table of Contents
1. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
2. Unit Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
2.1. MPC-H Series - Front Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
2.2. MPC-H Series - Back Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
2.3. MPC-V Series - Hardware Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
2.4. Button Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
3. Getting Started . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
3.1. Installing the MPC Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
3.1.1. Apply Power to the MPC-20V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
3.1.2. Connect your PC to the MPC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
3.2. Communicating with the MPC-20V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
3.3. Installing and Operating the Optional MPC-REMOTE Hardware . . . . . . . . . . . . . . . . . 3-4
4. Hardware Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
4.1. Connecting the Power Supply Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
4.1.1. Installing the Cable Keepers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
4.1.2. Connect the MPC to Your Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
4.2. Connection to Switched Outlets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
4.3. Serial Console Port Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
4.3.1. Connecting a Local PC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
4.3.2. Connecting an External Modem . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
4.4. Connecting the Network Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
4.5. Connecting the Optional MPC-REMOTE Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
5. Basic Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
5.1. Communicating with the MPC Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
5.1.1. The Text Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
5.1.2. The Web Browser Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
5.1.3. Access Via PDA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
5.2. Configuration Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
5.3. Defining System Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
5.3.1. The Real Time Clock and Calendar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-8
5.3.2. The Invalid Access Lockout Feature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-10
5.3.3. Automated Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-11
5.3.4. Log Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-12
5.3.4.1. The Audit Log and Alarm Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-12
5.3.4.2. The Current Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-13
5.3.4.3. Reading and Erasing Logs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-13
5.3.5. Callback Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-14
5.4. User Accounts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-16
5.4.1. Command Access Levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-16
5.4.2. Plug Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-17
5.5. Managing User Accounts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-18
5.5.1. Viewing User Accounts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-18
5.5.2. Adding User Accounts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-20
5.5.3. Modifying User Accounts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-22
5.5.4. Deleting User Accounts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-22

Table of Contents
v
5. Basic Configuration (continued)
5.6. The Plug Group Directory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-23
5.6.1. Viewing Plug Groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-24
5.6.2. Adding Plug Groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-24
5.6.3. Modifying Plug Groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-26
5.6.4. Deleting Plug Groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-26
5.7. Defining Plug Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-27
5.7.1. The Boot / Sequence Delay Period. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-29
5.8. Serial Port Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-30
5.8.1. Serial Port Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-30
5.8.2. Serial Port Configuration Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-30
5.9. Network Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-35
5.9.1. Network Port Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-36
5.9.2. Network Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-38
5.9.3. IP Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-40
5.9.3.1. Adding IP Addresses to the Allow and Deny Lists . . . . . . . . . . . . . 5-41
5.9.3.2. Linux Operators and Wild Cards . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-41
5.9.3.3. IP Security Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-42
5.9.4. Static Route . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-43
5.9.5. Domain Name Server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-43
5.9.6. SNMP Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-45
5.9.7. LDAP Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-47
5.9.7.1. Adding LDAP Groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-50
5.9.7.2 Viewing LDAP Groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-51
5.9.7.3. Modifying LDAP Groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-51
5.9.7.4. Deleting LDAP Groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-52
5.9.7.5. LDAP Kerberos Set Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-54
5.9.8. TACACS Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-56
5.9.9. RADIUS Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-58
5.9.10. Email Message Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-60
5.10. Save User Selected Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-61
6. Reboot Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
6.1. Ping-No-Answer Reboot . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
6.1.1. Adding Ping-No-Answer Reboots . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3
6.1.2. Viewing Ping-No-Answer Reboot Profiles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
6.1.3. Modifying Ping-No-Answer Reboot Profiles . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5
6.1.4. Deleting Ping-No-Answer Reboot Profiles . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5
6.2. Scheduled Reboot . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-6
6.2.1. Adding Scheduled Reboots . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-6
6.2.2. Viewing Scheduled Reboot Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-9
6.2.3. Modifying Scheduled Reboots . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-9
6.2.4. Deleting Scheduled Reboots . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-10
7. Alarm Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
7.1. The Over Current Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-3
7.2. The Over Temperature Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-6
7.3. The Circuit Breaker Open Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-9
7.4. The Lost Communication with AUX Units Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-12
7.5. The Lost Voltage (Line In) Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-15
7.6. The Ping-No-Answer Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-18
7.7. The Invalid Access Lockout Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-21

Table of Contents
vi
8. The Status Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
8.1. The Network Status Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
8.2. The Plug Status Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-3
8.3. The Plug Group Status Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-5
8.4. The Current Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-7
8.5. The Current History Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-9
9. Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-1
9.1. Operation via the Web Browser Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-1
9.1.1. The Plug Control Screen - Web Browser Interface . . . . . . . . . . . . . . . . . . . . . . 9-1
9.1.2. The Plug Group Control Screen - Web Browser Interface . . . . . . . . . . . . . . . . 9-2
9.2. Operation via the Text Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-5
9.2.1. The Plug Status Screen - Text Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-5
9.2.2. Switching and Reboot Commands - Text Interface . . . . . . . . . . . . . . . . . . . . . 9-6
9.2.3. Applying Commands to Several Plugs - Text Interface . . . . . . . . . . . . . . . . . . 9-8
9.3. The Automated Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-9
9.4. Manual Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-10
9.5. Logging Out of Command Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-10
10. SSH Encryption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-1
11. Syslog Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-1
11.1. Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-1
11.2. Testing Syslog Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-2
12. SNMP Traps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-1
12.1. Configuration: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-1
12.2. Testing the SNMP Trap Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-2
13. Saving and Restoring Configuration Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-1
13.1. Sending Parameters to a File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-1
13.2. Restoring Saved Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-2
14. Upgrading MPC Firmware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-1
15. Command Reference Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-1
15.1. Command Conventions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-1
15.2. Command Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-2
15.3. Command Set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-3
15.3.1. Display Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-3
15.3.2. Control Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-5
15.3.3. Configuration Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-8
Appendices:
A. RS232 Port Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Apx-1
B. Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Apx-2
C. Customer Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Apx-3
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Index-1

Table of Contents
vii
List of Figures
2.1. MPC-8H - Front Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
2.2. MPC-16H - Front Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
2.3. MPC-8H-1 - Back Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
2.4. MPC-8H-2 - Back Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
2.5. MPC-16H-1 - Back Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
2.6. MPC-16H-2 - Back Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
2.7. MPC-20V Series - Hardware Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
5.1. The Plug Status Screen (Text Interface; MPC-20V Shown) . . . . . . . . . . . . . . . . . . . . . . . . 5-2
5.2. The Home Screen (Web Browser Interface) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
5.3. The System Parameters Menu (Text Interface) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6
5.4. The System Parameters Menu (Web Browser Interface) . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6
5.5. The Add User Menu (Text Interface) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-19
5.6. The Add User Menu (Web Browser Interface) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-19
5.7. The Add Plug to Group Menu (Text Interface) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-25
5.8. The Add Plug to Group Menu (Web Browser Interface) . . . . . . . . . . . . . . . . . . . . . . . . . . 5-25
5.9. The Plug Parameters Menu (Text Interface) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-28
5.10. The Plug Parameters Menu (Web Browser Interface) . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-28
5.11. Serial Port Configuration Menu (Text Interface) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-31
5.12. Port Configuration Menu (Web Browser Interface) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-31
5.13. Network Parameters Menu (Text Interface) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-34
5.14. Network Configuration Menu (Web Browser Interface) . . . . . . . . . . . . . . . . . . . . . . . . . . 5-34
5.15. Network Port Parameters Menu (Web Browser Interface) . . . . . . . . . . . . . . . . . . . . . . . . 5-36
5.16. Network Parameters Menu (Web Browser Interface) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-38
5.17. SNMP Access Menu (Text Interface) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-44
5.18. SNMP Trap Menu (Text Interface) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-44
5.19. SNMP Parameters Menu (Web Browser Interface) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-44
5.20. LDAP Parameters Menu (Text Interface) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-46
5.21. LDAP Parameters Menu (Web Browser Interface) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-46
5.22. Add LDAP Group Menu (Text Interface) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-49
5.23. Add LDAP Group Menu (Web Browser Interface) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-49
5.24. LDAP Kerberos Set Up Menu (Text Interface) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-53
5.25. LDAP Kerberos Set Up Menu (Web Browser Interface) . . . . . . . . . . . . . . . . . . . . . . . . . . 5-53
5.26. The TACACS Parameters Menu (Text Interface) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-55
5.27. The TACACS Parameters Menu (Web Browser Interface) . . . . . . . . . . . . . . . . . . . . . . . . 5-55
5.28. The RADIUS Parameters Menu (Text Interface) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-57
5.29. The RADIUS Parameters Menu (Web Browser Interface) . . . . . . . . . . . . . . . . . . . . . . . . 5-57
5.30. The Email Messaging Parameters Menu (Text Interface) . . . . . . . . . . . . . . . . . . . . . . . . . 5-59
5.31. The Email Messaging Parameters Menu (Web Browser Interface) . . . . . . . . . . . . . . . . . 5-59
6.1. The Add Ping-No-Answer Menu (Text Interface) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
6.2. The Add Ping-No-Answer Menu (Web Browser Interface) . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
6.3. The Add Scheduled Reboot Menu (Text Interface) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-7
6.4. The Add Scheduled Reboot Menu (Web Browser Interface) . . . . . . . . . . . . . . . . . . . . . . . 6-7
7.1. The Alarm Configuration Menu (Text Interface) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2
7.2. The Alarm Configuration Menu (Web Browser Interface) . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2
7.3. The Over Current Alarm Menu (Initial Threshold, Text Interface Shown) . . . . . . . . . . . . . . 7-4
7.4. The Over Current Alarm Menu (Initial Threshold, Web Browser Interface Shown) . . . . . . 7-4
7.5. The Over Temperature Alarm Menu (Initial Threshold, Text Interface Shown) . . . . . . . . . . 7-7
7.6. The Over Temperature Alarm Menu (Initial Threshold, Web Browser Interface Shown) . . 7-7
7.7. The Circuit Breaker Open Alarm Menu (Text Interface) . . . . . . . . . . . . . . . . . . . . . . . . . . 7-10
7.8. The Circuit Breaker Open Alarm Menu (Web Browser Interface) . . . . . . . . . . . . . . . . . . 7-10
7.9. The Lost Communication with AUX Units Alarm Menu (Text Interface) . . . . . . . . . . . . . . 7-13
7.10. The Lost Communication with AUX Units Alarm Menu (Web Browser Interface) . . . . . . 7-13

Table of Contents
viii
7.11. The Lost Voltage (Line In) Alarm Menu (Text Interface) . . . . . . . . . . . . . . . . . . . . . . . . . . 7-16
7.12. The Lost Voltage (Line In) Alarm Menu (Web Browser Interface) . . . . . . . . . . . . . . . . . . 7-16
7.13. The Ping-No-Answer Alarm Menu (Text Interface) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-19
7.14. The Ping-No-Answer Alarm Menu (Web Browser Interface) . . . . . . . . . . . . . . . . . . . . . . 7-19
7.15. The Invalid Access Lockout Alarm Menu (Text Interface) . . . . . . . . . . . . . . . . . . . . . . . . . 7-22
7.16. The Invalid Access Lockout Alarm Menu (Web Browser Interface) . . . . . . . . . . . . . . . . . 7-22
8.1. The Network Status Screen (Text Interface) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-2
8.2. The Network Status Screen (Web Browser Interface) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-2
8.3. The Plug Status Screen (Administrator Mode; Text Interface) . . . . . . . . . . . . . . . . . . . . . . 8-4
8.4. The Plug Status Screen (Administrator Mode; Web Browser Interface) . . . . . . . . . . . . . . 8-4
8.5. The Plug Group Status Screen (Administrator Mode; Text Interface) . . . . . . . . . . . . . . . . 8-6
8.6. The Plug Group Status Screen (Administrator Mode; Web Browser Interface) . . . . . . . . . 8-6
8.7. The Current Monitor Screen (Text Interface) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-8
8.8. The Current Monitor Screen (Web Browser Interface) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-8
8.9. The Current History Screen (Text Interface) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-9
8.10. The Current History Screen (Web Browser Interface) . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-10
9.1. The Plug Control Screen (Administrator Mode; Web Browser Interface) . . . . . . . . . . . . . 9-2
9.2. The Plug Group Control Screen (Administrator Mode; Web Browser Interface) . . . . . . . . 9-3
9.3. The Help Menu (Administrator Mode; Text Interface) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-5
9.4. The Plug Status Screen (Administrator Mode; Text Interface) . . . . . . . . . . . . . . . . . . . . . . 9-6
11.1. The Test Menu (Text Interface, Administrator Mode Only) . . . . . . . . . . . . . . . . . . . . . . . . 11-2
A.1. RS232 Console Port Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Apx-1

1-1
1. Introduction
WTI’s MPC series Managed Power Controllers allow secure, remote monitoring and
management of AC powered rack mount equipment via SSL, SSH, web browser, telnet,
external modem or local terminal. The MPC can monitor power to your equipment, and
automatically notify you when changes in current levels, temperature, circuit breaker
status or other factors exceed user-defined threshold values.
The MPC features two separate power circuits with up to 20 Amps handling capacity per
branch circuit, and is available in a horizontal, rack mount version with eight or sixteen
switched outlets, or as a “zero unit” vertical mount model with 20 switched outlets.
Power Monitoring and Management:
The MPC constantly monitors current, temperature levels, circuit breaker status and
other factors at your network equipment rack. If the MPC detects that user defined
thresholds for these values have been exceeded, the unit can promptly notify you
via email, SNMP, Syslog, LED or audible alarm. In addition, the MPC can also notify
you when it detects that a device is not responding to ping commands, when the
Invalid Access Lockout has been triggered, or when a loss of communication with the
optional auxiliary units is detected. The MPC also records current consumption data
to a convenient log file, which can be retrieved in either ASCII, XML, or CSV format or
displayed in graph format.
Security and Co-Location Features:
Secure Shell (SSHv2) encryption and address-specific IP security masks prevent
unauthorized access to command and configuration functions.
The MPC also provides four different levels of security for user accounts: Administrator,
SuperUser, User and ViewOnly. The Administrator level provides complete access to
all plug functions, operating features and configuration menus. The SuperUser level
allows switching and rebooting of all plugs but does not allow access to configuration
functions. The User level allows access to only a select group of Administrator-defined
plugs. The ViewOnly level allows you to check plug status and unit status, but does not
allow switching or rebooting of outlets.
The MPC also includes full Radius support, LDAP capability, TACACS capability, DHCP
and an invalid access lockout feature. An Audit Log records all user access, login and
logout times and command actions.
Convenient, Durable Design:
The MPC features two separate power circuits and can support up to 40 Amps per unit;
each power circuit is split into two separate circuit breakers. 120 VAC models include
NEMA 5-20 R outlets and 240 VAC models include IEC320-C13 outlets. The MPC is
also available with an optional remote front panel, which can be used to display the
status of MPC units installed in hard-to-reach spots, deep inside equipment racks. Each
MPC unit can also be connected to up to three additional units, allowing control of up to
80 outlets via a single IP Address .

1-2
Introduction
Model Numbers
The MPC series includes horizontal/vertical 8/16/20 outlet and 120/240 VAC models to
accommodate a variety of data center equipment racks and power distribution needs.
Eight and sixteen outlet MPC-H (Horizontal) Series:
• MPC-8H-1 120 VAC, 8 ea. NEMA 5-20R Outlets
• MPC-8H-2 240 VAC, 8 ea. IEC320-C13 Outlets
• MPC-16H-1 120 VAC, 16 ea. NEMA 5-20R Outlets
• MPC-16H-2 240 VAC, 16 ea. IEC320-C13 Outlets
20-outlet MPC-V (Vertical) Series:
• MPC-20V-1 120 VAC, 20 ea. NEMA 5-20R Outlets
• MPC-20V-2 240 VAC, 20 ea. IEC320-C13 Outlets
Standalone front panel display unit:
• MPC-REMOTE
Typographic Conventions
^ (e.g. ^X) Indicates a control character. For example, the text
"^X" (Control X) indicates the [Ctrl] key and the [X]
key must be pressed simultaneously.
COURIER FONT Indicates characters typed on the keyboard.
For example, /RB or /ON A2.
[Bold Font] Text set in bold face and enclosed in square brackets,
indicates a specific key.
For example, [Enter] or [Esc].
< > Indicates required keyboard entries:
For Example: /P <n>.
[ ] Indicates optional keyboard entries.
For Example: /P [n].

2-1
8.8.8 8.8.8
REMOTE
www.wti.com MPC-8H
Managed Power
Controller
AUX 1
AUX 2 AUX 3 CONSOLE PORT
AUDIBLE
ALARM
DEFAULT
ON INPUT A
PLUGS PLUGS
INPUT B
A1 A2 A3 A4 B1 B2 B3 B4
DISPLAY
SELECTION
AMPS KWATTS
VOLTS TEMP
12345
678 9
Figure 2.1: MPC-8H - Front Panel
2. Unit Description
2.1. MPC-H Series - Front Panel
As shown in Figures 2.1 and 2.2, the MPC-H Series Front Panel includes the following
components:
1. Power Circuit A - Indicator Lights: LED indicators, which light when power is
applied to the corresponding outlet on Power Circuit A.
2. Power Circuit A - Digital Display: An LED digital readout, which can be used
to show Amps, Kilowatts, Volts or Temperature for Power Circuit A. Note that the
Display Selection Button is used to determine which value will appear on the digital
display.
3. Display Selection Button and Indicators: Determines which measurement will
appear on the Digital Displays for Circuits A and B. Each time the Display Selection
Button is pressed, the Digital Displays will toggle between Amps, Kilowatts, Volts
and Temperature, and the LED indicators will light to show which measurement is
currently selected. Please refer to Section 2.3 for additional button functions.
4. Power Circuit B - Digital Display: Same as Item 2 above, except displays values
for Power Circuit B.
8.8.8 8.8.8
REMOTE
www.wti.com MPC-16H
Managed Power
Controller
AUX 1
AUX 2 AUX 3 CONSOLE PORT
AUDIBLE
ALARM
DEFAULT
ON INPUT A
PLUGS PLUGS
INPUT B
A1 A2 A3 A4
A5 A6 A7 A8
B1 B2 B3 B4
B5 B6 B7 B8
DISPLAY
SELECTION
AMPS KWATTS
VOLTS TEMP
12345
678 9
Figure 2.2: MPC-16H - Front Panel

2-2
Unit Description
5. Power Circuit B - Indicator Lights: Same as Item 1 above, except LEDs light to
indicate On/Off status of Power Circuit B outlets.
6. Link Ports: Four RJ45 connectors, which can be used to link the MPC unit to up
to three other MPC units, plus the optional MPC-REMOTE, status display panel.
When your MPC unit is linked to other MPC units, this allows control of up to eighty
outlets via one IP address.
7. Console Port: A DB9, RS232 serial port (DTE), which can be used for connection
to a local terminal or external modem, as described in Section 4. For a description
of the Console Port interface, please refer to Appendix A.
8. Default Button: This button can be used to either reset the unit to default
parameters or to perform several other functions, described in Section 2.3.
9. Audible Alarm Button and LED: When any of the Alarms discussed in Section 7
are triggered, this LED will light, and the MPC will emit an audible alarm signal. To
turn off the audible alarm single, press the Audible Alarm Button once. Please refer
to Section 2.3 for additional button functions.

2-3
Unit Description
A-1 A-2 A-3 A-4 B-5 B-6 B-7 B-8 10/100 BaseT
BUS
B
BUS
A
ACT
ALARM
A
B
LINK
12345678
Figure 2.3: MPC-8H-1 - Back Panel
A-1 A-2 A-3 A-4 B-5 B-6 B-7 B-8 10/100 BaseT
BUS
B
BUS
A
ACT
ALARM
A
B
LINK
12345678
Figure 2.4: MPC-8H-2 - Back Panel
BUS
A
BUS
B
BUS
A
BUS
B
A-1 A-2 A-3 A-4 A-5 A-6 A-7 A-8
B-1 B-2 B-3 B-4 B-5 B-6 B-7 B-8 10/100 BaseT
ACT
A
B
ALARM
LINK
1343
26578
6
Figure 2.5: MPC-16H-1 - Back Panel
BUS
A
BUS
B
BUS
A
BUS
B
A-1 A-2 A-3 A-4 A-5 A-6 A-7 A-8
B-1 B-2 B-3 B-4 B-5 B-6 B-7 B-8 10/100 BaseT
ACT
A
B
ALARM
LINK
1343
26576 8
Figure 2.6: MPC-16H-2 - Back Panel

2-4
Unit Description
2.2. MPC-H Series - Back Panel
As shown in Figures 2.3, 2.4, 2.5 and 2.6, the MPC-H Series Back Panel includes the
following components:
1. Power Circuit A - Power Inlet: An IEC320-C20 AC inlet which supplies power to
MPC control functions and the Circuit “A” outlets. Also includes cable keeper
(not shown.)
2. Power Circuit B - Power Inlet: An IEC320-C20 AC inlet which supplies power to
MPC control functions and the Circuit “B” outlets. Also includes cable keeper
(not shown.)
3. Power Circuit A - Circuit Breaker(s): Note that on 16 outlet models, there are two
circuit breakers for each power circuit. The maximum amps for each circuit breaker
are as follows:
• MPC-8H-1 and MPC-16H-1: 20 Amp Circuit Breaker(s).
• MPC-8H-2 and MPC-16H-2: 16 Amp Circuit Breaker(s).
4. Power Circuit A - Switched Outlets: AC Outlets that can be switched On, Off or
rebooted in response to user commands:
• MPC-8H-1: Four (4) each, NEMA 5-20R Outlets.
• MPC-8H-2: Four (4) each, IEC320-C13 Outlets.
• MPC-16H-1: Eight (8) each, NEMA 5-20R Outlets.
• MPC-16H-2: Eight (8) each, IEC320-C13 Outlets.
5. Power Circuit B - Switched Outlets: Same as Item 4 above.
6. Power Circuit B - Circuit Breaker(s): Same as Item 3 above.
7. Alarm Indicator Lights: Two LEDs which light when an alarm condition is detected
at the corresponding power circuit. For information on Alarm Configuration, please
refer to Section 7.
8. Network Port: An RJ45 Ethernet port for connection to your 100Base-T, TCP/IP
network. Note that the MPC features a default IP address (192.168.168.168). This
allows you to connect to the unit without first assigning an IP address. Note that the
Network Port also includes two, small LED indicators for Link and Data Activity. For
more information on Network Port configuration, please refer to Section 5.9.

2-5
Unit Description
Managed Power Controller
MPC-20V
8.8.8 8.8.8
DEFAULT
AUDIBLE
ALARM ON
DISPLAY
SELECTION
AMPS KWATS VOLTS TEMP
INPUT A INPUT B
AUX
1
AUX
3
REMOTE
DISPLAY
AUX
2
Ethernet
10/100
CONSOLE
1
2
3
7
4
5
6
10
10
1211
14
8
9
9
13
Managed Power Controller
MPC-20V
8.8.8 8.8.8
DEFAULT
AUDIBLE
ALARM ON
DISPLAY
SELECTION
AMPS KWATS VOLTS TEMP
INPUT A INPUT B
AUX
1
AUX
3
REMOTE
DISPLAY
AUX
2
Ethernet
10/100
CONSOLE
1
2
3
7
4
5
6
8
10
1211
14
910
9
13
MPC-20V-1 MPC-20V-2
Figure 2.7: MPC-20V Series - Hardware Description

2-6
Unit Description
2.3. MPC-V Series - Hardware Description
As shown in Figure 2.7, MPC-V Series units include the following components:
1. Default Button: This button can be used to either reset the unit to default
parameters or to perform several other functions, as described in Section 2.3.
2. Audible Alarm Button and LED: Two LEDs which light when an alarm condition
is detected at the corresponding power circuit. For information on Alarm
Configuration, please refer to Section 7. Please refer to Section 2.3 for additional
button functions.
3. Display Selection Button and Indicators: Determines which measurement will
appear on the Digital Displays for Circuits A and B. Each time the Display Selection
Button is pressed, the Digital Displays will toggle between Amps, Kilowatts, Volts
and Temperature, and the LED indicators will light to show which measurement is
currently selected. Please refer to Section 2.3 for additional button functions.
4. Link Ports: Four RJ45 connectors, which can be used to link the MPC unit to up
to three other MPC units, plus the optional MPC-REMOTE, status display panel.
When your MPC unit is linked to other MPC units, this allows control of up to eighty
outlets via one IP address.
5. Network Port: An RJ45 Ethernet port for connection to your 100Base-T, TCP/IP
network. Note that the MPC features a default IP address (192.168.168.168). This
allows you to connect to the unit without first assigning an IP address. Note that the
Network Port also includes two, small LED indicators for Link and Data Activity. For
more information on Network Port configuration, please refer to Section 5.9.
6. Console Port: A DB9, RS232 serial port (DTE), which can be used for connection
to a local terminal or external modem, as described in Section 4. For a description
of the Console Port interface, please refer to Appendix A.
7. Power Circuit A - Digital Display: An LED digital readout, which can be used
to show Amps, Kilowatts, Volts or Temperature for Power Circuit A. Note that the
Display Selection Button (Item 3) is used to select the value that will appear on the
digital display.
8. Power Circuit B - Digital Display: Same as Item 7 above, except displays values
for Power Circuit B.
9. Power Circuit A - Circuit Breaker(s): There are two circuit breakers for each
power circuit. The maximum amps for each circuit breaker are as follows:
• MPC-20V-1: 20 Amp Circuit Breaker(s).
• MPC-20V-2: 16 Amp Circuit Breaker(s).
10. Power Circuit B - Circuit Breaker(s): Same as Item 9 above, except circuit
breakers apply to Power Circuit B.

2-7
Unit Description
11. Power Circuit A - Switched Outlets: AC Outlets that can be switched On, Off or
rebooted in response to user commands:
• MPC-20V-1: Ten (10) each, NEMA 5-20R Outlets.
• MPC-20V-2: Ten (10) each, IEC320-C13 Outlets.
12. Power Circuit B - Switched Outlets: Same as Item 11 above, except outlets are
for Power Circuit B.
13. Power Circuit A - Power Inlet: An IEC320-C20 AC inlet which supplies power to
the Circuit “A” outlets. Also includes cable keeper (not shown.)
14. Power Circuit B - Power Inlet: An IEC320-C20 AC inlet which supplies power to
the Circuit “B” outlets. Also includes cable keeper (not shown.)
2.4. Button Functions
The Default, Audible Alarm and Display Selection buttons can be used to perform
several functions described below:
1. Reboot Operating System:
a) Press and hold the Default button for five seconds, and then release it.
b) The MPC will reboot it's operating system; all plugs will be left in their current
On/Off state.
c) If the optional MPC-REMOTE unit is installed, and this operation is performed
at the MPC-REMOTE unit, all connected MPC units will also be rebooted.
2. Set Parameters to Factory Defaults:
a) Simultaneously press both the Default button and the Display Selection button,
hold them for five seconds, and then release them.
b) All MPC parameters will be reset to their original factory default settings, and
the unit will then reboot. All plugs will be left in their current On/Off state.
c) This function will not be applied to other connected MPC units.
3. Toggle/Default All Plugs:
a) Simultaneously press both the Default button and Audible Alarm button, hold
them for five seconds, and then release them.
b) The MPC will switch all plugs to the Off state. If all plugs are already in the Off
state, then the unit will reset all plugs to their user defined default states.
c) This function will not be applied to other connected MPC units.

2-8
Unit Description
4. Enable/Disable Audible Alarm:
a) In the default state, the Audible Alarm is Enabled.
b) To disable the Audible Alarm, press and hold the Audible Alarm button for three
seconds and then release it. To enable the Audible Alarm, press and hold the
Audible Alarm button for three seconds again.
c) If the optional MPC-REMOTE unit is installed, and this operation is performed
at the MPC-REMOTE unit, all connected MPC units will also be rebooted,
otherwise, the operation will only be applied to the unit where the buttons
reside.

3-1
3. Getting Started
This Quick Start Guide describes a simplified installation procedure for the MPC series
hardware, which will allow you to communicate with the unit in order to demonstrate
basic features and check for proper operation.
Note that this Quick Start Guide does not provide a detailed description of unit
configuration, or discuss advanced operating features in detail. In order to take full
advantage of the features provided by this unit, it is recommended that you should refer
to the remainder of this User’s Guide.
3.1. Installing the MPC Hardware
Note: This section describes the installation procedure for the MPC-20V,
MPC-16H and MPC-8H hardware. For Quick Start installation instructions for
the optional MPC-REMOTE unit, please refer to Section 3.3.
3.1.1. Apply Power to the MPC-20V
Refer to power rating nameplate on the MPC unit, and then connect the unit to an
appropriate power source. Note that the MPC features two separate AC inputs and
two separate power busses; connect power cables to the unit’s Circuit “A” and Circuit
“B” Power Inlets, install the cable keepers (as described in Section 4.1.1), then connect
the cables to an appropriate power supply. Refer to the table below for information
concerning power requirements and maximum load.
Model No.
Total
Outlets
Input
Voltage
Max. Load
per Outlet
Max. Load
per Bus
Max. Load
per Unit
MPC-8H-1 8 100 to 120 VAC 20 Amps 20 Amps 40 Amps
MPC-8H-2 8 100 to 240 VAC 10 Amps 16 Amps 32 Amps
MPC-16H-1 16 100 to 120 VAC 20 Amps 20 Amps 40 Amps
MPC-16H-2 16 100 to 240 VAC 10 Amps 16 Amps 32 Amps
MPC-20V-1 20 100 to 120 VAC 20 Amps 20 Amps 40 Amps
MPC-20V-2 20 100 to 240 VAC 10 Amps 16 Amps 32 Amps
Other manuals for MPC Series
1
This manual suits for next models
7
Table of contents
Other WTI Controllers manuals
Popular Controllers manuals by other brands

Asco
Asco WSDU-M Series Installation and maintenance instructions

Chromalox
Chromalox CTF Configuration software manual

Kessler-Ellis Products
Kessler-Ellis Products SUPERtrol II Addendum to Manual

Omron
Omron F3SX-N-D1RR2 Original instructions

Outback Power Systems
Outback Power Systems MX60 Installation and user manual

Mitsubishi Electric
Mitsubishi Electric MELSEC-QS Series user manual