XEMEX DINgate DSO User manual

USER MANUAL
DINgate DSO
Copyright ©XEMEX
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by
any means, electronic, mechanical, photocopying, recording or otherwise, without prior written permission of the publisher.

User Manual - DINgate DSO
01 October 2021 XEMEX Confidential Page 2 of 16
DOCUMENT INFO
Version: 1.0
Status: Draft
Version date: 1/10/2021
Filename: User Manual - DINgate DSO.docx
Author: Luc Olieslagers
Number of pages: 16
HISTORY CHANGES
VERSION
DATE
DESCRIPTION
1.0
11/08/2021
Draft

User Manual - DINgate DSO
01 October 2021 XEMEX Confidential Page 3 of 16
TABLE OF CONTENTS
1INTRODUCTION...................................................................................................................................... 5
1.1 Scope .............................................................................................................................................................. 5
1.2 Target group................................................................................................................................................... 5
1.3 Disclaimer....................................................................................................................................................... 5
1.4 Applicable product versions ........................................................................................................................... 5
1.5 Intended usage............................................................................................................................................... 5
1.6 Technical assistance ....................................................................................................................................... 5
1.7 Used symbols.................................................................................................................................................. 5
1.8 Safety precautions.......................................................................................................................................... 6
2TECHNICAL DESCRIPTION................................................................................................................... 7
3TECHNICAL SPECIFICATIONS ............................................................................................................. 8
3.1 Mains power connection................................................................................................................................ 8
3.2 RS485 / Modbus RTU Interface ...................................................................................................................... 8
3.2.1 Physical Interface ....................................................................................................................................... 8
3.2.2 Protocol Description................................................................................................................................... 8
3.3 IR Interface ..................................................................................................................................................... 8
3.4 User Interface - LEDs ...................................................................................................................................... 9
3.5 SIM card slot................................................................................................................................................... 9
3.6 LTE antenna connection ................................................................................................................................. 9
3.6.1 DINgate DSO 1.0......................................................................................................................................... 9
3.6.2 DINgate DSO 1.1......................................................................................................................................... 9
3.7 Enclosure ........................................................................................................................................................ 9
3.8 Environmental conditions .............................................................................................................................. 9
3.9 Standards........................................................................................................................................................ 9
4INSTALLATION INSTRUCTIONS.........................................................................................................11
4.1 Guidelines for safety and installation........................................................................................................... 11
4.2 Mounting...................................................................................................................................................... 11
4.3 Electrical wiring diagram .............................................................................................................................. 11
4.4 Data connection with ABB B21 / B23 E-meter ............................................................................................. 12
4.4.1 Via IR Interface......................................................................................................................................... 12
4.4.2 Via Modbus Interface............................................................................................................................... 12
4.5 Insert/extract SIM card................................................................................................................................. 13
4.6 LTE Antenna.................................................................................................................................................. 13
4.7 Mains power................................................................................................................................................. 13
4.8 Configuration................................................................................................................................................ 14
5OPERATING INSTRUCTIONS..............................................................................................................15
5.1 PWR –POWER Status LED –Red LED ........................................................................................................... 15
5.2 WAN –Network Status LED –Green LED ..................................................................................................... 15
5.3 Service button .............................................................................................................................................. 15

User Manual - DINgate DSO
01 October 2021 XEMEX Confidential Page 4 of 16
6CLEANING.............................................................................................................................................16
7LIFTING AND CARRYING.....................................................................................................................16
8MAINTENANCE AND SERVICE ........................................................................................................... 16

User Manual - DINgate DSO
01 October 2021 XEMEX Confidential Page 5 of 16
1Introduction
1.1 Scope
This manual is applicable to DINgate DSO, a communication gateway for the ABB B21/B23 E-meter family.
It describes the specifications, installation and operation of the product. Please read this document carefully before
installation and operating.
1.2 Target group
The installation and the operation of this device and any maintenance must be carried out by a qualified person in
accordance with specific local standards and safety regulations.
1.3 Disclaimer
The information in this document is subject to change without notice and should not be construed as a promise by
Xemex. Xemex assumes no liability for possible errors in this document. In no event shall Xemex be liable for direct,
indirect, special, incidental, or consequential damages of any kind arising out of the use of this document, nor shall
Xemex be liable for incidental or consequential damages arising out of the use of this document, described software
or hardware.
1.4 Applicable product versions
This manual is applicable for following product versions:
Product version
Description
DINgate 1.0 –DSO
4G Cat-1 with GPRS fallback communication gateway for ABB B21/B23 E-meters
DINgate 1.1 –DSO
4G Cat-M communication gateway for ABB B21/B23 E-meters
1.5 Intended usage
The DINgate DSO module can only be used in combination with the ABB B21/B23 E-meter family and shall operate
within the specified values only.
1.6 Technical assistance
In case technical assistance is needed, contact Xemex NV:
XEMEX NV
Metropoolstraat 11a
B-2900 Schoten
Belgium
Tel: +32 201 95 95
E-mail: support@xemex.eu
1.7 Used symbols
Following symbols are used in this document and/or are marked on the product:
Alternating current

User Manual - DINgate DSO
01 October 2021 XEMEX Confidential Page 6 of 16
Three-phase alternating current
Equipment protected throughout by DOUBLE INSULATION or REINFORCED
INSULATION
Caution, possibility of electric shock
Caution
1.8 Safety precautions
DANGER —HAZARDOUS VOLTAGES
WARNING - These installation/servicing instructions are for use by qualified personnel only.
To avoid electrical shock, do not perform any servicing other than that contained in the
operating instructions unless you are qualified to do so.
WARNING –Mains protection
WARNING - The DINgate module must always be protected by fuses on the incoming side. To
enable maintenance DINgate module, it is recommended to install a short circuit protection.
Do not operate the equipment other than indicated by the technical data.
Always adhere to the following checklist:
1. Only qualified personnel or licensed electricians should install the Xemex DINgate DSO. The mains voltages
of 230 Vac can be lethal!
2. Follow all applicable local and national electrical and safety codes.
3. Install the device in an electrical enclosure (panel or junction box) or in a limited access electrical room.
4. Verify that circuit voltages and currents are within the proper range for the DINgate module.
5. Ensure that the DINgate is placed behind fuses or circuit breakers.
6. Equipment must be disconnected from the HAZARDOUS LIVE voltages before access.
7. Before applying power, check that all the wires are securely installed by tugging on each wire.
8. Do not install the DINgate module where it may be exposed to temperatures below –20°C or above 70°C,
excessive moisture, dust, salt spray, or other contamination. The device requires an environment no worse
than pollution degree 2 (normally only non-conductive pollution; occasionally, a temporary conductivity
caused by condensation must be expected).
9. Do not drill mounting holes in the device. Click the module on a DIN Rail instead.
10. If the DINgate device is installed incorrectly, the safety protections may be impaired.

User Manual - DINgate DSO
01 October 2021 XEMEX Confidential Page 7 of 16
2Technical description
The Xemex DINgate DSO device is a communication gateway with a Modbus Interface and an optical interface to
connect an ABB B21 of B23 E-meter.
It has following interfaces:
•Main power connection 230V
•RS485 / Modbus RTU Communication Interface
•Optical Interface
•User Interface - LEDs
•SIM card slot (for 2FF SIMs)
•LTE antenna connection (SMA)
The DINgate DSO module reads out the ABB B21 or B23 E-meter every 10 seconds and logs the data. Data can be
readout using the DLMS protocol via a TCP/IP connection over LTE.
The DLMS object model uses the SMR5 specification as a reference. Extra OBIS objects are added to provide LTE
connection settings and diagnostics. For these extra objects, the ESMR specification is used as reference.
The combination DINgate DSO + ABB E-meter can be seen as a compact version of the Dutch smart meter.
LTE antenna connection
RS485 / Modbus RTU
Interface
Mains power
connection 230V
User Interface - LEDs
SIM card slot
IR Interface

User Manual - DINgate DSO
01 October 2021 XEMEX Confidential Page 8 of 16
3Technical specifications
3.1 Mains power connection
DANGER
Working with high voltages is a potential danger to life. Persons exposed to high voltages can
suffer cardiac arrest, burns or other serious injuries. To avoid such accidents, make sure to
disconnect the power supply before starting the installation.
Nominal Voltage: 230 Vac
Voltage range: 220-240 Vac +/-10%
Frequency: 50 or 60 Hz
I nom: 10 mA
Connector: 2-pole screw terminal connector
Terminal wire: Solid wire / 0.2 –6 mm2
Stranded wire / 0.2 –4 mm2
Max torque: 0.6 Nm
Wire stripping: 7 mm
3.2 RS485 / Modbus RTU Interface
3.2.1 Physical Interface
Connector: Screw terminal connector for A, B and Shield
Terminal wire: 0.2 -1.5 mm2
Wire stripping length: 5 –6 mm
Max torque: 0.2 Nm
Max cable length: 30 meter
Cable location: indoor
3.2.2 Protocol Description
Protocol: Modbus RTU master over RS485
Modbus address default value = 1
Baud rate: 1200 ... 115200
default value = 19200 baud
Line setting: 8N1 (line settings register value = 0x04) , 8E1 (line settings register value = 0x24)
default value = 8E1
3.3 IR Interface
Optical interface to connect to ABB meter without wire connection.
Is an alternative for the RS485 Modbus connection between DINgate DSO and the ABB E-meter.

User Manual - DINgate DSO
01 October 2021 XEMEX Confidential Page 9 of 16
3.4 User Interface - LEDs
Power / Modbus indicator: Red LED
WAN indicator: Green LED
(See operating instruction 5.1 and 5.2 for functional explanation of the LEDs.)
3.5 SIM card slot
SIM card type: mini SIM (2FF) 25 x 15 mm
SIM Insert / extract: push / push
3.6 LTE antenna connection
The DINgate DSO is equipped with an LTE Cat-1 modem with GPRS fallback (DINgate DSO 1.0) or an LTE Cat-M
modem (DINgate DSO 1.1) functionality.
The supported frequency bands are:
3.6.1 DINgate DSO 1.0
-LTE Cat-1: B1, B3, B7, B8, B20
-GPRS: 900/1800 MHz
-Connector type on DINgate: SMA Female
3.6.2 DINgate DSO 1.1
-LTE-M: B3 (1800MHz) / B8 (900MHz) / B20 (800MHz)
-Connector type on DINgate: SMA Female
3.7 Enclosure
DIN rail mount: DIN 43880 / 2 units
Dimensions: 90 x 36 x 65 mm
Weight: 106 gr
Material: PA66-FR
3.8 Environmental conditions
Protection class II
Operating temperature -20 °C - +70 °C
Storage temperature -40 °C - +70 °C
Relative humidity < 75 % year’s average at 21 °C
< 95 % less than 30 days/year, at 25 °C
Pollution Degree 2
Altitude < 2000m
Application area Residential, Indoors in suitable meter cabinet
3.9 Standards
Safety: IEC 60950-1
Radiated emission: EN 55016-3-2
Conducted emission: EN 55016-2-1
Harmonic current emission: EN 61000-3-2
Voltage changes, fluctuations & flicker: EN 61000-3-3
Electrostatic discharge: EN 61000-4-2
RF immunity: EN 61000-4-3
Electrical fast transient: EN 61000-4-4
Surges: EN 61000-4-5

User Manual - DINgate DSO
01 October 2021 XEMEX Confidential Page 10 of 16
RF common mode: EN 61000-4-6
Voltage dips: EN 61000-4-11

User Manual - DINgate DSO
01 October 2021 XEMEX Confidential Page 11 of 16
4Installation instructions
4.1 Guidelines for safety and installation
This installation guide must be consulted in all cases when manipulating parts which are marked
with the Caution symbol.
The installation and the operation of this device and any maintenance must be carried out by a
qualified person in accordance with specific local standards and safety regulations.
Caution: never open the secondary circuit of a Current Transformer while current is flowing
through the primary circuit!
If the secondary circuit is opened when primary current is flowing, then the voltage will go to a very
high value, possibly causing electrical arcing and/or electrical shock to service personnel. Therefore
CT’s with internal TVS must be used.
Failing to obey the ”Guidelines for safety and installation”, the guarantee no longer applies.
4.2 Mounting
Mount the device in a DIN rail cabinet.
4.3 Electrical wiring diagram
WARNING
The DINgate DSO module power connection always needs to be protected with a circuit
breaker.

User Manual - DINgate DSO
01 October 2021 XEMEX Confidential Page 12 of 16
4.4 Data connection with ABB B21 / B23 E-meter
4.4.1 Via IR Interface
Place de DINgate DSO module on the left side of the ABB E-meter so both IR interfaces make contact.
4.4.2 Via Modbus Interface
B (-)
A (+)
Shield

User Manual - DINgate DSO
01 October 2021 XEMEX Confidential Page 13 of 16
4.5 Insert/extract SIM card
The DINgate DSO has as slot on the front to insert a SIM card:
-Formfactor: mini SIM or 2FF
-To insert: push the SIM, with the contact area on the right side, in the slot until it clicks.
-To extract: push the SIM a bit further in the housing until it clicks and then release it to let it spring back.
4.6 LTE Antenna
The antenna used to connect to the DINgate DSO needs to have an SMA male connector.
The supported bands need to correspond with the bands provided by the SIM operator within the available LTE and
GPRS bands. (see 3.6)
4.7 Mains power
DANGER
Working with high voltages is a potential danger to life. Persons exposed to high voltages can suffer
cardiac arrest, burns or other serious injuries. To avoid such accidents, make sure to disconnect the
power supply before starting the installation.
WARNING
The DINgate DSO module power connection always needs to be protected with a circuit breaker.
N
L

User Manual - DINgate DSO
01 October 2021 XEMEX Confidential Page 14 of 16
4.8 Configuration
The DINgate DSO modules are preconfigured in production.
Some configuration settings can be changed using specific tooling (remote or local via optical interface). This is
described in document “Xemex product configuration via Gurux.docx” but out of scope for this document.

User Manual - DINgate DSO
01 October 2021 XEMEX Confidential Page 15 of 16
5Operating instructions
The DINgate DSO module in combination with the ABB E-meter acts as small version of a smart meter.
The unit supports the industry-standard protocol DLMS-COSEM for the WAN connection. This protocol implements
the SMR5 application layer.
The DINgate module gives visual feedback on its working state by its 2 Status LED Indicators:
5.1 PWR –POWER Status LED –Red LED
•Not lit: DINgate module is not powered
•Blinking: DINgate module is powered, but did not (yet) able to readout the ABB meter
•Lit: DINgate module is powered, and has readout the ABB meter
5.2 WAN –Network Status LED –Green LED
•Not lit: The DINgate module is not connected to a radio network.
This may have one of the following causes
-No or wrong SIM card (disabled)
-No network coverage
-Modem is defect
•Blinking: The DINgate module is registered to the radio network
In this state the module is able to receive an SMS or RING trigger. No end to end data
session with the head-end system can be established.
•Lit: The DINgate module is registered to the radio network and a PDP context was established.
This means the module got an IP address from the network and the head-end system is
able to establish a data connection with the module.
Warning: the nominal state of the network status LED depends on the configuration of the module:
1. Always on configuration: Nominal state is 'LED Lit'.
This means the module can always be reached on its IP address by the head-
end system.
2. Triggered configuration: Nominal state is 'LED blinking'.
In this state the module first needs to receive a ‘trigger’ before a PDP context
will be established and the LED temporary be lit.
5.3 Service button
For future use.

User Manual - DINgate DSO
01 October 2021 XEMEX Confidential Page 16 of 16
6Cleaning
Clean the unit with a slightly damp cloth and mild detergent.
7Lifting and carrying
Use care when lifting and carrying the product.
8Maintenance and Service
There are no serviceable parts inside.
End Of Document.