D2443-01-05 CN5384 SEM1630 User Guide
IMPORTANT - CE & SAFETY REQUIREMENTS
This product is suitable for enviroment Installation category II pollution degree.
The product is classed as "PERMANENTLY CONNECTED EQUIPMENT".
Product must be DIN rail mounted, inside a suitable enclosure providing environmental protection to IP65 or greater.
Dc supply must be derived from a local supply and not a distribution system.
Max relay contact rating 250 V AC @ 1 A (30 V DC @ 1A). Any circuit connected to a contact must be fused with a 2A (T) fuse.
To maintain CE EMC requirements , input and supply wires must be less than 30 metres.
The product contains no serviceable parts , or internal adjustments. no attempt must be made to repair this product. Faulty units must be returned to supplier for repair.
This product must be installed by a qualified person. All electrical wiring must be carried out in accordance with the appropriate regulations for the place of installation.
Before attempting any electrical connection work, please ensure all supplies are switched off.
ABSOLUTE MAXIMUM CONDITIONS ( To exceed may cause damage to the unit):-
Supply Voltage ± 30 V dc (Protected for over voltage and reverse connection)
Current with over voltage ± 200 mA
Input Voltage ± 5 V between any terminals
Input Current ± 100 mA between terminals 7 & 10
Ambient Temperature (-30 to 75) °C Humidity (10 to 95) % RH (Non condensing)
Status Instruments Ltd, Status Business Park, Gannaway Lane, Tewkesbury, Gloucestershire, UK, GL20 FD
Web Page: www.status.co.uk Tel : +44 (0) 16 4 296 1 Fax: +44 (0) 16 4 293746 email : sales@status.co.uk
Every effort has been taken to ensure the accuracy of this document, however we do not accept responsibility for damage, injury, loss or expense resulting from errors and omissions, and we reserve the right of amendment without notice.
Important - Potentially Hazardous situations. Persons responsible for the installation and operation of this equipment must be fully aware of all
aspects of this guide. Failure to follow the instructions can cause severe injuries and damage.
The following parameter can be configured by simply entering as prompted by
the software package.
· Input type (K,J,E,N,T,R,S,mV,PT100,mA)
· Setpoint Relay 1 & 2
· Hysterisis Relay 1 & 2
· Units (°C, °F, mV, mA)
· Relay 1 & 2 Type (High or Low)
PRODUCT SPECIFICATION
mA
Universal Input
10
9
8
7
mV
++
--
PT100
+
-
Dual trip Output
SEM1630
1
V s
USB
+
-
+
-
3
1
4
5
6
n/o
n/c
c
n/o
n/c
c
Relay 1
Relay
11
SEM1630 USER GUIDE
DIN AIL MOUNTED T IP AMP
UNIVE SAL INPUT
DUAL Form C OUTPUT
RECEIVE AND UNPACKING
CONFIGURATION
Please refer to the product data sheet for full specification, available to down load at www.status.co.uk.
Please inspect the packaging and instrument thoroughly for any signs of transit damage. If the instrument has been damaged, please notify
your supplier immediately.
SEM1630
USB LINK SOFTWARE
USB CABLE
Download @
www.status.co.uk
COMPUTER
Factory default:
Input type = P
Units = °C
Relay 1 = H
Setpoint Relay 1 = 50
Hysterisis Relay = 1
Relay = H
Setpoint Relay = 50
Hysterisis Relay = 1
IMPORT NT The SEM1630 can be configured whilst connected and powered, but a portable battery powered computer must be
used to avoid the effects of ground loops.
Note: The power supply and USB port of this device share the same ground , care must be taken to ensure isolation between PC and ground.
This is best achieved by using a portable laptop or notebook PC.
FRONT PANEL INDICATION
Relay 1 alarm LED on in alarm state
Relay 2 alarm LED on in alarm state
State LED on when input is out of range
USB configuration port
MECHANICAL INSTALLATION
SEM1630 Enclosure
Style DIN 43880 (1 module width)
Material Polyamide 6.6 self extinguishing
Terminals Screw terminal
Cable 2.5 mm Max
Colour Grey
3 mm
MOUNTING
Screw driver
EN50022 DIN RAIL
1
2
+ 70 °C Max
- 20 °C Min
UNIVERSAL INPUT CONNECTION
For cable length < 3 Metres no screen or twist pair required.
Thermocouple inputs must use correct compensation cable.
PT100 inputs all three wire must be equal length (resistance).
Use recommended types for cable length (3 to 30) metres.
mV
+
+
-
-
PT100
mA
+
-
SUPPLY
Max cable length 30 metres
3 mm
ELECTRICAL INSTALLATION
Screw Driver
Screened Cable Twisted Pair Cable
10
7
7
9
77
TC Compensation Cable
Screened 1.0 TURN OFF SUPPLY BEFORE WORKING ON ANY
ELECTRICAL CONNECTION.
.0 FUSE CONTACT CIRCUITS A (T).
3.0 MAX CONTACT RATING 50 V ac
(30 V dc) @ 1 A
10
9
8
7
SEM1630
1
V s
USB
+
-
+
-
3
11
1
4
5
6
n/o
n/c
c
n/o
n/c
c
Relay 1
Relay
A (T)
A (T)
To fit or release module
Insert screw driver into
slot and lever latch
away from body
17.5 mm
1
2
11 110
987
4 5 6
1 3
90 mm
56.4 mm
RELAY 1
T/C
1
2
D2443-01-05 CN5384 SEM1630 User Guide
RELAY 1
RELAY
STATE
USB
RELAY 1
RELAY
STATE
USB
RELAY 2
STATE
USB
Note: The Relays are inverted on power up, the side label shows the powered condition. In a non-alarm condition loss of power to the SEM1630
will cause the relay to change state.

Popular Control Unit manuals by other brands

Roland super quartet mks-7 owner's manual

Roland

Roland super quartet mks-7 owner's manual

Sioux Tools 1785 Service and operation manual

Sioux Tools

Sioux Tools 1785 Service and operation manual

MSD 6A 6201 installation instructions

MSD

MSD 6A 6201 installation instructions

Festo VMPA1-HS Assembly instructions

Festo

Festo VMPA1-HS Assembly instructions

IDEC MicroSmart Series quick start guide

IDEC

IDEC MicroSmart Series quick start guide

3Com CoreBuilder 9000 Getting started guide

3Com

3Com CoreBuilder 9000 Getting started guide

Altronix MOM5C installation guide

Altronix

Altronix MOM5C installation guide

Quectel LTE OPEN EVB user guide

Quectel

Quectel LTE OPEN EVB user guide

Millenium MPS-150X user manual

Millenium

Millenium MPS-150X user manual

Broadcast Tools I/O Sentinel 4 G2 Installation and operation manual

Broadcast Tools

Broadcast Tools I/O Sentinel 4 G2 Installation and operation manual

Land Pride 380-137A Assembly instructions

Land Pride

Land Pride 380-137A Assembly instructions

Xiamen Four-Faith Communication F8913D user manual

Xiamen Four-Faith Communication

Xiamen Four-Faith Communication F8913D user manual

Wavetronix Click 200 quick start guide

Wavetronix

Wavetronix Click 200 quick start guide

D-Link DMC-1002 Quick installation guide

D-Link

D-Link DMC-1002 Quick installation guide

H3C SecPath PSR300-12A2 user manual

H3C

H3C SecPath PSR300-12A2 user manual

Congatec conga-QMX8X quick start guide

Congatec

Congatec conga-QMX8X quick start guide

Task Force Tips FlipTip Instruction for operation and maintenance

Task Force Tips

Task Force Tips FlipTip Instruction for operation and maintenance

GST I-9300 manual

GST

GST I-9300 manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.