Siemens Building Technologies SpA CE1N7601e 05-04-2004
4/8
Every change of jumper setup should be made under power off. Alternatively, if change is
made under power on conditions, the control unit must be powered off for at least 5s.
If no Intelligas valve should be connected to EV output, insert a valve termination Rv
1.8Kohm 1/2W (supplied with the equipment) in the EV terminal. This will avoid any wrong
valve fault signal.
______________________________________________________________________________________________
After powering up (24V AC) the control unit LYC11 carries out these phases in sequence:
1. Sensor preheating phase. During this phase, about 1min, the detection system is not
operational. Moreover, it is not possible to open the solenoid valve if normally closed,
while it is possible to if normally open.
2. TEST phase. During this phase, about 3min, all internal timers are zeroed in order to
facilitate sensor test (alarm simulation).
3. Normal operation phase. This is the normal operating phase of the control unit while
both gas alarm monitoring and self test for plant faults (sensor and valve) and system
faults (control unit) are active.
In presence of dangerous gas or carbon monoxide concentrations control unit LYC11
enters gas alarm phase and carries out these operations:
§Closes the gas cut-off solenoid valve and avoids it can be open again until alarm
condition is true. Closing is made as follows:
-NC Valve type = voltage cut-off from EV terminals
-NO Valve type = voltage feed to EV terminals, by impulses or continuously
(please refer to VALVE MODE jumper),
§Activates flashing of red alarm LED
§Activates auxiliary devices (if connected to the relay)
Once gas alarm condition is passed the control unit must be reset to normal operation.
Press RESET button on front side: the control unit carries out the following operations:
§makes possible manual opening of cut-off valve
§deactivates flashing of red alarm LED that turns steady on
§deactivates auxiliary devices (if connected to the relay)
At any moment, starting from normal operating condition, it is possible to activate again
TEST phase by pressing RESET button for at least 5s.
Note:
Return to normal operating condition by pressing RESET button is possible only if there
are no active alarms.
WARNING:
The sensor must be replaced within the 5th year from installation date
Operation