xtra XR10 User manual

A Division of ITW Ltd
Foster Refrigerator
Oldmedow Road
King’s Lynn
Norfolk, PE30 4JU
United Kingdom
Original Service Manual
XR10, XR20 & XR35 Blast Chiller Cabinets
LAE CIB-BC-PU1 Controller
April 2014 Issue 2
English
0772
www.fosterrefrigerator.co.uk

1 | P a g e
GB
Manual Information & Health & Safety Notes
1
Environmental Management Policy with Disposal Requirements & General Electrical Safety
2
Start Up & Operation
3 to 4
User Settings
4 to 5
Parameters
5 to 9
Technical Data for Blast Chiller
10 to 11
Servicing/Cleaning
12 to 14
Wiring Diagrams
15
Troubleshooting & Alarms
16
Notes
17
Make sure the power supply is turned off before making any electrical
repairs.
To minimise shock and fire hazards, please do not plug or unplug the unit
with wet hands.
During maintenance and cleaning, please unplug the unit where required.
Care must be taken when handling or working on the unit as sharp edges
may cause personal injury, we recommend the wearing of suitable PPE.
Ensure the correct moving and lifting procedures are used when relocating a
unit.
Do NOT use abrasive cleaning products, only those that are recommended.
Never scour any parts of the refrigerator. Scouring pads or chemicals may
cause damage by scratching or dulling polished surface finishes.
Failure to keep the condenser clean may cause premature failure of the
motor/compressor which will NOT be covered under warranty policy.
Do NOT touch the cold surfaces in the freezer compartment. Particularly
when hands are damp or wet, skin may adhere to these extremely cold
surfaces and cause frostbite.
Please ensure the appropriate use of safety aids or Personnel Protective
Equipment (PPE) are used for you own safety.
The products and all information in this manual are subject to change without prior notice.
We assume by the information given that the person(s) working on these refrigeration units are
fully trained and skilled in all aspects of their workings. Also that they will use the appropriate safety
equipment and take or meet precautions where required.
The service manual does not cover information on every variation of this unit; neither does it cover the
installation or every possible operating or maintenance instruction for the units.

2 | P a g e
GB
Product Support and Installation Contractors.
Foster Refrigerator recognises that its activities, products and services can have an adverse impact
upon the environment.
The organisation is committed to implementing systems and controls to manage, reduce and
eliminate its adverse environmental impacts wherever possible, and has formulated an
Environmental Policy outlining our core aims. A copy of the Environmental Policy is available to all
contractors and suppliers upon request.
The organisation is committed to working with suppliers and contractors where their activities have
the potential to impact upon the environment. To achieve the aims stated in the Environmental
Policy we require that all suppliers and contractors operate in compliance with the law and are
committed to best practice in environmental management.
Product Support and Installation contractors are required to:
1. Ensure that wherever possible waste is removed from the client’s site, where arrangements are in
place all waste should be returned to Foster Refrigerator’s premises. In certain circumstances waste
may be disposed of on the client’s site; if permission is given, if the client has arrangements in place
for the type of waste.
2. If arranging for the disposal of your waste, handle, store and dispose of it in such a way as to
prevent its escape into the environment, harm to human health, and to ensure the compliance with
the environmental law. Guidance is available from the Environment Agency on how to comply with
the waste management ‘duty of care’.
3. The following waste must be stored of separately from other wastes, as they are hazardous to the
environment: refrigerants, polyurethane foam, and oils.
4. When arranging for disposal of waste, ensure a waste transfer note or consignment note is
completed as appropriate. Ensure that all waste is correctly described on the waste note and include
the appropriate six-digit code from the European Waste Catalogue. Your waste contractor or Foster
can provide further information if necessary.
5. Ensure that all waste is removed by a registered waste carrier, a carrier in possession of a waste
management licence, or a carrier holding an appropriate exemption. Ensure the person receiving the
waste at its ultimate destination is in receipt of a waste management licence or valid exemption.
6. Handle and store refrigerants in such a way as to prevent their emission to atmosphere, and
ensure they are disposed of safely and in accordance with environmental law.
7. Make arrangements to ensure all staff who handle refrigerants do so at a level of competence
consistent with the City Guilds 2078 Handling Refrigerants qualification or equivalent qualification.
8. Ensure all liquid substances are securely stored to prevent leaks and spill, and are not disposed of into storm
drains, foul drain, or surface water to soil.
If not disposed of properly all refrigerators have components that can be harmful to the environment.
All old refrigerators must be disposed of by appropriately registered and licensed waste contractors,
and in accordance with national laws and regulations.
Foster Refrigerator recommends that the equipment is electrically connected via a Residual Current
Device; such as a Residual Current Circuit Breaker (RCCB) type socket, or through a Residual Current
Circuit Breaker with Overload Protection (RCBO) supplied circuit.

3 | P a g e
GB
Initial Set Up
After unpacking, clean and allow the cabinet to stand for 2 hours before turning on
(cleaning directions supplied within this manual). Ensure the cabinet is situated away from
both hot and cold air sources, as this will affect its performance. Make sure that a minimum
clearance of 10cm around the cabinet is available for ventilation and effective operation.
Install the drip tray underneath the cabinet after placing the unit in position.
Connect the unit to a suitable mains power outlet and turn the supply on. Do not plug or unplug the
unit with wet hands.
Standby
When left for several minutes the cabinet will automatically switch to standby, this helps reduce
energy consumption.
When in standby mode the cabinet will show the middle LED on the main display flashing green
slowly.
During this time the controller is still connected to the mains and standby does not cut off the main
power supply. As a consequence only the compressor and condenser are switched off during this
time.
If the cabinet is going to be unused for a prolonged amount of time than the units power supply
should be switched off and or disconnected from the mains supply.
To exit standby press any button on the keypad and the controller will revert to displaying the
current temperature.
Button 1
Button 2
Button 3
Display 1 LED 4 LED 5
LED 1
LED 2
LED 3
Display 2 LED 7 LED 6
Buttons & Icons
Button 1
Decrease Value/ Information
LED 1
Cycle Indicator ‘ Soft Chill’
Button 2
Select Cycle and Increase Value
LED 2
Cycle Indicator ‘Defrost’
Button 3
Start/Launch Cycle
LED 3
Cycle in Progress
Display 1
Main Temperature
Display 2
Cycle Status Display
Other Visible Indicators:
LED 4
Temperature shown in °C
LED 6
Probe Cycle Mode Active
LED 5
Temperature shown in °F
LED 7
Timer Cycle Mode Active

4 | P a g e
GB
Button Description
Button 1 –Decrease/ Information - This button is used as a decrease button and when pressed
will show the current controller information i.e. time remaining when using a cycle and the current
temperature.
Button 2 –Choice of Cycle & Increase - From here you can select either ‘Soft Chill’ or ‘Defrost’
cycles. By selecting this button the LED for the relevant cycle will illuminate. From this point you can
use button 3 to confirm and launch the selected cycle.
This is also used as an increase button when amending parameter values.
Button 3 –Start/Launch Cycle - This will start a cycle and then the LED’s around this button
(LED 3) will illuminate in a circular chase pattern confirming the action. If pressed and held this
button will also stop a cycle.
Before starting a cycle we advise that you bring the cabinet down to temperature for
optimum performance. Select a Soft Chill Cycle (as described below) but only run this for
15 minutes. To stop after this time press and hold the Start/Launch button until the cycle
stops. Warning ‘rEG’ will show on the display to acknowledge that the cycle didn’t
complete as determined by the parameters, this will clear after selecting your preferred
cycle.
Selecting a Soft Chill
Activate a cycle by pressing the ‘Select Cycle’ button until the ‘Soft Chill’ LED is illuminated. Press
the ‘Start/ Launch Cycle’ button to start the cycle. The cabinet will decide if this cycle should be run
by a probe or timer mode at the start of the cycle (as described below).
Cycle Run Type
After pressing the ‘Start/Launch Cycle’ button and the unit will automatically detect if the cabinet
should run in a ‘Probe’ or ‘Time’ cycle. A ‘Probe’ cycle is determined by the temperature read from
the food probe already inserted in the product at the start of the cycle. The ‘Time’ cycle is
determined if the food probe is not inserted in the product at the start of the cycle. Please Note: If
this button is pressed without selecting either a Soft Chill or Defrost cycle the unit will
continually run on a probe detection cycle until 90 minutes is up and there is no
temperature control with this type of cycle.
Defrost & the Drip Tray
Check no foreign bodies obstruct the waste in the base of the cabinet. The drip tray is situated
underneath the cabinet and should be emptied regularly as water will collect here.
There are two methods of defrost:
> Natural Defrost
Turn the cabinet off at the mains and or stop any cycles. Leave the cabinet door ajar and the
frost will melt and collect in the drip tray.
> Forced Defrost
Press the ‘Select Cycle’ button followed by ‘Defrost Cycle’.
Press the ‘Start/Launch Cycle’ and a defrost will take place showing LED 2 illuminated.
Modifying the End of Cycle Time or Temperature
While the current cycle is running press button 3. You will then be able to use buttons 1 and 2 to
increase or decrease the values.
Stopping a Cycle or Function
It is possible to stop or interrupt a cycle at any time by pressing the ‘Start/Launch’ button and
holding for several seconds. After doing this ‘rEG’ will show on the display to acknowledge that the
cycle didn’t complete as determined by the parameters.
End of Cycle Alarm
At the end of each cycle the audible alarm will sound to notify the user. This can be silenced by
pressing any button on the keyboard.

5 | P a g e
GB
Cabinets have their parameters set at point of build to the correct settings.
If you wish to modify these set points then you should have a full understanding of their
purpose and the following instructions.
To amend any parameter press buttons 1 & 2 together for 5 seconds.
Parameter ‘P01’will be displayed when the menu has been successfully accessed.
To move to the next parameter press button 1 or 2. Once on the parameter you wish to adjust press
and hold button 3 while also using button’s 1 or 2 to modify the pre-set value.
After adjustment has been made release button 3 to save the changes. The menu will automatically
show the next parameter.
If no buttons are pressed for 5 seconds then the controller will leave the adjustment menu.

6 | P a g e
GB
Parameters highlighted in grey are not visible under the Foster standard parameter set up.
Parameter
Description
Range/Parameter Information
Min
Max
Units
All XR
Models
P01
Temperature scale
1=°C
2=°F
1
2
1
P02
Ambient probe calibration
-10
10
°K
0
P03
Skewer probe activation
0=NO
1=YES
0
1
1
P04
Skewer probe calibration
-10
10
°K
0
P05
Action digital entry 1
0=NON
1=DOOR
0
1
0
P06
Polarity Digital Entry 1
0=NO
1=NF
0
1
0
P07
Action Digital Entry 2
0=NON
1=DIG INP
2=EVP
0
2
0
P08
Polarity Digital Entry 2
0=NO
1=NF
0
1
0
P09
Display Digital Entry 2
0=CD
1=HP
0
1
0
P10
Evaporator probe calibration
-10
10
°K
0
P11
Presence of bar graph
0 : No
1 : Yes
0
1
1
P12
Presence of light key
0: No
1: Light key
2: Progression cycle
0
2
1
P13
Type of buzzing sound
0: Frequency 1 (0.5s ON, 0.5s OFF)
1: Frequency 2 (0.35s ON, 0.35s OFF)
2: Frequency 3 (0.25s ON, 0.25s OFF)
0
2
0
P14
Max duration of sound alarm
-1 = Buzzer never stops
-1
99
min
1
P15
Alarm repeated afterwards
-1 = No repeat
-1
99
min
-1
P16
Function Standby
0=NO
1=YES
0
1
1
P17
Standby timer
1
60
min
10
P18
Anti-smell function
0=NO
1=YES
0
1
0
P19
Anti-smell timer
Interval between the start of two functions
1
120
min
60
P20
Anti-smell duration
Duration of function
1
120
min
30

7 | P a g e
GB
P69
Maximum duration of the anti-smell
function
-1
24
hrs.
6
P21
Display slowdown
0
100
0
P22
Machine number
1
255
1
P23
Manual defrost activated
0=NO
1=YES
0
1
1
P24
Interval between 2 defrosting operations
0
99
hrs.
6
P25
Temperature at end of defrost
Evaporator probe
-50
100
°C
10
P26
Max. duration of defrost
1
99
min
30
P27
Type of defrost
0=OFF
1=ELE
2=GAS
0
2
0
P28
Drainage time
0
99
min
3
P29
Check display on defrosting
0
60
min
10
P30
Ventilators activated during defrost
0=NO,
1=YES
0
1
1
P31
Temperature at ventilator switching on
after defrosting
Evaporator probe
-50
100
°C
-5
P32
Ventilators switched off after defrost
0
60
min
0
P33
Defrost at the beginning of cooling cycle
0=NO,
1=YES
0
1
0
P34
Defrost at the beginning of conservation
cycle
0=NO,
1=YES
0
1
0
P35
Defrost delayed at the beginning of
conservation cycle
0
99
min
10
P36
Compressor delayed after switching on
0
30
min
0
P37
Min. time between 2 start-ups of
compressor
0
30
min
1
P38
Minimum standby duration after
compressor is switched off
0
30
min
1
P39
Compressor on with failing probe T1
0
30
min
3
P40
Compressor stopped with failing probe
T1
0
30
min
6
P41
Compressor stop delayed by door
opening
0
30
min
1

8 | P a g e
GB
P42
Choice of cycle by default
0 = Refrigeration. + S.P.
1 = Delayed Refrigeration
2 = Freezing + S.P.
3 = Delayed Freezing
0
3
0
P43
Set point refrigeration conservation
Set point of ambient probe
for conservation
-50
100
°C
3
P44
Selection of soft chill cycle function
activated
0=NO
1=YES
0
1
1
P45
Set point soft chill ambient probe
Set point of ambient probe
during refrigeration cycle
-50
100
°C
-5
P46
Selection of freezing cycle activated
0=NO
1=YES
0
1
0
P47
Set point freezing conservation
Set point of ambient probe
for conservation
-50
100
°C
-21
P48
Regulation differential
1
15
°K
3
P49
Duration of skewer probe presence test
0
99
s
60
P50
Check skewer probe inserted
0
99
°K
5
P51
Duration of pressure on key to switch
off cycle in progress
0
20
s
4
P52
Regulation type
0=FRA
1=UK
2=Specified by user
0
2
1
P53
High refrigeration limit
63°C for FRA
70°C for UK
-50
100
°C
70
P54
Set point of refrigeration cycle
10°C for FRA
03°C for UK
-50
100
°C
3
P55
Max. duration of refrigeration
120min for FRA
90 min for UK
1
180
min
80
P56
High freezing limit
63°C for FRA
70°C for UK
-50
100
°C
70
P57
Set point freezing cycle
-18°C for FRA
-18°C for UK
-50
100
°C
-18
P58
Max. duration of freezing
300 min for FR
270 min for UK
1
400
min
270
P59
Temperature alarm mode
0=NO
1=ABS
2=REL
0
2
0
P60
Low temperature absolute alarm
-50
100
°C
-50

9 | P a g e
GB
P61
High alarm absolute temperature
-50
100
°C
100
P62
Low alarm differential
-12
0
°K
0
P63
High alarm differential
0
12
°K
0
P64
Temperature alarm delayed
0
120
min
60
P65
Door alarm delayed
0
30
min
5
P66
Operation with condenser alarm
0=NO
1=ALR
2=STP
0
2
0
P67
Display with sounding skewer probe.
0=E2
1=UN
0
1
0
P68
Reset
0
1
0

10 | P a g e
GB
XR10 & 20 Models
XR10
XR20
Chilling Capacity per Cycle (Kg)
12
20
Cooling Duty@ -15°C (Watts)
510
920
Number of Fans
1
1
Evaporating Temperature (°C)
-15
-15
Compressor
Hermetic
Hermetic
Gas
R404a
R404a
Gas Charge (Grams)
300
450
Power Consumption (Watts)
600
900
Current Consumption (Amps)
3.1
4.2
Electrical Supply
230/1/50 13A
230/1/50 13A
Total Heat Rejection (Watts)
1514
3052
Maximum Ambient Room Temperature
+43°C
+43°C
(1) - Evacuation of water from defrost 20
(2) - Electric supply cable

11 | P a g e
GB
XR35 Model
XR35
Chilling Capacity per Cycle (Kg)
35
Cooling Duty@ -15°C (Watts)
2080
Number of Fans
1
Evaporating Temperature (°C)
-15
Compressor
Hermetic
Gas
R404a
Gas Charge (Grams)
1400
Power Consumption (Watts)
1600
Current Consumption (Amps)
5.1
Electrical Supply
230/1/50 13A
Total Heat Rejection (Watts)
5120
Maximum Ambient Room Temperature
+43°C
(1) - Evacuation of water from defrost 20
(2) - Electric supply cable

12 | P a g e
GB
Important: Before cleaning or the removal of any parts, the unit should be put into
standby and then the power supply should be turned off at the mains.
Please do not plug or unplug the unit with wet hands. Only when cleaning has been
completed and the unit is dry should the cabinet be turned back on at the mains. Using
high pressure water jets or lances is prohibited; the warranty policy will not cover
problems that result from failure to heed the above warning.
Removing the Unitcover
You should only be required to remove the unitcover for access to the condenser, compressor and or
controller electrics.
Remove both the fixing screws situated at the bottom on the unitcover. Tilt the cover forward and
pull towards you. Refitting is the same action but in reverse ensuring the fixing screws are refit.
XR10 & 20 Models
XR35 Model
Condenser
Controller Electrics
Unitcover
Fixing Screws
Fixing Screws
Unitcover
Controller
Electrics
Condenser Fan Motor/ Plate

13 | P a g e
GB
Cleaning the Condenser
XR10 & XR20 models will clearly see the condenser after removal of the unitcover.
XR35 model will have to also remove the Condenser Fan Plate and motor.
To do this unscrew the two fixing screws positioned on
The top of the condenser fan plate.
Tilt the plate forward on the rubber pivots and
then remove from the unit. You will now be
able to access the condenser for cleaning.
Once the unitcover is removed please do not leave the unit unattended.
Cleaning the condenser should be scheduled every 3 to 6 months and carried out by a service
engineer. Use a soft brush or vacuum cleaner to remove dirt/dust.
If there are any stubborn grease deposits left on or through the condenser call your supplier to carry
out a full service (this is normally chargeable). Failure to maintain the condenser may invalidate the
warranty of the condensing unit and cause premature failure of the motor/compressor. DO NOT use
a wire brush to clean the condenser. Re-fit any panels removed after cleaning.
Access to the Evaporator
After opening the door you will be able to see the evaporator assembly situated at the rear of the
cabinet.
>Firstly, remove all shelves or pans and ladderacking before trying to proceed with the
following instructions.
>To remove the fan and or guard unscrew the guard fixings and pull it towards you.
>To access the reducer valve, evaporator coil and air probe, remove one or more of the
locking screws and then pivot the fan motor baffle on its rubber mounts. This baffle can be
totally removed if required.
Rear of Cabinet/ Birds Eye
View
Evaporator
Coil
Expansion
Valve
Locking
Screw
Racking
Evaporator
Fan
Rubber
Pivot
Air
Probe
Fixing Screws

14 | P a g e
GB
Door Removal
Firstly remove the unitcover (as described before), and
unscrew the pivot screw from the top of the door. You can
now remove the door from the upper hinge bracket.
To refit reverse these instructions and make sure to refit the
spacer washer.
(The unitcover is only visible on this image for illustrative
purposes)
Door Gaskets
Door gaskets should be inspected on a regular basis and replaced if damaged. To clean, wipe with a
warm damp soapy cloth followed by a clean damp cloth. Finally thoroughly dry before closing the
door.
Regular Cabinet Cleaning
As and when required remove all product and shelving (beware of cold and or sharp components)
from the unit. Clean exterior and interior surfaces with mild liquid detergent, following the directions
on the pack at all times. Rinse surfaces with a damp cloth containing clean water. Never use wire
wool, scouring pads/powders or high alkaline cleaning agents i.e. bleaches, acids and chlorines as
these may cause damage. Dry the unit thoroughly before re-using.
Shelves, Pans and Supports
Shelves, Pans and their supports should be removed to clean. The shelves and pans are dishwasher
safe; however the supports should be cleaned with warm soapy water then rinsed and dried.
Pivot
Door
Pivot
Screw
Top Hinge Bracket
& fixing screws

15 | P a g e
GB
Diagram for XR10, 20, 35 Model
SdA : Ambient probe
SdP : Core probe
Cp : Compressor
Vc : Condenser Fan
Ve : Evaporator Fan
Cd : Evaporator Fan Capacitor
Rev : Evaporator Coil Heater (option)
Vo : Anti-smell fan (option)
Model Specific Details :
. without Cd1for model XR10
. without Ve2 for models XR10, XR20 andXR35
Supply 1~230v
Control Board
Front USB Connector
Black
Blue
Blue
Brown
Black
Brown

16 | P a g e
GB
Fault
Cause of Fault
Action /Solution To Rectify
Safety & Utility
cE
>Indicates a communication
problem between the display
PCB and the controller PCB.
>Press any button to acknowledge the warning
& clear the fault
dEF
>Indicates a defrost cycle is in
progress.
rEG
>Indicates that the cycle has
not progressed according to
how the parameters are set.
Function Faults
E1
>Faulty Air Probe.
>Acknowledge the alarm by pressing any key to
silence the audible alarm.
>Check and replace the probe if and where
required.
E2
>Faulty Food Probe –If the
probe is faulty, it is possible to
use the cabinet in ‘Time
Cycle’.
>Acknowledge the alarm by pressing any key to
silence the audible alarm.
>In the case of a faulty food probe it is always
possible to run a cycle in timer mode.
>Check and replace the probe if and where
required.
ELE
>Power Failure –the cycle will
have stopped and a hold cycle
will be active.
>Acknowledge the alarm by pressing any key to
silence the audible alarm.
>If the duration of the power cut is unknown
the regulator will switch to conservation mode
and display rEG.
>If the power was cut during the conservation
cycle the regulator will carry on this mode
when power is resumed.
Corrosion Issues –Listed below are the most common reasons of corrosion on Stainless
Steel. Before reporting any issues of corrosion please ensure the following has been adhered too.
>Floor Cleaner –Splashes of floor cleaner can cause signs of corrosion on the cabinet
base and side panels. This is due to floor chemicals being a lot higher in acidity then
standard stainless cleaner. Also the vapour from these chemicals can hang in the air and
prolong the damage.
>Incorrect Use Of Cleaning Products –Bleaches, acids and soda have a high acidic
content and should be avoided on the cabinet’s internal and external parts. Only stainless
specific products should be used or warm soapy water. Even when using these methods a
clean warm water wipe down should be used to ensure all chemicals have been removed
from the panels. Drying the unit thoroughly can also help.
>Area Where Water/ Chemicals Can Gather –As build-up of product could gather
on/in the cabinet likewise this can also gather in nearby gulley’s, drains etc. Please
ensure these are also run clean of any chemicals.
>High Temperatures - Cleaning solutions can become more aggressive when used with
and in high temperatures. Ensure temperatures do not exceed 60°C thus avoiding
blackening of stainless steel surfaces.
>Salt and Brine - If salt or foods containing a brine is used within the area of the blast
chiller pitting in the stainless could be visible if not cleaned regularly. Any spillage of salt
or brine should be cleaned off the surface first by a soft cloth and then rinsing with warm
soapy & clean water.
>Chlorination –at times water chlorine levels can be high and this can have a corrosive
effect on stainless. Although rare this is a factor that should be made aware of.

17 | P a g e
GB
Before calling your supplier please make sure that:
a) The plug has not come out of the socket and the mains power supply is on i.e. is the
controller illuminated?
b) Check to see if the unit is in standby
c) The fuse has not blown
d) The cabinet is positioned correctly –cold or warm air sources are not affecting the
performance
e) The condenser is neither blocked nor dirty
f) The products are placed in the unit correctly
g) Defrost is not in progress or required
If the reason for the malfunction cannot be identified, disconnect the electrical supply to the unit and
contact your supplier. When requesting a service call, please quote the model and serial number
(a 9 digit number) which can be found on the silver label located on the inside of the unit.

GB

Foster European Operations
France
Foster Refrigerator France SA
Tel: (33) 01 34 30 22 22. Fax: (33) 01 30 37 68 74.
Email: info@foster-fr.com
Germany
Foster Refrigerator Gmbh,
Tel: (49) 781 990 7840. Fax (49) 781 990 7844.
Email: info@foster-gmbh.de
Foster Refrigerator
Oldmedow Road
Kings Lynn
Norfolk
PE30 4JU
Tel: 0843 216 8833
Fax: 0843 216 4707
Website: www.fosterrefrigerator.co.uk
Email: support@foster-uk.com
a Division of ‘ITW (UK) Ltd’
XR10 –XR35/SM 04/14v2 UK
This manual suits for next models
2
Table of contents
Popular Chiller manuals by other brands

AIREDALE
AIREDALE LogiCool LCC20 Technical manual

Master Bilt
Master Bilt MCR-33-101 Specifications

Moffat
Moffat Friginox RR36A Specification sheet

Trane
Trane CenTraVac CDHH Installation, operation and maintenance

SMC Networks
SMC Networks HRS-R Series Operation manual

Nordcap
Nordcap SKF 7 GN 1/1 Installation

Carrier
Carrier HERMETIC CENTRIFUGAL LIQUID CHILLERS 19XR Product data

hailea
hailea HC-100A instruction manual

Daikin
Daikin EWAH TZ D Series Installation, operation and maintenance manual

Quantech
Quantech QWC3 manual

dIXEL
dIXEL XB570L Operating and instruction manual

Solid State Cooling Systems
Solid State Cooling Systems THERMOCUBE 200 product manual