ADPRO Network I/O Units – Technical Manual
33355_00 3
Disclaimer
Thecontentsofthisdocumentareprovidedonan"asis"basis.Norepresentationorwarranty(eitherexpressorimplied)ismadeastothecompleteness,
accuracyorreliabilityofthecontentsofthisdocument.Themanufacturerreservestherighttochangedesignsorspecificationswithoutobligationandwithout
furthernotice.Exceptasotherwiseprovided,allwarranties,expressorimplied,includingwithoutlimitationanyimpliedwarrantiesofmerchantabilityand
fitnessforaparticularpurposeareexpresslyexcluded.
Intellectual Property and Copyright
Thisdocumentincludesregisteredandunregisteredtrademarks.Alltrademarksdisplayedarethetrademarksoftheirrespectiveowners.Youruseofthis
documentdoesnotconstituteorcreatealicenseoranyotherrighttousethenameand/ortrademarkand/orlabel.Thisdocumentissubjecttocopyrightowned
byXtralis.Youagreenottocopy,communicatetothepublic,adapt,distribute,transfer,sell,modify,orpublishanycontentsofthisdocumentwithoutthe
expresspriorwrittenconsentofXtralis.
Trade Name Statement
Xtralis,theXtralislogo,TheSoonerYouKnow,VESDA-E,VESDA,ICAM,ECO,OSID,HeiTel,ADPRO,IntrusionTrace,LoiterTrace,ClientTrace,
SmokeTrace,XOa,XOh,iTrace,iCommand,iRespond,iCommission,iPIR,andFMSTaretrademarksand/orregisteredtrademarksofXtralisand/orits
subsidiariesintheUnitedStatesand/orothercountries.Otherbrandnamesmentionedhereinareforidentificationpurposesonlyandmaybetrademarksof
theirrespectiveholder(s).
General Warning
Thisproductmustonlybeinstalled,configuredandusedstrictlyinaccordancewiththeGeneralTermsandConditions,UserManualandproductdocuments
availablefromXtralis.Allproperhealthandsafetyprecautionsmustbetakenduringtheinstallation,commissioning,andmaintenanceoftheproduct.The
systemshouldnotbeconnectedtoapowersourceuntilallthecomponentshavebeeninstalled.Propersafetyprecautionsmustbetakenduringtestsand
maintenanceoftheproductswhenthesearestillconnectedtothepowersource.Failuretodosoortamperingwiththeelectronicsinsidetheproductscan
resultinanelectricshockcausinginjuryordeathandmaycauseequipmentdamage.Xtralisisnotresponsibleandcannotbeheldaccountableforanyliability
thatmayariseduetoimproperuseoftheequipmentand/orfailuretotakeproperprecautions.OnlypersonstrainedthroughanXtralisaccreditedtrainingcourse
caninstall,testandmaintainthesystem.
Liability
Youagreetoinstall,configure,andusetheproductsstrictlyinaccordancewiththeUserManualandproductdocumentsavailablefromXtralis.
Xtralisisnotliabletoyouoranyotherpersonforincidental,indirect,orconsequentialloss,expenseordamagesofanykindincludingwithoutlimitation,lossof
business,lossofprofits,orlossofdataarisingoutofyouruseoftheproducts.Withoutlimitingthisgeneraldisclaimerthefollowingspecificwarningsand
disclaimersalsoapply:
Fitness for Purpose
Youagreethatyouhavebeenprovidedwithareasonableopportunitytoappraisetheproductsandhavemadeyourownindependentassessmentofthefitness
orsuitabilityoftheproductsforyourpurpose.Youacknowledgethatyouhavenotreliedonanyoralorwritteninformation,representation,oradvicegivenbyor
onbehalfofXtralisoritsrepresentatives.
Total Liability
Tothefullestextentpermittedbylawthatanylimitationorexclusioncannotapply,thetotalliabilityofXtralisinrelationtotheproductsislimitedto:
i. inthecaseofservices,thecostofhavingtheservicessuppliedagain;or
ii. inthecaseofgoods,thelowestcostofreplacingthegoods,acquiringequivalentgoodsorhavingthegoodsrepaired.
Indemnification
YouagreetofullyindemnifyandholdXtralisharmlessforanyclaim,cost,demand,ordamage(includinglegalcostsonafullindemnitybasis)incurredorwhich
maybeincurredarisingfromyouruseoftheproducts.
Miscellaneous
Ifanyprovisionoutlinedaboveisfoundtobeinvalidorunenforceablebyacourtoflaw,suchinvalidityorunenforceabilitywillnotaffecttheremainderwhichwill
continueinfullforceandeffect.Allrightsnotexpresslygrantedarereserved.
Document Conventions
Thefollowingtypographicconventionsareusedinthisdocument:
Convention Description
Bold Usedtodenote:emphasis.
Usedfornamesofmenus,menuoptions,toolbarbuttons…
Italic Usedtodenotereferencestootherpartsofthisdocumentorotherdocuments.Usedfortheresultofanaction.
Thefollowingiconsareusedinthisdocument:
Icon Description
Note.Thisiconindicatesinformationofspecialinterestthatwillhelpthereadermakefulluseoftheproduct,optimiseperformance,etc.Failureto
readthenotewillnotresultinphysicalharmtothereader,ordamagetoequipmentordata.
Caution!Thisiconindicatesdangertoequipment.Thedangercanbelossofdata,physicaldamagetotheequipment,orpermanentcorruptionof
configurationdetails.
Warning!Thisiconindicatesdangerofphysicalharmtothereader.Notfollowinginstructionsmayleadtodeathorpermanentinjury.
Warning!Thisiconindicatesdangerofelectricshock.Thismayleadtodeathorpermanentinjury.

Network I/O Units – Technical Manual ADPRO
4 33355_00
Contact Us
UK and Europe+441442242330 D-A-CH+49431232841 The Americas+17817402223
Middle East +96265885622 Asia+862152400077 Australia and New Zealand+61399367000
www.xtralis.com
Environmental Information
Thecrossed-outwheeledbinmeansthatwithintheEuropeanUniontheproductmustbetakentoseparatecollectionattheproductend
oflife.Thisappliestothedevicebutalsotoanyaccessoriesmarkedwiththissymbol.Donotdisposeoftheseproductsasunsorted
municipalwaste.
Ifyouneedmoreinformationonthecollection,reuse,andrecyclingsystemspleasecontactyourlocalwasteadministration.Youcan
alsocontactusformoreinformationontheenvironmentalspecificationsofourproducts.

ADPRO Network I/O Units – Technical Manual
33355_00 5
Contents
1 About the Network I/O Units 7
1.1 Features 7
1.2 RequirementsforMonitoredInputs 8
1.3 OrderingInformation 8
1.4 PossibleConfigurations 9
1.5 IdentifyingNewUnits 9
1.6 Specifications–BaseUnit 9
1.7 Specifications–ExtensionUnit 10
1.8 LEDIndicators 10
2 Installation 12
2.1 ConnectionsandAdjustments 12
2.2 ReplacingorRemovingaUnit 13
2.3 SettingtheBaseUnitIPAddress 14
2.4 UpdatingtheFirmware 15
2.5 TroubleshootingFirmwareUpdates 16
2.6 InputCircuits 16
3 Frequently Asked Questions 18

Network I/O Units – Technical Manual ADPRO
6 33355_00

ADPRO Network I/O Units – Technical Manual
33355_00 7
1 About the Network I/O Units
Note
YoucanfindthelatestversionsofthisdocumentandanyreferenceddocumentontheXtralisSecurity
SolutionsSupportsitewww.xtralissecurity.com(logonmayberequired).Ifadocumentnumberis
indicated(betweenparentheses),youcanenteritintheKeywordsboxonthesite,andsearchforthe
document.
1.1 Features
TheNetwork(Net)I/OunitsaremoduleswithLEDindicators,contactinputsandrelayoutputs,controlledbyan
ADPRONVR+device.TheNetI/Ounitsarecompatiblewiththefollowingdevicetypes:
lADPROFastTrace2Series:FastTrace2,FastTrace2X,andFastTrace2E
lADPROiFTSeries:iFTandiFT-E
lADPROiFTGateway
lADPROV31001.
ThehostsystemcontrolstheNetI/OunitsthroughtheEthernetnetwork(10Mbpsnetworkonly).
Thebaseunitoffers:
l4monitoredorunmonitoredinputsforvoltage-freecontacts.Thepossiblestatesare:
oidle
oalarm
otampershortcircuit(monitoredinputsonly)
otamperopencircuit(monitoredinputsonly).
l4relayoutputs(voltage-freeswitchovercontacts)withstatusLED.
l3LEDindicatorsforthesystemstatusofthecontrollingADPRONVR+device:
ored=recording
oyellow=fault
ogreen=powersupply.
Thebaseunitis:
lmountedonaDINrail
lextendiblewithonetothreeextensionunits.Extensionunitsarepoweredfromthebaseunit.Eachextension
unitoffers:
o4monitoredorunmonitoredinputs
o4relayoutputs.
lpoweredbyalocaladapter(12VDC;min.350mA)orbyaPoE2switchorinjector.
Baseunit: Extensionunit:
1OntheV3100,theinputsalwaysfunctionasunmonitoredinputs;monitoredinputsarenotpossible.
2PoE=PoweroverEthernet

Network I/O Units – Technical Manual ADPRO
8 33355_00
AsyoucanlinkyourADPRONVR+devicetoupto8units(8baseunits,eachwithupto3extensionunits),you
canobtainatotalof128extrainputsand128extraoutputs.
1.2 Requirements for Monitored Inputs
MonitoredinputsareonlyavailableonthenewNetI/Ounits.TouseaNetI/Ounitwithmonitored inputs,all the
requirements listedbelowmustbefulfilled:
lForabaseunit:
oThebaseunithardwaremustbeversion2(V2).
oThebaseunitfirmwaremustbeversion2(V2).
oTheADPRONVR+devicecontrollingtheunitmustberunningfirmwareversionXO4.02orabove.
lForanextensionunit:
otheextensionunithardwaremustbeversion2(V2).
oitsbaseunitmustfulfiltherequirementsaslistedabove.
Ifanyoftheaboverequirementsisnotfulfilled,theunitswillfunctionasthelegacyunits,withunmonitoredinputs
(only2states:idle/alarm).Thenewunitsarebackwardscompatiblewiththelegacyunits.
Fordetailsonidentifyingneworlegacyunits,seeIdentifying New Unitsonpage9.
Foranoverviewofallpossiblecombinationsofnewandlegacyunits,seePossible Configurationsonpage9.
1.3 Ordering Information
UsethesereferencenumberstoplaceyourorderwithXtralis:
Item Reference number
Baseunit 49841000
Extensionunit 49841010

ADPRO Network I/O Units – Technical Manual
33355_00 9
1.4 Possible Configurations
Thetablebelowprovidesanoverviewofallpossiblecombinationsofnewandlegacyunits(baseandextension),
andtheresultingpossibilitiesfortheinputs(monitoredorunmonitored):
Base unit Behaviour inputs on base
unit Extension unit Behaviour inputs on
extension unit
HardwareV1
FirmwareV1orV2 Unmonitored(2states) HardwareV1orV2 Unmonitored(2states)
HardwareV2
FirmwareV1 Unmonitored(2states) HardwareV1orV2 Unmonitored(2states)
HardwareV2
FirmwareV2
XOversion<4.02
Unmonitored(2states) HardwareV1orV2 Unmonitored(2states)
HardwareV2
FirmwareV2
XOversion≥4.02
Monitored(4states) HardwareV1 Unmonitored(2states)*
Monitored(4states) HardwareV2 Monitored(4states)
(*)Inthiscase,configureallinputsoftheextensionunitsasNEOL.Fordetails,seeInput Circuitsonpage16.
1.5 Identifying New Units
Youcaneasilyidentifythenewunits.Thelabelsforthenewunits(onthepackagingandontheunititself)
indicatethenewhardwareandfirmwareversions(=V2).Thelegacyunitsdonothavetheselabels.Beloware
examplesofnewlabels:
A=indicatesversion2hardware.
B=indicatesversion2firmware(firmwareresidesonbaseunitonly).
1.6 Specifications – Base Unit
Powersupply Usea12VDC/350mA(min.)adapterorPoEswitch/injector
Voltage 12VDC±10%
Current 190mAmax.(allLEDsandrelaysactivated)
140mA(allrelaysoff)
Inputs 4monitoredorunmonitoredinputsforvoltage-freecontacts:idle,alarm,
tampershortcircuit,tamperopencircuit(tamperstatesonlyonmonitored
inputs)
Outputs 4switchoverrelaycontacts:NC/C/NO,rated30VDC@1A
Dimensions 72mmx89.7mmx62.2mm
Operatingtemperature 0–40°C
Relativehumidity 20–93%(non-condensing)

Network I/O Units – Technical Manual ADPRO
10 33355_00
Jumpers SW1:shortedtemporarilytoreset(internaluse,default=open)
SW2/SW4:default=open.
LEDs D9:on=videosystemispowered
D11:on=videosysteminerrorstate
D10:on=videosystemiscurrentlyrecording
D18:on=relayK1activated
D19:on=relayK2activated
D20:on=relayK3activated
D21:on=relayK4activated
1.7 Specifications – Extension Unit
Powersupply Poweredbybaseunit
Voltage 12VDC±10%
Current 50mAmax.(allLEDsandrelaysactivated)
10mA(allrelaysoff)
Inputs 4monitoredorunmonitoredinputsforvoltage-freecontacts:idle,alarm,
tampershortcircuit,tamperopencircuit(tamperstatesonlyonmonitored
inputs)
Outputs 4switchoverrelaycontacts:NC/C/NO,rated30VDC@1A
Dimensions 54mmx89.7mmx62.2mm
Operatingtemperature 0–40°C
Relativehumidity 20–93%(non-condensing)
LEDs D18:on=relayK1activated
D19:on=relayK2activated
D20:on=relayK3activated
D21:on=relayK4activated
Theextensionunitissettoanaddressfrom0to2usingDIP1.(Address3isnotsupportedbythesoftware.)For
details,seeInstallationonpage12.
1.8 LED Indicators
ThefollowingLEDindicatorsareavailableontheNetI/Ounits:
LED Description
GreenLED(onbaseunitonly):indicatesthatthecontrollingADPRONVR+deviceispoweredon.
YellowLED(onbaseunitonly):indicatesafaultonthecontrollingADPRONVR+device.Ifthe
yellowLEDlightsup,checkthestatusofyourADPRONVR+device.Formoreinformation,seethe
XO Client Software User Manual(21796).
RedLED(onbaseunitonly):correspondswiththeblueLEDonthecontrollingADPRO
NVR+device.Indicatesstoragemediaactivityonthedevice(recording).
1 Indicatesthatoutputrelay1ontheunitisactivated.
2 Indicatesthatoutputrelay2ontheunitisactivated.
3 Indicatesthatoutputrelay3ontheunitisactivated.
4 Indicatesthatoutputrelay4ontheunitisactivated.

ADPRO Network I/O Units – Technical Manual
33355_00 11
Note
ThethreesystemLEDs(power,fault,andrecording)areonsimultaneouslywhentheunit'sIP
addressisstillatthedefaultsetting.

Network I/O Units – Technical Manual ADPRO
12 33355_00
2 Installation
2.1 Connections and Adjustments
Caution!
Before plugging or unplugging any extension units, switch off the power to the base unit.
Pluggingorunpluggingextensionunitswithpoweronmayresultinpermanent and irreparable
damage tothebaseand/orextensionunits.
Thetablebelowprovidesanoverviewoftheconnectors.

ADPRO Network I/O Units – Technical Manual
33355_00 13
Connector Description
IP(baseunitonly) UseanEthernetcabletoconnectthebaseunittotheIPnetwork,and(optionally)to
powertheunitoverEthernet(PoE).
IfusingPoE,fixtheincludedclampontheEthernetcableinsidethemountingbox.
PlacetheclampascloseaspossibletotheNetI/Ounit.
12V(baseunitonly) Optional:ifyouareusingalocalpoweradapterinsteadofPoE,connecttheDCpower
wirestothe0Vand+terminals.Respectthepolarity!
Ifusingalocalpoweradapter,fixtheincludedclamponthepowersupplyinput.Make
oneloopinsidetheclamp.
IN 1–4 Inputs.EachinputhasitsownGND(0V).Theinputsfunctionasmonitoredinputs
(4states),dependingonhardware,firmware,andADPRONVR+firmwareversion.For
details,seeRequirements for Monitored Inputsonpage8.
OUT 1–4 Voltage-freeswitchoverrelaycontactoutputs.Eachoutputhasacommonterminal(C)
andanormalopen(NO)andnormalclosed(NC)terminal.
DIP1 (extension
unitsonly)
DIPswitchtosettheextensionunitaddressfrom0to2(address3isnotsupportedin
theADPRONVR+software)asindicatedinthetablebelow.Theswitchforthemost
significantbit(MSB)islocatedaway from the edge oftheunit.
To set address Set switch
MSB Other
0 OFF OFF
1 OFF ON
2 ON OFF
Caution!
Youcanmounttheunitsinaplasticormetalbox.Ifmountinginametalbox:makesurethatthemetal
boxisearthed,andconnectthe0Vpowerinputterminalofthebaseunittotheearth.
2.2 Replacing or Removing a Unit
Caution!
Before plugging or unplugging any extension units, switch off the power to the base unit.
Pluggingorunpluggingextensionunitswithpoweronmayresultinpermanent and irreparable
damage tothebaseand/orextensionunits.

Network I/O Units – Technical Manual ADPRO
14 33355_00
Itmay,forexample,damageinput/output1(relaypermanentlyactive)andsendincorrectsignalstotheADPRO
NVR+device.
Proceedasfollowsbeforepluggingorunpluggingextensionunits:
lIfthebaseunitispoweredviaalocalpoweradapter:unplug the power adapter fromthebaseunit.
lIfthebaseunitispoweredviaPoE:unplug the network (Ethernet) cable fromthebaseunit.
Afterpluggingorunpluggingtheextensionunits,plugthepoweradapterornetworkcablebackin.
2.3 Setting the Base Unit IP Address
ThedefaultIPaddressofthebaseunitis192.168.1.100withsubnetmask255.255.255.0.Thethreesystem
LEDsonthebaseunitwilllightupsimultaneouslyiftheunitisstillsetatthedefaultaddress.
TheextensionunitsdonothaveanIPaddress.Youassignthemanaddress(orsequencenumber)usingtheDIP
switchontheunit.Fordetails,seeConnections and Adjustmentsonpage12.
UsetheNetFindertooltolocateallbaseunitsonyournetworkandsettheirIPaddresses.Youcanfindthe
NetFindertoolontheDVDthatcomeswithyourADPRONVR+device,orontheXtralisSecuritysite
www.xtralissecurity.com.
Caution!
NetFinderwillnotdetectunitsbehindarouter.MakesurethatyourPCandtheunitsareinthesame
IPnetworksegment.
TosetthebaseunitIPaddress,proceedasfollows:
1. StartNetFinderonyourPC.
2. ClickSearch.
NetFinderwillindicatetheNetI/Ounitsingreen.Theunit'sfirmwareversionisindicatedbetween
parentheses.

ADPRO Network I/O Units – Technical Manual
33355_00 15
3. Clickthedesiredunit,andthenclickAssign.
4. TypetheIPaddress,thesubnetmaskandthegateway,andthenclickOK.
Theunitstoresthesettingsinitsflashmemory.
2.4 Updating the Firmware
UsetheNetFindertooltoupdatethefirmwareonabaseunit.TheunitwillpreserveitsIPaddress,subnetmask,
andgatewaysettingsduringanupdate.
Thereisnofirmwareontheextensionunits.
Caution!
NetFinderwillnotdetectunitsbehindarouter.MakesurethatyourPCandtheunitsareinthesame
IPnetworksegment.ThefirmwareupdateusestheTrivialFileTransferProtocol(TFTP).Makesureit
isenabledonyourPC.Forinstructions,seeTroubleshooting Firmware Updatesonpage16.
Toupdatethebaseunitfirmware,proceedasfollows:
1. StartNetFinderonyourPC.
2. ClickSearch.
NetFinderwillindicatetheNetI/Ounitsingreen.
3. Clickthedesiredunit,andthenclickReboot.
4. SelecttheForce bootload mode option,andthenclickOK.
Ifsuccessful,themessageSuccess – Device rebooted willappear.
Theunitisnowdisabledandgoesinrebootmode.
5. ClickOK toclosethewindow.,andthenclickSearch toupdatethelistofdevicesinNetFinder.Theunitin
rebootmodewillappearinyellow(andwithnameHydraIO).
6. Clickthedesiredunit,andthenclickUpdate.

Network I/O Units – Technical Manual ADPRO
16 33355_00
7. Selectthefirmwarefile(.img),andthenclickOpen.
Thesystemwillnowupgradetheunit'sfirmware.Whensuccessful,themessageTransfer successful will
appearintheWindowsCommandscreen.
2.5 Troubleshooting Firmware Updates
Ifupdatingthefirmwarefails,thencheckifTFTPisactiveinyouroperatingsystem,andcheckthenetwork
settings.
TFTP not active or blocked by firewall
NetFinderusesTFTP(TrivialFileTransferProtocol)toupdatethebaseunit'sfirmware.Youmayneedtoenable
TFTPinyourWindowsoperatingsystem.
Also,checkifyourfirewallisnotblockingtheTFTPapplication.
ToenableTFTPinWindows,proceedasfollows:
1. ChooseStart >Control Panel>Programs and Features.
2. ClickTurn Windows features on or off.
3. InthelistofWindowsfeatures,selecttheTFTP Client checkbox.
4. ClickOK.
Network issue
Forupdatingthefirmware,thePCthathasNetFinderinstalledandthebaseunitmustbeinthesamenetwork
segment.ThePCneedstoconnecttothebaseunit,butthebaseunitalsoneedstocommunicatebacktothe
PC.Ifupdatingthefirmwarefails,thenchecktheIPaddressandsubnetmaskofbothPCandbaseunit.
Forexample:thePCwithNetFinderhasIPaddress10.0.0.3andsubnetmask255.255.0.0.
ThebaseunithasIPaddress10.0.2.10andsubnetmask255.255.255.0.
ThePCcanconnecttothebaseunit,becauseitcanconnecttoanydevicewithIPaddressinthe10.0.x.xrange.
However,thebaseunitcannotconnecttothePC,asitcanonlyreachthe10.0.2.xrange.Inthiscase,the
firmwareupdatewillfail.
Tosolvetheissue:useNetFindertomodifythesubnetmaskofthebaseunit(inthiscaseto255.255.0.0),and
thenrunthefirmwareupgradeagain.
2.6 Input Circuits
BelowaretheNEOL,SEOL,andDEOLconfigurationsfortheinputs.UseSEOLandDEOLwithmonitored
inputsonly.
Forcorrectoperation,youalsohavetoindicatetheusedinputcircuitconfigurationintheXOclientsoftware.For
moreinformation,seetheXO Client Software User Manual(21796).

ADPRO Network I/O Units – Technical Manual
33355_00 17
Normallyopen–NEOL
Shortcircuit=alarm
Opencircuit=idle
(Defaultsetting)
Normallyopen–SEOL
Shortcircuit=alarm
1K1=idle
Opencircuit=tamper
Normallyclosed–NEOL
Shortcircuit=idle
Opencircuit=alarm
Normallyclosed–SEOL
Shortcircuit=tamper
1K1=idle
Opencircuit=alarm
Normallyopen–DEOL
Shortcircuit=tamper
1K1=alarm
3K3=idle
Opencircuit=tamper
Normallyclosed–DEOL
Shortcircuit=tamper
1K1=idle
3K3=alarm
Opencircuit=tamper

Network I/O Units – Technical Manual ADPRO
18 33355_00
3 Frequently Asked Questions
Can I upgrade legacy Net I/O units so they provide monitored inputs?
No.Theonlyunitsthatcanprovidemonitoredinputsarethenewunitswiththenewhardware.
Can I replace a legacy Net I/O unit by a new one?
Yes.Youcanjustswaptheunits.Makesuretoswitchoffpowerbeforeswapping.
Afterswapping,checktheunit'sconfigurationintheXOclient:makesuretheinputs/outputsareconfiguredas
before.IfusingXOversion4.02orabove,checkthatallinputsaresettoNEOL.Testifthenewunitfunctions
exactlyliketheoldone.
Can I install the new firmware V2 on a legacy base unit?
Yes,butitisnotrecommended.Althoughthenewfirmwareiscompatiblewiththelegacyunits,itdoesnot
changetheunit'sfunctionality:theinputsonthelegacyunitcanonlybeusedasunmonitoredinputslikebefore.
Also,theinputsonanyconnectedextensionunits(evennewones)canonlybeusedasunmonitoredinputsifthe
baseunithastheoldhardware.
Can I use a Net I/O unit with monitored inputs with a V3100 device?
No,monitoredinputsarenotavailableonV3100devices.MonitoredinputsrequirefirmwareversionXO4.02(or
above),whichisnotcompatiblewiththeV3100devices.
However,youcanusethenewNetI/OunitswiththeV3100device,buttheinputswillfunctionasunmonitored
inputsonly.
I have a spare, legacy Net I/O unit available. Can I use it to replace a faulty, new Net I/O unit with
monitored inputs?
No.Thelegacyunitsdonotsupportmonitoredinputs.Ifyoureplaceanewunit(baseorextension)with
monitoredinputsbyalegacyunit,thesystemresponse(statusidle,alarm,ortamperalarm)willbeincorrect.
Thetablebelowindicatestheexpectedstatusandtheactualresultifyoureplaceanewunitwithmonitored
inputsbyalegacyunitwithunmonitoredinputs.
End of line config Expected status Event in XO
SEOLNormalopen 1k1=idle Alarm
closedcontact/shortcircuit=alarm Alarm
opencircuit=tamper Tamper
SEOLNormalclosed 1k1=idle Tamper
opencontact/opencircuit=alarm Alarm
shortcircuit=tamper Tamper
DEOLNormalopen 3k3=idle Tamper
1k1=alarm Tamper
opencircuit=tamper Tamper
shortcircuit=tamper Tamper
DEOLNormalclosed 1k1=idle Tamper
3k3=alarm Tamper
opencircuit=tamper Tamper
shortcircuit=tamper Tamper
Caution!
Goodpracticedictatesthatyoucheckidlefunctionalityafterrepair.


www.xtralis.com
UK and Europe+441442242330 D-A-CH+49431232841 The Americas+17817402223
Middle East +96265885622 Asia+862152400077 Australia and New Zealand+61399367000
A Disclaimer about this document, statements about Intellectual Property, Copyrights, and Liability, as well as a General
Warning are available in an earlier section of this document.
DocumentNo:33355_00
This manual suits for next models
1
Table of contents
Popular I/O System manuals by other brands

Siemens
Siemens SIMATIC ET 200SP Product information

Power Electronics
Power Electronics SD 300 Series Getting started manual

SMC Networks
SMC Networks 56-EX600-SEN7-X10 instruction manual

VIA Technologies
VIA Technologies EMIO-3430 quick guide

ATEN
ATEN VM7584 quick start guide

Extron electronics
Extron electronics TLP VIM user guide

Acromag
Acromag Acropack AP440 Series user manual

Solartron
Solartron Digital Input/Output Module manual

LoRa Alliance
LoRa Alliance YO Analog Quick installation guide

Siemens
Siemens Simatic S7-1500 Function manual

HIMA
HIMA HIMax X-AI 16 51 manual

Allen-Bradley
Allen-Bradley 1769-ECL installation instructions