TRANSDUCER
DIGITAL INPUT 4, PROGRAMMABLE. DEFAULT = SET POINT SELECTION
DIGITAL INPUT 3, PROGRAMMABLE. DEFAULT = E-STOP OR JUMPER
ANALOG OUTPUT, COMMON. (CONNECTED INTERNALLY TO CHASSIS
THROUGH 1MΩ)
ANALOG OUTPUT, PROGRAMMABLE. DEFAULT = NOT USED. CURRENT
0-20mA (LOAD<500Ω)
DIGITAL INPUT COMMON. TO ACTIVATE A DIGITAL INPUT, THERE MUST BE
>= +10V (OR =< -10V) BETWEEN THE INPUT AND DCOM. THE 24V MAY BE
PROVIDED BY THE AQUAVAR (X1-10 OR BY AN EXTERNAL 12-24V SOURCE
OF EITHER POLARITY.
AUXILIARY VOLTAGE OUPUT COMMON (CONNECTED INTERNALLY AS
FLOATING)
AUXILIARY VOLTAGE OUTPUT 24VDC/250mA (REFERNCE TO GND). SHORT
CIRCUIT PROTECTED. TRANSDUCER/DIGITAL INPUT POWER SUPPLY.
ANALOG OUTPUT, PROGRAMMABLE. DEFAULT = NOT USED. CURRENT
0-20mA (LOAD<500Ω)
ANALOG INPUT CHANNEL 2. RESOLUTION 0.1%, ACCURACY ± 1%.
10V/1mA REFERENCE VOLTAGE OUTPUT FOR ANALOG INPUT
POTENTIOMETER, ACCURACY ±2%. (NOT USED.)
ANALOG INPUT CIRCUIT COMMON. (CONNECTED INTERNALLY TO
CHASSIS GROUND THROUGH 1MW. JUMPER WIRE TO X1-11.)
ANALOG INPUT CHANNEL 1, 2ND TRANSDUCER. DEFAULT2=FREQUENCY
REFERENCE.
RELAY OUTPUT 1, PROGRAMMABLE. DEFAULT = RUN
POWER TO DRIVE
MAXIMUM: 250VAC / 30VDC, 2A
MINIMUM: 500mW (12V, 10mA)
RELAY OUTPUT 3, PROGRAMMABLE. DEFAULT = RUN
POWER TO DRIVE
MAXIMUM: 250VAC / 30VDC, 2A
MINIMUM: 500mW (12V, 10mA)
RELAY OUTPUT 2, PROGRAMMABLE. DEFAULT = RUN
POWER TO DRIVE
MAXIMUM: 250VAC / 30VDC, 2A
MINIMUM: 500mW (12V, 10mA)
RELAY OUTPUTS
ON
J1:AI1 ON: 0...20mA (Ri=100K Ω)
DIGITAL INPUT 6, PROGRAMMABLE. DEFAULT = NOT USED
DIGITAL INPUT 5, PROGRAMMABLE. DEFAULT = HOA (GROUP 12)
DIGITAL INPUT 2, PROGRAMMABLE. DEFAULT = LOW WATER
DIGITAL INPUT 1, PROGRAMMABLE. DEFAULT = RUN ENABLE
ANALOG INPUT CIRCUIT COMMON. (CONNECTED
INTERNALLY TO CHASSIS GND. THROUGH 1 M Ω.
J1:AI1 OFF: 0...10V (Ri=312K Ω)
J1:AI1 ON: 0...20mA (Ri=100K Ω)
DIGITAL OUTPUTS ANALOG I/O
ON
ON
J1:AI1 OFF: 0...10V (Ri=312K Ω)
TERMINAL FOR TRANSDUCER SHIELD. (CONNECTED
INTERNALLY TO CHASSIS GROUND)
ON
RO1A
RO3C
RO3B
RO3A
RO2C
RO2A
RO2B
RO1B
29
ONON
28
25
27
26
3130 32
ON
J2
ON
26
25
27
323028 29 31
GROUND
(SHIELD)
GND
+ 24V
DCOM
RO1C
DI1
DI2
DI3
DI5
DI6
DI4
AGND
+ 10V
AGND
AO1
AO2
AGND
AI2
14
22
24
23
21
20
19
15
16
17
18
WHITE
[OR BLACK]
10
11
12
13
9
8
7
6
5
4
3
BROWN
[OR RED]
SCR
AI1
ON
AI2
AI1
ON
2
1
VFD 1
GROUND
(SHIELD)
14
21
20
23
24
22
15
17
16
18
19
TRANSDUCER
(MOUNTED ON
DISCHARGE
MANIFOLD)
9
10
12
11
13
3
4
5
7
8
6
BROWN
[OR RED]
WHITE
[OR BLACK]
AI1
AI2
2
1
ON
ON
VFD 2
J5
J4
J3
J2
J1
J5
J4
J3
J2
J1
CUSTOMER SUPPLIED SERVICE RATED
SERVICE DISCONNECT
(CUSTOMER RESPONSIBLE FOR WIRE
AND CONDUIT SIZES BETWEEN
CUSTOMER DISCONNECT, AND CONTROL
PANEL, BASED ON STATION FULL LOAD
AMPS AND NEC CODE)
A
PE
PE
U2
"C"
V2 W2 U2 W2
V2
U1
PE
"F"
PE
"E"
V1 W1
"F"
U1 W1V1
"C"
"K" "K"
NOTES:
1. CONDUIT AND WIRE SIZES SHOWN ARE MINIMUM REQUIRED;
LARGER SIZES MAY BE SUBSTITUTED IF CONDUIT SIZE PERMITS.
2. USE 90° C WIRE FOR MOTOR WIRE RUNS; INCLUDE TAG READING
"MOTOR WIRE TO BE NO LESS THAN 90° C RATED".
3. INCLUDE TAG READING "TORQUE SCREWS TO 6-14 LB-IN, USE
COPPER WIRE ONLY" ON CONTROL INTERFACE WIRING.
4. CUSTOMER RESPONSIBLE FOR WIRE AND CONDUIT SIZES
BETWEEN CUSTOMER DISCONNECT, AND CONTROL PANEL,
BASED ON STATION FULL LOAD AMPS AND NEC CODE.
5. STATION MEETS 5kA SCCR RATING ONLY IF CUSTOMER SUPPLY
THE FOLLOW SUPPLY FUSES OR EQUIVALENT CIRCUIT BREAKER
CLASS RK1, J, T - 400 A MAX.
CLASS RK5 - 200 A MAX
CLASS G - 60 A MAX
CLASS CC - 30 A MAX
"J
"E"
"J"
"E"
"D"
"E"
"D"
BC
JUMPER POSITION
IF MIDDLE DRIVE(S)
J2 JUMPER MAY BE
SHOWN AS
SEPERATE J2, J5
OR AS A SINGLE
LARGE J2
JUMPER POSITION IF FIRST OR
LAST (TERMINATING) DRIVES
J2
ON ON
ON ON
J2J2 J5
OR
ON ON ON
J2
A
SCREEN
AGND
SCREEN
B
RS485 MULTIPLE DRIVE
CONNECTIONS
J2
10 (+24)
VFD 1
VFD TERMINALS
14 (DI2)
14 (DI2)
VFD 2
VFD 1
VFD TERMINALS
UE H5425 (SUCTION PRESS.-10PSI)
CUSTOMER INSTALLED PRESSURE SWITCH
P/N: 77-001-135
N.O.
N.C.
COM.
3ɸ ONLY
"H"
"H"
SIMPLEX
DUPLEX
SIMPLEX
DUPLEX
"I"
REVISION HISTORY
REV DESCRIPTION REV BY DATE
1UPDATED DISCONNCET SIZES, WIRE SIZES AND FUSE SIZES. M. MARTINEZ FEB-08-2011
2UPDATED FUSES MODEL NUMBERS & P/N'S (SEE COLUMN H). LNT FEB-15-2011
3UPDATED NOTES AND CHARTS. M. MARTINEZ MAR-08-2011
4UPDATE POWER REQUIREMENTS CHART PER UL508A M. REYES 1/19/2012
5CHANGE BORDER TO XYLEM MP 10/12/2012
6CORRECT DUPLEX STATION FLA 21.2/19.2 FOR 3HP,208V/3Ø/60HZ DTT 1/5/2014
7UPDATED LIP INFORMATION DTT 4/27/2015
8ECN2017-0006, ADD 5HP, 208V/1 Ø/60HZ; UPDATED VFD 1.5HP,208-230V/3 Ø/60HZ DTT 1/26/2017
10661 NEWKIRK STREET
DALLAS, TX 75220
800.786.7480
SHEET:
DATE:
DRN: DATE:
CHK:
DRAWING #:
REV
DRAWING NAME:
SIZE
THIS DRAWING AND THE INFORMATION DEPICTED THEREIN IS THE
PROPERTY OF XYLEM. COPIES ARE ISSUED IN STRICT CONFIDENCE
AND SHALL NOT BE REPRODUCED OR COPIED, OR USED AS THE
BASIS FOR THE MANUFACTURE OR SALE OF PRODUCTS WITHOUT
PRIOR WRITTEN PERMISSION OF XYLEM. OF
PROJECT #:
M MARTINEZ 02/02/2011
VN 02/07/0211
11033-01
VALUE BOOSTER
CPC DRIVES
B8 1 1
BOOSTER
208V-230V/1ɸ
ACD E FHJK
HP GROUND
WIRE
VFD/MOTOR
WIRE
VFD/MOTOR
CONDUIT
VFD FUSES FUSE
WIRE
VFD GND
WIRE
FPSI MODEL FRAME MODEL P/N
1 1/2 14 AWG
14 AWG 1/2"
FG-CPC20121
R1
HJS15 43-011-015 12 AWG 14 AWG
2
10 AWG
FG-CPC20171 HJS25 43-011-025 10 AWG
3FG-CPC20241 HJS30 43-011-030 10 AWG
510 AWG FG-CPC20311 R2 HJS40 43-011-040 8 AWG 10 AWG