4
The set will now continuously run, when pressure has been raised to the duty point and the flow switch has
registered no flow is taking place, the on demand indicator will be extinguished and the pump set can be
stopped by pressing the stop button on the control panel.
If the set point has not been satisfied or flow is taking place then the on demand indicator will be illuminated
and the stop button will have no effect and the pump will continue to run.
To stop the pump set after use, close the discharge valve and the pressure will rise and flow will cease, press
the stop button and the set will stop. Replace the ruptured sprinkler head/s and open the set discharge valve
to bring the set back into operation.
In the advent of water failure where the pump will not be able to make pressure the main power supply should
be isolated until the water supply has been reinstated.
General alarm contact
When the pump set starts, or a fault occurs the internal audible alarm will sound at the set, a failsafe alarm
volt free contact will close to indicate to a remote monitoring device (not supplied) that the pump set has
started or a problem has occurred. This contact will also operate under power failed conditions.
Flow alarm contact
When the pump set starts and flow takes place (indicating a real usage is taking place) the internal audible
alarm will sound at the set and a volt free contact will close, this contact can be used to activate the evacua-
tion alarm circuit (Not supplied).
Pump protection
The pump is protected against short circuit only I.E. fused supply. In the advent of overload the pump will
continue to run until destruction.
Indication
The control panel fascia is fitted with LED indicators for Power on (Green), Pump set on demand (Red) and
pump test failed (red).
Pump test automatic and manual
The pump test time can be set for either 4,7,14,21 or 28 day intervals. The pump will be started and run for
approximately 5 seconds, a pressure switch mounted directly on the pump discharge manifold before the non
return valve will monitor the pump to ensure that the pump has developed pressure within the allotted time.
This will also replenish any loses from the vessel. The volt free alarm contacts and internal alarm sounder will
not operate under successful test operation.
Pump test failure
If the pump fails to make pressure during the test operation then the general alarm volt free contact will oper-
ate, the internal audible alarm will sound and the test failed LED will be illuminated to signal pump failure. The
power supply should be isolated and the fault should be investigated and rectified, the alarm condition will be
reset when the power supply is reinstated.
The above test can be carried out manually at any time by pressing the test button.
Automatic re-pressurisation mode
When this option is selected the pump set will automatically start when pressure falls, and providing flow is
not taking place will re-pressurise the system and automatically stop. The general alarm contact will operate
to show that the set has started and reset when the set stops. The audible alarm will not operate under this
condition.
This option is useful when small losses due to pipe work leakage are difficult to find/repair.