YASKAWA VIPA PBR Series User manual

PBR | 920-1CA50 | Manual
HB153 | PBR | 920-1CA50 | en | 19-09
VIPA Networking Solutions
PROFIBUS MultiRepeater A5
www.vipa.com/en/service-support/manuals

920-1CA50_000_PBMR-A5,4,GB - © 2019
VIPA GmbH
Ohmstr. 4
91074 Herzogenaurach
Telephone: +49 9132 744-0
Fax: +49 9132 744-1864
Email: [email protected]
Internet: www.vipa.com

Table of contents
1 General.................................................................................................................... 4
1.1 Copyright © VIPA GmbH ................................................................................. 4
1.2 About this manual............................................................................................. 5
1.3 Safety information............................................................................................. 5
2 Product Description............................................................................................... 7
2.1 General............................................................................................................. 7
2.2 Product features............................................................................................... 8
2.3 Application areas.............................................................................................. 9
2.4 Additional Benefits............................................................................................ 9
2.5 Channel Structure............................................................................................. 9
2.6 Grounding System.......................................................................................... 10
2.7 Cable lengths for PROFIBUS DP................................................................... 10
2.8 Cable types for PROFIBUS DP...................................................................... 11
2.9 Status display................................................................................................. 12
3 Installation Instructions....................................................................................... 13
3.1 Location.......................................................................................................... 13
3.2 Position........................................................................................................... 13
3.3 Mounting......................................................................................................... 13
3.4 Power Supply................................................................................................. 14
3.5 Backbone........................................................................................................ 14
3.6 Spur Segments............................................................................................... 16
3.7 Termination..................................................................................................... 16
3.8 Baudrate switch.............................................................................................. 17
4 Technical data ...................................................................................................... 18
5 Glossary................................................................................................................ 20
VIPA Networking Solutions Table of contents
HB153 | PBR | 920-1CA50 | en | 19-09 3

1 General
1.1 Copyright © VIPA GmbH
This document contains proprietary information of VIPA and is not to be disclosed or used
except in accordance with applicable agreements.
This material is protected by the copyright laws. It may not be reproduced, distributed, or
altered in any fashion by any entity (either internal or external to VIPA), except in accord-
ance with applicable agreements, contracts or licensing, without the express written con-
sent of VIPA and the business management owner of the material.
For permission to reproduce or distribute, please contact: VIPA, Gesellschaft für Visuali-
sierung und Prozessautomatisierung mbH Ohmstraße 4, D-91074 Herzogenaurach, Ger-
many
Tel.: +49 9132 744 -0
Fax.: +49 9132 744-1864
EMail: [email protected]
http://www.vipa.com
Every effort has been made to ensure that the information contained in
this document was complete and accurate at the time of publishing. Nev-
ertheless, the authors retain the right to modify the information.
This customer document describes all the hardware units and functions
known at the present time. Descriptions may be included for units which
are not present at the customer site. The exact scope of delivery is
described in the respective purchase contract.
Hereby, VIPA GmbH declares that the products and systems are in compliance with the
essential requirements and other relevant provisions. Conformity is indicated by the CE
marking affixed to the product.
For more information regarding CE marking and Declaration of Conformity (DoC), please
contact your local VIPA customer service organization.
VIPA, SLIO, System 100V, System 200V, System 300V, System 300S, System 400V,
System 500S and Commander Compact are registered trademarks of VIPA Gesellschaft
für Visualisierung und Prozessautomatisierung mbH.
SPEED7 is a registered trademark of profichip GmbH.
SIMATIC, STEP, SINEC, TIA Portal, S7-300, S7-400 and S7-1500 are registered trade-
marks of Siemens AG.
Microsoft and Windows are registered trademarks of Microsoft Inc., USA.
Portable Document Format (PDF) and Postscript are registered trademarks of Adobe
Systems, Inc.
All other trademarks, logos and service or product marks specified herein are owned by
their respective companies.
All Rights Reserved
EC Conformity Declaration
Conformity Information
Trademarks
VIPA Networking Solutions
General
Copyright © VIPA GmbH
HB153 | PBR | 920-1CA50 | en | 19-09 4

Contact your local VIPA Customer Service Organization representative if you wish to
report errors or questions regarding the contents of this document. If you are unable to
locate a customer service centre, contact VIPA as follows:
VIPA GmbH, Ohmstraße 4, 91074 Herzogenaurach, Germany
Telefax: +49 9132 744-1204
EMail: [email protected]
Contact your local VIPA Customer Service Organization representative if you encounter
problems with the product or have questions regarding the product. If you are unable to
locate a customer service centre, contact VIPA as follows:
VIPA GmbH, Ohmstraße 4, 91074 Herzogenaurach, Germany
Tel.: +49 9132 744-1150 (Hotline)
EMail: [email protected]
1.2 About this manual
This manual describes the PROFIBUS MultiRepeater 920-1CA50 from VIPA. It contains a
description of the construction, project implementation and usage.
Product Order number as of state:
HW
PBMR-A5 920-1CA50 01
The manual is targeted at users who have a background in automation technology.
1.3 Safety information
The system is constructed and produced for:
ncommunication and process control
ngeneral control and automation tasks
nindustrial applications
noperation within the environmental conditions specified in the technical data
ninstallation into a cubicle
DANGER!
This device is not certified for applications in
– in explosive environments (EX-zone)
The manual must be available to all personnel in the
nproject design department
ninstallation department
ncommissioning
noperation
Information product sup-
port
Technical support
Objective and contents
Target audience
Applications conforming
with specifications
Documentation
VIPA Networking Solutions General
Safety information
HB153 | PBR | 920-1CA50 | en | 19-09 5

CAUTION!
The following conditions must be met before using or commis-
sioning the components described in this manual:
– Hardware modifications to the process control system should only be
carried out when the system has been disconnected from power!
– Installation and hardware modifications only by properly trained per-
sonnel.
– The national rules and regulations of the respective country must be
satisfied (installation, safety, EMC ...)
National rules and regulations apply to the disposal of the unit!Disposal
VIPA Networking Solutions
General
Safety information
HB153 | PBR | 920-1CA50 | en | 19-09 6

2 Product Description
2.1 General
The PROFIBUS MultiRepeater A5 is advanced, flexible and robust network components
for PROFIBUS DP installations, to implement long multi-device spur lines and backbone
structures with star/tree segments.
nPROFIBUS DP is a high speed communication bus that has to comply with strict rules
concerning spur lines, because of possible reflections that could lead to communica-
tion disturbances. If spur lines or star segments are required, costly investments in
repeaters have to be done.
nA innovative component for such applications is the PROFIBUS MultiRepeater A5.
These are perfect economic solutions to implement reliable spur lines in high speed
DP networks. They have the functionality of 5 galvanic isolated transparent repeaters.
This allows network structures with extended spur lines that individually can handle a
maximum of 31 devices and a length equal to the main bus. The MultiRepeater
refresh a received message on one Channel and transfer it to all the other Channels
(chicken foot topology).
nBecause the PROFIBUS MultiRepeater A5 creates isolated segments, the device can
now be removed and added during operation. Also electrical bus problems and EMC
disturbances in a spur do not spread to the other segments. The intelligent logic and
isolation circuits of the MultiRepeaters do not change the bit width. This means the
MultiRepeaters do not have limitations in serial placement. The logic also detects the
transmission speed automatically.
nTo assist the installation work, termination is integrated and can be switched on/off.
The grounding concept is also selectable: direct or capacitive grounding. The Multi-
Repeaters are powered by a 10 to 32 DC Voltage (110/230V AC versions are also
available). For troubleshooting, maintenance and commissioning the MultiRepeaters
are equipped with a display on the outside, which indicate the status of each Channel
(Data and Error).
VIPA Networking Solutions Product Description
General
HB153 | PBR | 920-1CA50 | en | 19-09 7

2.2 Product features
n5 Galvanic isolated channels (repeater segments)
nTransparent for all PROFIBUS DP protocols
nDP-RS485 specifications for each channel
nCable redundancy for channel 1+2
n9.6 Kbps to 12 Mbps
n31 devices per channel
n1200 m spur line length (depends on transmission speed)
nNo limit in serial placement or cascading of MultiRepeaters
nNo address required
nIntegrated termination facilities (switches)
nConfigurable grounding system (direct or capacitive)
nIP 65 classification
Long spur lines to instruments and the possibility to remove/insert them during operation.
Short circuit protection on each spur line is automatically provided.
VIPA Networking Solutions
Product Description
Product features
HB153 | PBR | 920-1CA50 | en | 19-09 8

2.3 Application areas
nDynamic spur lines to actuators, flow meters and pH analyzers
nRemovable drives and motors
nPull/Plug motor control centres (drawers)
nRoof mounted devices in tank farms
nDirty and humid environments
nBarrier for non-galvanic isolated equipment
nLarge star/tree structured networks
nOutdoor applications with device and cable stress
2.4 Additional Benefits
nHot slave insertion and removal during operation
nShort circuit protection on each Channel
nCompact and robust construction
nStatus and error display (per Channel)
nSuitable for all DP cables
nConveniently arranged networks
nEasy extendable installations
nOn-board DB9 female connector on each channel for maintenance activities
nCost Savings
Because of the isolation and intelligence the PROFIBUS-Multi-Repeater provides, it can
be used as a barrier for electrically sensitive segments. This keeps the backbone and
other Channels clean.
2.5 Channel Structure
Each channel is electrically isolated and internally connected to the transparent intelligent
backbone. The termination is switchable and powered by the MultiRepeater. The
shielding of the PROFIBUS cable can be directly grounded or indirectly grounded.
VIPA Networking Solutions Product Description
Channel Structure
HB153 | PBR | 920-1CA50 | en | 19-09 9

2.6 Grounding System
The PROFIBUS MultiRepeater can be grounded by 3 methods:
nDirect grounding on the Ground Rail
nIndirect grounding (through a capacitor)
nCombination of direct and indirect
The power supply must be grounded directly on the Ground Rail. The shielding of the
PROFIBUS cables can be directly or indirectly grounded. If you do not want to ground all
or some cables to the common ground, i.e. compensating current, the cable shielding
must be connected to pin "I" which stands for Indirect grounding. A capacitor with a par-
allel high value resistor will separate the 2 potentials, ensuring protection of the signal
against non-DC disturbances. If by accident on 1 channel the Direct Grounding is con-
nected with the Indirect Grounding, the connection to the Direct Grounding bypasses the
capacitor in the Indirect Ground connection. The current on the shield will flow to Direct
Ground.
2.7 Cable lengths for PROFIBUS DP
The cables on the channels and the main channel must comply with the PROFIBUS DP
cable specifications for RS485.
Baudrate (kbit/s) 9.6 19.2 45.45 93.75 187.5 500 1500 3000 6000 12000
Segment length
(m)
1200 1200 1200 1200 1000 400 200 100 100 100
Segment length
(feet)
3940 3940 3940 3940 3280 1310 656 328 328 328
VIPA Networking Solutions
Product Description
Cable lengths for PROFIBUS DP
HB153 | PBR | 920-1CA50 | en | 19-09 10

2.8 Cable types for PROFIBUS DP
The cable type must comply with the PROFIBUS DP cable specifications for RS485.
Parameter Value
Wires 2 (twisted)
Impedance 135 ... 165 Ohm (3 to 20 MHz)
Capacity < 30 pF/m
Loop resistance < 110 Ohm/km
Wire diameter > 0.64 mm
Wire area > 0.32 mm2
The PROFIBUS MultiRepeater can handle cables based on multiple protection sheaths
with an overall cable diameter between 6 ... 12 mm.
VIPA Networking Solutions Product Description
Cable types for PROFIBUS DP
HB153 | PBR | 920-1CA50 | en | 19-09 11

2.9 Status display
The Status LEDs on the PROFIBUS MultiRepeater 920-1CA50 are very useful for diag-
nostics.
OFF Blinking ON
POWER Power is not switched on or
an internal failure
Power supply not stable or
an internal failure
Power supply OK
Main READY Power is not switched on or
an internal failure
Trying to detect the trans-
mission speed, but has not
locked it yet
The transmission speed has
been detected
Main RX-OK No communication detected
on the Main Channel
1 or more devices communi-
cating on the Main Channel
1 or more devices communi-
cating on the Main Channel
Main ERROR No problem has been
detected
Problem in the cabling has
been detected (Main
Channel)
Problem in the cabling has
been detected (Main
Channel)
Channel RX-OK There is no communication
detected (on this Channel)
1 or more devices communi-
cating (on this Channel)
1 or more devices communi-
cating (on this Channel)
Channel ERROR No problem has been
detected
Problem in the cabling has
been detected (on this
Channel)
Problem in the cabling has
been detected (on this
Channel)
VIPA Networking Solutions
Product Description
Status display
HB153 | PBR | 920-1CA50 | en | 19-09 12

3 Installation Instructions
3.1 Location
The PROFIBUS MultiRepeater A5 can be installed everywhere in a non-hazardous area
that complies with IP 65 (DIN 40 050) and the specified temperature range of -40 ... +75°
Celsius.
3.2 Position
Der PROFIBUS MultiRepeater A5 can be installed in every position, but it is recom-
mended to install it with the cable glands pointing down to create a more reliable protec-
tion against moist and dust (water compartment and glands). In this position it is also
easier to read the status display.
3.3 Mounting
The PROFIBUS MultiRepeater has 4 mounting holes for 4 ... 5 mm screws. To reach the
holes on position 1 and 2, the top lid has to be removed.
It is recommended to mount the MultiRepeater A5 with at least 4 suitable screws/bolts in
position 1, 2, 3 and 4. Be careful with the flat cable that connects the lid with the PCB.
VIPA Networking Solutions Installation Instructions
Mounting
HB153 | PBR | 920-1CA50 | en | 19-09 13

3.4 Power Supply
The 4-pin screw type power connector is located on the bottom left of the PCB:
1 Power LEDs
3 Power connector
The power supply must comply with the following specifications:
nVoltage: 10 - 32V DC
nCurrent: min. 130 mA
nWire diameter: < 2.5 mm2
nCable thickness: 5 to 10 mm
To connect the 24V supply to the 4-pin screw-type terminal, proceed as follows:
1. Strip the insulation from the cable or the conductors for the 24V power supply.
2. Secure the crimp terminals in the screw-type terminal.
There is a grounding point that can be used.
To connect the power supply, you need a 3 mm screwdriver.
If the power is switched on it can be diagnosed by the following indicators on the PCB:
nAll the LEDs should be shortly blinking.
nThe "READY" LED is ON or Blinking
nThe Power LEDs are ON (5V, 3V3 and 1V8).
It is recommended to use a power supply with a ground lead (3-wire).
3.5 Backbone
Connect the DP backbone cable to the bottom connector of the Main-Channel. If the Mul-
tiRepeater is not the last device on the bus segment, connect the Bus-Out cable to the
top connector of the Main-Channel.
Procedure
Testing
VIPA Networking Solutions
Installation Instructions
Backbone
HB153 | PBR | 920-1CA50 | en | 19-09 14

1 Bus-In Connector
2 Communication status LED
3 Bus-Out Connector
Pin Wiring
A Green wire
B Red wire
I Cable shielding
Shield Cable shielding
Connecting the indirect cable shielding is not required when the ground
clips are used.
If the Main-Channel recognizes valid PROFIBUS messages from one or more connected
devices, the "RX-OK" LED of the Main Channel should be blinking.
Pin layout of the screw
terminals
Test
VIPA Networking Solutions Installation Instructions
Backbone
HB153 | PBR | 920-1CA50 | en | 19-09 15

3.6 Spur Segments
Connect the spur segments to the connectors of Channel 1 to 5.
1 Communications status LEDs
2 Channel connector
Pin Wiring
A Green wire
B Red wire
I Cable shielding
Shield Cable shielding
If a Channel recognizes valid PROFIBUS messages from one or more connected
devices, the "RX-OK" LED of the Channel should be blinking.
3.7 Termination
The termination of the main channel has been set to OFF by default. If the MultiRepeater
is the last/first device on the segment, the termination must be set to ON.
The termination of the channels have been set to ON by default, because it is assumed
that the new segment is started at the MultiRepeater.
1 Termination of the main channel (default OFF)
2 Termination of the channels (default ON)
Pin layout of the screw
terminals
Testing
VIPA Networking Solutions
Installation Instructions
Termination
HB153 | PBR | 920-1CA50 | en | 19-09 16

Don’t forget to switch the termination ON at the other end of the segment
and make sure it is powered continuously.
3.8 Baudrate switch
The PROFIBUS MultiRepeater A5 recognizes the transmission speed by default. If it is
required that the MultiRepeater is locked to a certain transmission speed, the baudrate
switch should be set to the required value.
1 Baudrate switch
To set the rotary switch, use a 3 mm screwdriver.
0 = Auto detect (default)
1 = 9.6 kbps
2 = 19.2 kbps
3 = 45.45 kbps
4 = 93.75 kbps
5 = 187.5 kbps
6 = 500 kbps
7 = 1500 kbps
8 = 3000 kbps
9 = 6000 kbps
A = 12000 kbps
B ... F = Auto detect
Switch values
VIPA Networking Solutions Installation Instructions
Baudrate switch
HB153 | PBR | 920-1CA50 | en | 19-09 17

4 Technical data
Order no. 920-1CA50
Dimensions and weight
Dimensions L x H x D (mm) with screws
Weight
213 x 210 x 95 mm
Weight Approx. 800 g
Mounting screws 4 to 5 mm
Ambient conditions
Operating temperature -40 ... +75 °C
Isolation class IP 65 (DIN 40 050)
Protocol specifications
Supported Protocols DP-V0, DP- V1, DP-V2, FDL, MPI, FMS, PROFIsafe, PROFIdrive and
any other FDL based protocol.
Transmission speed 9.6 kbps to 12 Mbps (including 45.45 kbps)
Transmission speed detection Auto detect (default) or selectable with rotary switch
Transmission speed switch 0 = Normal repeating (Auto detect) (default)
1 = 9.6 kbps
2 = 19.2 kbps
3 = 45.45 kbps
4 = 93.75 kbps
5 = 187.5 kbps
6 = 500 kbps
7 = 1500 kbps
8 = 3000 kbps
9 = 6000 kbps
A = 12000 kbps
B...F = Auto detect
Transmission speed detection time < 10 s (if it is set to auto detect)
Data delay time At baudrate: Normal mode:
9.6 - 93.75 kbps ≤1.25 Tbit
187.5 - 500 kbps ≤1.3 Tbit
1.5 Mbps ≤1.4 Tbit
3 Mbps ≤1.6 Tbit
6 Mbps ≤2.0 Tbit
12 Mbps ≤3.0 Tbit
Delay time jitter Max. ¼ bit time
PROFIBUS cable specifications
Cable lengths 1200 m at 9.6 kbps to 93.75 kbps
1000 m at 187.5 kbps
VIPA Networking Solutions
Technical data
HB153 | PBR | 920-1CA50 | en | 19-09 18

Order no. 920-1CA50
400 m at 500 kbps
200 m at 1.5 Mbps
100 m at 3 Mbps to 12 Mbps
Cable thickness 6 to 12 mm
Wire diameter < 2.5 mm2
Wire type Stranded or Solid core
Number of devices Maximum 31 per Channel (including MultiRepeaters, OLMs, Laptops/
PCs, etc)
Termination Integrated and switchable. Powered according to IEC 61158
(390/220/390 Ohm)
nAll Channels (default: ON)
nMain-Channel (default: OFF)
Cascading depth No limits
Redundancy No
Power supply specifications
Nominal supply voltage 10 to 32 V DC
Current consumption 130 mA at 24 V power supply (all Channels fully loaded)
Power dissipation Max. 4.1 W
Reverse polarity protection Yes
Cable thickness 5 to 10 mm
Wire diameter < 2.5 mm2
Others
MTBF Not available
VIPA Networking Solutions Technical data
HB153 | PBR | 920-1CA50 | en | 19-09 19

5 Glossary
Address Unique number of a device connected to the network. With PROFIBUS this can be 0 to 126.
127 is a broadcast address.
Analyzer Software tool to observe the protocol traffic. Combi-Analyzers can also inspect the signal
quality. Other term: Bus Monitor
Backbone The primary bus cable. Most of the time only the control systems, MultiRepeaters and fiber
optic couplers are connected to this cable. The field devices are connected behind the MultiRe-
peaters and fiber optic couplers.
Bit Time (Tbit) The bit time Tbit is the time, which elapses during the transmission of one bit. It depends on the
baudrate and is calculated as follows Tbit = 1 (bit) / baudrate (bps).
Examples:
12 Mbps ® Tbit = 83 ns
1,5 Mbps ® Tbit = 667 ns
Busparameters Settings that define the timing behaviour on the bus. They are defined in the master. Examples:
Tslot, MaxTSDR.
C Capacitance
DGND Digital Ground
DIN German Institute for Standardization (www.din.de)
DP-V0 DP-V0 is the basic stage of the PROFIBUS DP communication protocol. DP-V0 devices
(master and slaves) perform the following basic functionalities:
nCyclic exchange of I/O data between controlling and slave devices
nDevice, Identifier (module) and Channel related Diagnosis
nParameterization of DP-slaves
nConfiguration of DP-slaves
DP-V1 DP-V1 is the first stage of extension of PROFIBUS DP after DP-V0. DP-V1 devices shall
comply with the following features:
nDevice related diagnosis is replaced by status and alarms.
nThe first three octets of the user parameterization data are now standardized
nOptionally these devices may support:
– Acyclic communication (MS1, MS2)
– If alarms are used, MS1 shall be supported
DP-V2 DP-V2 is the second stage of extension of PROFIBUS DP after DP-V1. DP-V2 devices shall
comply with the following features:
nData Exchange Broadcast (DxB) for slave to slave communication (publisher/subscriber
principle).
nIsochronous Mode (time tick synchronized operating slaves, e.g. drives)
nUp- and/or download of Load Region Data (domains)
nClock Control (synchronization within slaves) and Time Stamping
nRedundancy
EMC (Electromagnetic
Compatibility)
The extent to which an electric or electronic device will tolerate electrical interference from other
equipment (immunity), and will interfere with other equipment. Within the European Community
as well as in other countries it is regulated by law that electric and electronic components and
equipment comply with basic standards such as IEC 61000-6-2 or IEC 61326 or corresponding
individual product standards.
Hub A Hub refreshes a signal and passes the information on to all nodes which are connected to the
Hub. Data frames which were received on one port are transferred to all the other ports
(chicken foot topology).
VIPA Networking Solutions
Glossary
HB153 | PBR | 920-1CA50 | en | 19-09 20
This manual suits for next models
2