P. 5IM01C50C03-02EN
Item Parameter name Protocol
revision Descriptions Initial setting
Calibration Analog output trim D/A trim 7, 5 Allows the calibration of a selected analog output with an external reference at the
operating endpoint
-
Clear D/A trim <Override D/A
trim>
7 <5> Overrides any previous D/A trimming by restoring factory calibration values -
Scaled D/A trim 5Allows the calibration of the analog output with the external reference which is
scaled at 0 to 100%
Sensor trim Snsr trim 7Trimming -
Snsr zero trim 7Zeroing -
Snsr trim reset 7Reset sensor trim for factory setting -
Snsr L trim 7Display lower point of sensor trim 200.0°C
Snsr U trim 7Display upper point of sensor trim 850.0°C
HART output Time stamp Time stamp 7date and the time information which the transmitter maintains from the time of the
power on
1900/1/1 0:00
Polling address Poll addr 7Display and setting for multidrop (0 to 63) 0
Loop current mode 7Loop current setting at multidrop Off
Preambles Num req preams 7Number of requested preambles 5
Num resp preams 7Number of response preambles 5
Set real-time clock Set real-time clock 7Setting for date and time 1900/1/1 0:00
Burst mode Total burst msgs 7The number of burst mode functions 3
Burst mode 7Setting for burst mode Off
Burst command 7Setting for burst command cmd1
Burst dev var 7Setting for device variable of cmd9 or cmd33 First slot: DV0, the rest not used
Burst trigger mode 7Burst trigger mode selection from “Continuous”, “Window”, “Rising”, “Falling”, or “On
change”
Continuous
Burst trigger level 7Setting for burst trigger level 0°C
Burst units 7Setting for unit of burst trigger level °C
Update period 7Update period for burst message 8s
Max update period 7Maximum update period for burst message 60s
Event notication Num events support 7Maximum number of event support 1
Notif control 7Enable event notication on token-passing data link layer Off
Event mask 7Even masking Off
Retry time 7Event notication retry time 8s
Max update time 7Maximum update time for event notication 60s
Debounce interval 7Debounce Interval to detect an event 8s
Event status 7Display event status -
First unack evt tgr 7Display event time -
Device information Manufacturer 7, 5 Manufacturer identication code YOKOGAWA
Model 7, 5 Model name YTA70-J
Tag 7, 5 Tag number, up to 8 alphanumerical characters -
Long Tag 7, 5 Tag number, up to 32 alphanumerical characters. -
Descriptor 7, 5 Text which can be used by user in any way. Up to 16 alphanumerical characters -
Message 7, 5 Text which can be used by user in any way. Up to 32 alphanumerical characters -
Date 7, 5 Date information. MM/DD/YY. Not incremented. The date is updated whenever
changing on guration via conguration tool
Factory calibration date
Write protect 7, 5 Enable write protect if correct password is entered*2 Not protected
Write enable 7Disable write protect -
New password 7, 5 Sets a new password for write protection, if correct password is entered -
Revision numbers 7, 5 Revision information for software and hardware -
Chng universal rev 7HART protocol revision switch function As specied in order
Review Input info 7, 5 List of input variables -
Output info 7, 5 List of output variables -
Device info 7, 5 See “Device information” in this table -
*1: Or as specied upon ordering.
*2: The initial setting of password upon shipment is "********".
*3: With T/C or milivolts for sensor type, the alarm is generated when the input signal drops down below 2.5 mV.
Parameters List
Item Parameter name Protocol
revision Descriptions Initial setting
Process variables Process variable Snsr <PV> 7 <5> Measured variables in engineering unit -
El/CJC <Electr> 7 <5> Terminal temperature -
Dev var status 7Display data quality and limit status of Snsr and El/CJC -
Dynamic variable PV/SV/TV/QV 7Display dynamic variables -
Dyn var status 7Display data quality and limit status of PV/SV/TV/QV -
Dyn var assign 7Setting an assignment for PV/SV/TV/QV PV=Sensor, SV=El/CJC,
TV=QV=None
Output value Loop current <PV AO> 7 <5> Output value in mA -
PV % rnge 7, 5 Output value with respect to the range in % -
PV Log Read max/min log 5Reads the maximum/minimum PV stored in the memory
Reset max/min 5Clears the PV maximum/minimum log and restart logging
Signal Condition Range value Range conguration 7Range setting for PV LRV/PV URV -
PV LRV/PV URV 7, 5 Lower/upper range value to denes the 0%/100% value of the measurement 0°C/150°C
Apply values 7Rerange by actual input -
Range Limit Snsr LSL/USL 7Maximum/minimum values for range setting -
El/CJC LSL/USL 7Maximum/minimum values for El/CJC range -40°C, 135°C
PV LSL/PV USL <LSL/USL> 7 <5> Shows the max./min. usable value for upper/lower range value -
Unit Snsr unit 7Unit of sensor °C
El/CJC unit 7Unit of El/CJC °C
PV unit 7, 5 Unit of PV °C
Damping Snsr damping <PV Damp> 7 <5> Damping time constant in seconds: 0.4 to 60.0s 0.4s
El/CJC damping 7Damping time constant in seconds: 0.4 to 60.0s 0.4s
Sensor Setup Sensor cong Snsr cong 7Sensor type and related settings. -
Snsr type 7, 5 Sensor type and related settings. [When T/C or millivolts is selected] Always select
“single” for a measurement type. [When RTD or ohm is selected] Always select 2-,
3- or 4-wire but others for the number of sensor wires.
Pt100, 3-wire, °C *1
Snsr wire 7Display the number of sensor 3-wire
Snsr El/CJC type 7Display Internal CJC or Fixed CJC Internal sensor
Snsr s/n 7Setting of serial number for connected sensor 0
RTD factor 5For RTD only. Leave it to “1.” 1
Cold junction compensation 5For T/C only. Always leave it to “1.internal sensor.” Internal sensor
Cable resistance Snsr cable resist 7Display resistance of sensor cable 5.0Ω
Cable resist measurement
<Measure value>
7 <5> Actually measure the cable resistance of 2-wire RTD/ohm for compensation -
Enter value 5Enter new value of the RTD/ohm cable resistance for compensation 5.0Ω
Minimum span limit PV min span 7Display PV minimum span 10°C
Snsr min span <Min. span> 7 <5> Minimum settable span 10°C
El/CJC min span 7El/CJC minimum span 10°C
Sensor errors Error detection 5Type of sensor errors to be detected for burnout operation. (1)No test performed, (2)
broken sensor, (3)shorted sensor*3, or (4)broken & shorted*3
broken sensor
Output Condition Analog output range Loop cur 0%(100%)
<AO 0%(100%)>
7 <5> Output value for 0%(100%) in mA. 4mA(20mA)
Loop cur lower(upper) limit
<AO lo(up) lim>
7 <5> Output lower(upper) limit in mA. NAMUR, or 3.8 to 23mA 3.8mA(20.5mA)
Set limit = NAMUR 7Setting for loop cur lower limit = 3.8mA, loop cur upper limit = 20.5mA -
Loop test 7, 5 Change the output manually for testing the loop. 4mA, 20mA, or value within 3.5 to
23mA
-
Sensor error value Broken snsr value 7Setting for analog output value when sensor broken 23.0mA
Shorted snsr value 7Setting for analog output value when sensor shorted 3.6mA
NAMUR down 7Set analog output value to 3.5mA -
NAMUR up 7Set analog output value to 23mA -
Sensor error values 5Enter or select the output value when sensor error is detected. NAMUR upscale,
NAMUR downscale, or value within 3.5 to 23mA
NAMUR upscale [high]*1
Diagnostics Status Sensor errors 7, 5 Show error status related to a sensor. When any one of the errors turns “ON”, check
the sensor and wiring
-
ADC errors 7, 5 Show error status related to analog to digital conversion. When any one of the errors
turns “ON”, restart the device. If error remains, replace the device
-
Misc. errors 7, 5 Show error status related to a device. When any one of the errors turns “ON”, restart
the device. If error remains, replace the device.
-
Ext device status 7This bit is set if any Device Variable is in an Alarm or Warning State Device Variable Alert (0x02)
Cfg chng count 7Conguration change counter -
Reset cfg chng ag 7Reset conguration change counter -
Error detection Snsr error detection 7Type of sensor errors to be detected for burnout operation broken and shorted sensor
Snsr probe break detect 7Display “Snsr probe break detect” when sensor error None
Service Device variable
logging
Read dev var max/min log 7Reads the maximum/minimum PV stored in the memory -
Reset dev var max/min log 7Clears the PV maximum/minimum log and restart logging -
Data trending Trend 7Data trending support function -
Simulation Simulate 7Execution of device variable simulation -
Device reset Master reset 7Software reset -
Revision Record
●ManualNo.:IM01C50C03-02EN
●Title:YTA70TemperatureTransmitter
Edition Date Page Revised item
1st Jan. 2014 —New Publication.
2nd Apr. 2016 P. 1
3. Handling Precaution
4. Standard Specications
P. 2
7. Approval Options
Add (6) and (7)
Delete RFI Effects
Revised description of EMC conformity
Revised description of Load resistance
Revised ATEX intrinsically safe model
Revised name plate
Edition Date Page Revised item
3rd June 2017 P. 1
P. 2
3. Handling Precaution
4. Standard Specications
Add Control of Pollution Caused by the
Product
Add (1), (3) and Note