7
■EPDT-251b■
Caution
1. Vertical or horizontal installation is possible including the intermediates between vertical and horizontal
positions, however, do not install it upside-down.
* Failure to do so may result in an abnormal operation.
2. Before connecting piping to the product, remove foreign substances, dirt, etc. inside of the piping by flushing.
* Failure to do so may prevent the product from functioning correctly.
3. Match the fluid flow direction with the inlet and outlet of the product to ensure proper installation.
* Failure to do so may prevent the product from functioning correctly. (The valve will not close.)
4. Make sure to connect a strainer (80-100 mesh) to the inlet of the product.
* Failure to do so may prevent the product from functioning correctly.
5. Do not apply excessive load, torque or vibration to the product.
* Doing so may result in drastically shortened service life.
6. Secure the space required for disassembly or
removal at maintenance or inspections.
* Failure to do so prevents maintenance or
inspections being implemented.
7. Do not get the product wet.
* Failure to do so may result in an electric leakage.
8. Do not apply insulation to the solenoid coil.
* Doing so may cause an abnormal operation.
9. When the product is used in a facility which cannot
stop operating, install a bypass line with a bypass
stop valve.
* Use the bypass line while troubleshooting or
disassembling the product so that the facility can
keep operating.
10. Before piping, remove foreign substances and note that seal materials must not flow into the inside of
the product and piping.
* Foreign substances may cause valve seat leakage and malfunction.
11. When using the product under the conditions where the outlet pressure can accidentally become
higher than the inlet pressure, install a check valve at the outlet side to prevent backflow.
* Failure to do so may cause the backflow even during the solenoid valve is closed.
12. If the product is used in a steam line and negative pressure generates at its outlet side when it is
closed, install a vacuum breaker at the outlet side.
13. When using the product in a steam line, install a steam trap in the line.
* Failure to do so may cause condensate-induced problems.
14. When the product is used in a steam line, install it in such a way that avoids condensate accumulation
at the inlet side.
* Failure to do so may result in malfunction.
15. In case of a possible frozen line, take proper measures to remove water inside the piping or equip the
product with insulating materials.
* Freezing may damage the product. Do not insulate the coil.
16. When installing the product in the piping, do not grip and turn the coil or turn it with a tool.
* Doing so may damage the coil.
17. Do not pull the lead wires or hold the wire to lift and carry the product.
* Doing so may damage the coil.
18. Make the lead wires connected to the coil long enough so that the coil is easily dismounted or
replaced when required.
19. Band and support the lead wires connected to the coil to avoid their contact with workers or other
equipment and to avoid subjecting the wires to its own weight and tension.
20. If the product is in a closed piping condition, the fluid inside the pipe will expand in volume due to the
rise in fluid temperature and product may be damaged.
21. Sticky fluids may cause parts to stick and lead to malfunction
Minimum space
for dismounting coil
Required space for
replacement of product
150 mm or more
80 mm
or more