6!
This equipment is intended for installation!
in a controlled temperature indoor area free!
from Conductive contaminants.!
!
!
Important Safety Warning!
Please comply with all warnings and!
operating instructions in this manual. Save!
this manual properly and read carefully the!
following instructions before installing the!
unit. Do not operate this unit before reading!
through all safety information and operating!
instructions carefully!
!
2.3.1 Transportation!
Please transport the UPS system only in !
the Micro Data Centre to protect against !
shock and impact.!
!
2.3.2 Preparation!
• Condensation may occur if the UPS!
system is moved directly from cold to!
warm environment. The UPS system must!
be absolutely dry before being installed.!
• Please allow at least two hours for the UPS!
system to acclimate to the environment.!
• Do not install the UPS system near water
or in moist environments.!
• Do not install the UPS system where it!
!would be exposed to direct sunlight or near!
a heater housing.!
• Do not block ventilation holes in the UPS!
!
2.3.3 Installation!
• Do not connect appliances or devices which!
!would overload the UPS system (e.g. laser!
printers) to the UPS output sockets.!
• Place cables in such a way that no one!
can step on or trip over them.!
• Do not connect domestic appliances such!
as hair dryers to UPS output sockets.!
• The UPS can be operated by any individuals!
with no previous experience.!
• Connect the UPS system only to an earthed!
shockproof outlet which must be easily!
accessible and close to the UPS system.!
• Please use only VDE-tested, CE-marked!
mains cable (e.g. the mains cable of your!
computer) to connect the UPS system to!
the building wiring outlet (shockproof outlet).!
• Please use only VDE-tested, CE-marked!
power cables to connect the loads to the!
UPS system.!
• Pluggable equipment includes aprotective!
!earth conductor that carries the leakage!
current from the load devices (computer!
equipment). Total leakage current must not!
exceed 3.5mA.!
!
2.3.4 Operation!
• Do not disconnect the mains cable on the
UPS system or the building wiring outlet!
(shockproof socket outlet) during operations!
since this would cancel the protective !
earthing of the UPS system and of all !
connected loads.!
• The UPS system features its own, internal!
!current source (batteries). The UPS output!
!sockets or output terminals block may be!
!electrically live even if the UPS system is !
!not connected to the building wiring outlet.!
• In order to fully disconnect the UPS!
!system, first press the OFF/Enter button to!
disconnect the mains.!
• Prevent fluids or other foreign objects!
!entering the UPS system.!
Zellabox!
Safety Instructions!
!
!
!
!
!
!
!
!
!
!
!!!!!!!!!!2.3 Uninterruptible Power Supply!