Zeta Alarm Systems SMARTCONNECT SMART6 User manual

GLT-261-7-3
Doc: GLT-261-7-1 Issue: W.I.P Date: 25/08/2018
Doc: GLT-261-7-10 Issue: 001 Date: 14.08.2020
MULTI-LOOP PANEL
Installation Manual

Smart Connect Multi-loop Installation Manual
www.zetaalarmsystems.com
2
Contents
Introduction .................................................................................................................................................................................................. 4
About the Smart Connect Multi-loop Fire Alarm System.......................................................................................................................... 4
Overall Features ........................................................................................................................................................................................ 4
Additional Features ....................................................................................................................................................................................... 5
Document Conventions................................................................................................................................................................................. 6
Circuits and Zones ..................................................................................................................................................................................... 6
Wiring Styles.............................................................................................................................................................................................. 6
System Components ..................................................................................................................................................................................... 7
Panel Types ............................................................................................................................................................................................... 7
Panel Modules........................................................................................................................................................................................... 8
Control Panel Installation and Dimensions ................................................................................................................................................. 10
Enclosure Dimensions ............................................................................................................................................................................. 10
Panel Construction Details ...................................................................................................................................................................... 10
Locating the Fire Alarm Control Panel..................................................................................................................................................... 11
Mounting the Enclosure.......................................................................................................................................................................... 11
Mounting Hole Dimensions..................................................................................................................................................................... 11
Planning Cable Entry ............................................................................................................................................................................... 13
Cable Grounding...................................................................................................................................................................................... 13
Mains Wiring ........................................................................................................................................................................................... 13
Battery Wiring ......................................................................................................................................................................................... 15
Assembling the panel.................................................................................................................................................................................. 18
Initial Power Up....................................................................................................................................................................................... 19
Module Installation ................................................................................................................................................................................. 19
TRM RJ45 Port Address Designation ....................................................................................................................................................... 20
Securing the modules.............................................................................................................................................................................. 20
Before Powering the Panel On................................................................................................................................................................ 20
Power on Procedure................................................................................................................................................................................ 21
Field Wiring ................................................................................................................................................................................................. 22
Wiring Overview...................................................................................................................................................................................... 22
SCM-ACM Field Wiring Connections ....................................................................................................................................................... 23
Wiring recommendations for Alarm Circuits (SCM-ACM) ....................................................................................................................... 24
SCM-ACM Specifications ......................................................................................................................................................................... 24
Compatible Warning Devices .................................................................................................................................................................. 25
Maximum Warning Devices per Circuit................................................................................................................................................... 25
SCM-MIM Field Wiring Connections ....................................................................................................................................................... 25
Wiring Recommendations for Input Circuits (SCM-MIM) ....................................................................................................................... 25
SCM-MIM Specifications ......................................................................................................................................................................... 25
SCM-RM Field Wiring Connections.......................................................................................................................................................... 26
SCM-RM Specifications............................................................................................................................................................................ 26
SCM-ZMM Field Wiring Connections ...................................................................................................................................................... 27
Wiring Recommendations for Zone Monitor Circuits (SCM-ZMM) ......................................................................................................... 27

Smart Connect Multi-loop Installation Manual
www.zetaalarmsystems.com
3
SCM-ZMM Specifications ........................................................................................................................................................................ 27
SCM-NM Field Wiring Connections ......................................................................................................................................................... 28
Wiring Recommendations for Network Wiring (SCM-NM) ..................................................................................................................... 29
SCM-NM Specifications ........................................................................................................................................................................... 29
SCM-LCM Field Wiring Connections........................................................................................................................................................ 30
Wiring Recommendations for Loop Card Modules (SCM-LCM) .............................................................................................................. 31
Loop Device Wiring and Device Information........................................................................................................................................... 31
SCM-LCM Specifications.......................................................................................................................................................................... 36
Compatible Loop Card Devices................................................................................................................................................................ 36
Power Supply............................................................................................................................................................................................... 37
PSU Specifications ................................................................................................................................................................................... 37
PSU Fuses ................................................................................................................................................................................................ 38
Power Supply Status Indications ............................................................................................................................................................. 38
Power Supply Signals............................................................................................................................................................................... 38
Panel Printer................................................................................................................................................................................................ 39
Loading/Replacing the Printer Paper Roll ............................................................................................................................................... 39
Status LED’s ............................................................................................................................................................................................. 40
Printer Maintenance ............................................................................................................................................................................... 40
Fault Finding................................................................................................................................................................................................ 41
Appendix A: SPECIFICATIONS ...................................................................................................................................................................... 41
FUNCTIONS REQUIRED BY EUROPEAN STANDARD EN54-2..................................................................................................................... 42
FUNCTIONS REQUIRED BY EUROPEAN STANDARD EN54-4..................................................................................................................... 42
Appendix B: STANDBY BATTERY REQUIREMENTS ....................................................................................................................................... 42
Appendix C: LOOP DEVICE ADDRESS SETTING............................................................................................................................................. 43
Appendix D: PRODUCT CODES .................................................................................................................................................................... 46
Appendix E: Ground Fault Impedance values.............................................................................................................................................. 46

Smart Connect Multi-loop Installation Manual
www.zetaalarmsystems.com
4
Introduction
About the Smart Connect Multi-loop Fire Alarm System
The Smart Connect Multi-loop Control Panel is a powerful intelligent fire alarm control system with a user friendly 4.3 inch touch
screen display, which has been designed to provide reliable life safety and property protection, while also being easy to install,
commission and operate. The Smart Connect Multi-loop system is totally modular which enables it to satisfy any size building fire alarm
needs.
By adding intelligent loop modules, the Smart Connect Multi-loop can be upgraded to support up to 3000 addressable devices spread
across a flexible number of loop cards (maximum of twelve loop cards). The system can also be expanded by adding Form C relay
output modules, network interface modules, alarm circuit modules, and zone monitor modules for conventional detectors and devices.
The Smart Connect Multi-loop system’s touchscreen interface is designed to make status information clear, and system control
functions simple to operate. Through the use of function buttons on the systems display the user can easily “SILENCE BUZZER”, “STOP
SOUNDERS” or “START SOUNDERS”, or “RESET” the system. The system status presentation is structured to allow the different types of
system events (Alarms, technical alarms, and faults) to be viewed independently. Each system event presents the user with a message
describing the location of the alarm report and the type of event (manual alarm, smoke, or heat). If additional details about the nature
of the alarm report or its location are required, the user can add a text label to the device or zone.
The 32-bit microcontroller (MCU) at the heart of Smart Connect Multi-loop rapidly processes logical decisions based on the status of
the smoke detection and other initiating devices to control the system outputs. The Windows based software ‘Smart Configurator’ is
used to configure the system’s operation based on the customer specified operating requirements, and reduce
commissioning/installation times.
The Smart Connect Multi-loop system continuously checks all software and hardware for proper operation. It checks all control panel
electronic hardware, system memory components, and the system program. A hardware watchdog circuit is provided to ensure that
System programs are functioning properly. If a problem develops with the program or processor, the watchdog circuit places the
System into a fault condition and resets it.
The Smart Connect Multi-loop system is equipped with a backup microprocessor on its termination board. To ensure reliable
operation, if the main panel’s CPU stops, the backup CPU will take over and allow the system to still be able to detect and annunciate
alarms.
The fire alarm operation is always processed as the highest priority over all other operating modes.
Overall Features
•Modular construction allows a panel to be specified using just the required modules.
•Up to 4, 6 or 12 Loop modules (depending on panel model).
•4.3” colour touch screen display.
•Capacity for up to 26 intelligent modules (depending on panel model).
•Full system redundancy.
•Extensive Day/Night mode programming.
•Full cause & effect programming via front of panel or the ‘Smart Configurator’ PC software.
•250 ZETA addressable MKII devices per loop card.
•254 available programmable zones.
•Up to 64 panel peer-to-peer network.
•Positive Alarm Sequence.
•Alarm Verification.
•Alarm circuit special application 24V mode.
•15A power supply.

Smart Connect Multi-loop Installation Manual
www.zetaalarmsystems.com
5
EXPLANATION OF ACCESS LEVELS
The Smart Connect System has the following access levels.
ACCESS
LEVEL
ACCESSED BY
ACCESS METHOD
FUNCTIONS ACCESSED
1
General public
Default state
View Panel
Override delay (if used)
2a
Responsible person
Enter user access code
(default 0001)
Start sounders
stop sounders
Silence buzzer
Reset panel
Access User Menu
2b
Responsible person
Enter user access code
(default 0001), and press
Menu Access Icon
Enable / disable sections of system
Test Mode
View Zones / Points
View event log
Turn off delay
3a
Installer / Engineer
Enter Engineer Password
(Default 9999), and press
Menu Access Icon
Configure loops
Assign zones
Assign Text to each point
Modify Alarm Operation Programming
Configure network (if fitted)
System Diagnostics (LED blink / loop Autocheck)
Change passwords
Configure TCP/IP Port
3b
Installer / Engineer
Open Enclosure
Connect wiring during Install
Battery check during Maintenance
Update Cause & Effect programming via USB
4
Authorised Service Engineer
Open Enclosure & PC S/W
Update Panel Firmware, Add new language
Care should be taken to ensure that the access method for each level is only available to suitably qualified personnel.
Additional Features
There is PC configuration software, a mobile monitoring application, a repeater panel and a LED Expander PCB available.
PC Configuration Software: Smart Configurator
Repeater Panel: SMART/REP

Smart Connect Multi-loop Installation Manual
www.zetaalarmsystems.com
6
Document Conventions
Circuits and Zones
Circuit = this refers to an actual electrical interface, initiating (detection), indicating (signal), or relay.
Zone = this is a logical concept for a fire alarm protected area, and will consist of at least one circuit.
The terms zone and circuit are used interchangeably throughout this manual.
On the Smart Connect Multi-loop, circuits can be either conventional or addressable inputs or outputs. Both hardwired conventional
inputs and outputs, and addressable inputs and outputs may be grouped together to form logical zones.
Wiring Styles
Loop Circuits have a redundant pathway (powered from both sides of the circuit) and are able to be wired either in the Class A
designation or in the Class X designation (designed to operate past any a single short circuit with the addition of EN54 listed isolators).
Conventional Zone Circuits do not have a redundant path. The SCM-ZMM has 6 Class B circuits and simply terminates at the last
device.
Alarm Circuits do not have a redundant path. The SCM-ACM has 2 Class B circuits and simply terminates at the last device.
Typical SMART Connect Multi-loop Network Fire Alarm Wiring

Smart Connect Multi-loop Installation Manual
www.zetaalarmsystems.com
7
System Components
Panel Types
Model
Description
SMART6
•W:380mm x H:530mm
•Space for up to 6 small modules
•Supplied with a 400W 15A PSU
•Space for 2 x 14Ah batteries.
SMART6/32
•W:380mm x H:530mm
•Space for up to 6 small modules
•Equipped with 32 zone LED expansion
•Supplied with a 400W 15A PSU
•Space for 2 x 14Ah batteries.
SMART10/64
•W:500mm x H:600mm
•Space for up to 10 small modules
•Equipped with 64 zone LED expansion
•Supplied with a 400W 15A PSU
•Space for 2 x 38Ah batteries
SMART10/P/64
•W:500mm x H:600mm
•Space for up to 10 small modules
•Equipped with panel printer
•Equipped with 64 zone LED expansion
•Supplied with a 400W 15A PSU
•Space for 2 x 38Ah batteries
SMART26/64
•W:1000mm x H:665mm
•Space for up to 26 small modules
•Equipped with 64 zone LED expansion
•Supplied with a 400W 15A PSU
•Space for 2 x 38Ah batteries

Smart Connect Multi-loop Installation Manual
www.zetaalarmsystems.com
8
SMART26/P/64
•W:1000mm x H:665mm
•Space for up to 26 small modules
•Equipped with panel printer
•Equipped with 64 zone LED expansion
•Supplied with a 400W 15A PSU
•Space for 2 x 38Ah batteries
SMART/REP
•W:300mm x H:200mm
•Smart Connect Repeater
•Please refer to GLT-261-7-12 Smart
Connect Repeater Manual for further
information
Panel Modules
Model No.
Description
Technical
SCM-LCM
Loop Card Module
The plug-in loop card module
provides power for, and
handles communications to
the analogue addressable
devices. It has 4 fault status
LED’s for added fault finding
assistance.
Loop Voltage: 35V Nominal
Maximum Loop Current: 450mA
Maximum Loop Capacity: 250 Addresses
Maximum Loop Length: 2KM
Maximum Loop Resistance: 22Ω + to +, 22Ω - to -
Maximum SLC Capacitance: 500nF
Maximum SLC Baud Rate: 1024 bits per second
Compatible Devices: MKII-AOP, MKII-AOH, MKII-
AHR, MKII-AHF, MKII-AHF/CS90, ZAI-MI, ZAIO-MI,
ZAZM-MI, ZAIO/230, ZASC-MI, MKII-SSB, MKII-AXT,
MKII-AXTB, ZRAP, ZRAPB (All are EN54 approved)
SCM-ACM
Alarm Circuit Module
The plug-in alarm circuit
module provides power for,
and handles communications
to the non-addressable
sounder appliances. It has 2 x
Class B circuits and can be
programmed to provide two
24v DC auxiliary outputs.
Circuit Voltage: 29VDC Nominal
Maximum Circuit Current: 500mA per circuit
Maximum Circuit Impedance: 4Ω
Maximum Circuit Length: Depends on AWG
Special Applications: Auxiliary 24 VDC Output
[Power limited & Unsupervised]
End of Line Resistor: 4K7Ω
Compatible Devices: ZXT, ZXTB, ZRP, ZRPB (All are
EN54 approved)
SCM-RM
Multi Relay Output
A Relay module that is
designed to be DIN mounted
inside of a SMART Connect
Multi-loop panel. It’s
powered and interfaced to
the CIE via a RJ45 connection.
Can be configured as a
programmable relay or a
common alarm, common
fault or common tech alarm
relay via the panel settings.
Relay Type: Form C x 3
Switching Capacity: 5 A, 30 VDC (resistive)
5 A, 250 VAC (general use)
Quiescent Current @ 30V: 39.3mA
Relay Operated Current (LEDs ON): 115.26mA

Smart Connect Multi-loop Installation Manual
www.zetaalarmsystems.com
9
SCM-NM
RS485 Network
The SMART Connect Multi-
loop system network has the
facility to monitor, indicate
and control the functions of a
fire alarm installation, thus
allowing signals to be
distributed around a large
site. The network will
accommodate up to 64
nodes. The network uses
RS485 data communication.
Communication Protocol: RS485
Maximum Network Size: 64 Nodes
Maximum Distance Between Nodes: 1KM (using a
screened data cable) or 100M (using a standard
fireproof cable)
Network Wiring Typologies: Bus or Ring
NOTE: Only 1 network module allowed per panel. If
a second module is fitted, it will be powered down
when the panel starts.
SCM-MIM
Multi Input Unit
An input module that is used
to monitor and raise alarm
from any ancillary equipment
such as sprinkler flow switch,
aspiration detectors,
secondary fire control panel,
beam detectors, external
power supplies etc.
Input Voltage: 23.7VDC Nominal
Wiring Class: 6 x Class B
Quiescent Current @ 30V: 39.3mA
Input Max Impedance: 10Ω
Input End of Line: 4K7Ω
Alarm Triggering Resistor: 1KΩ
SCM-ZMM
Zone Monitor
A zone monitor that can be
typically used for
conventional devices and/or
for special detectors that are
not available in addressable
form. It has 6 x Class B input
circuits.
Zone Voltage: 26VDC Nominal
Wiring Class: 6 x Class B[Power limited &
Supervised]
Zone Maximum Line Impedance: 10Ω
End of Line Resistor: 4K7Ω
Alarm Triggering Resistor: 1KΩ
Compatible Detectors: MKII-OP, MKII-HR, MKII-HF,
MKII-HF-CS90, MKII-OH, ZT-CP3 (All are EN54
approved)
SCM-PM
RS232 Printer
The plug-in RS232 module
will give a Smart Connect
Multi-loop panel the ability to
interface to RS232 serial
equipment and devices. This
is most commonly used to
connect the panel to an
RS232 panel printer, or a
desktop printer for real time
event log printing. The
module also has a 5V aux
output that is used to provide
power to the panel’s internal
printer.
Communication Protocol: RS232
Baud Rate: 9600
Data Bits: 8
Parity: None
Stop Bits: 1
Compatible Devices: CUSTOM PLUS2 Panel Printer

Smart Connect Multi-loop Installation Manual
www.zetaalarmsystems.com
10
Control Panel Installation and Dimensions
Enclosure Dimensions
See table 1 for full dimensions see table 1.
Table 1
Panel
A
B
C
D
E
F
Top
Knock
outs
Side
Knock
outs
Bottom
Knock
outs
Max
Battery
Size
SMART/6
535mm
385mm
355mm
150mm
120mm
505mm
18
12
4
2 x 14Ah
SMART/10
665mm
535mm
505mm
200mm
170mm
635mm
26
8
4
2 x 38Ah
SMART/26
665mm
975mm
945mm
200mm
170mm
635mm
64
28
20
2 x 38Ah
Panel Construction Details
All components are manufactured from Zintec.
Large and Medium Smart Multi-loop Enclosures
Back box and door 1.5 mm
Door plate 0.9 mm
All internal parts are 0.9 mm
Small Smart Multi-loop Enclosure
All parts are 0.9 mm
Smart Repeater Enclosure
All parts 0.9 mm.
The paint colour for the main box and door is RAL9005 Black Leatherette (Black version).
The internals are RAL9005 Black Leatherette.

Smart Connect Multi-loop Installation Manual
www.zetaalarmsystems.com
11
The control cabinet can be semi flushed into a wall or surface mounted.
Locating the Fire Alarm Control Panel
The control panel should be installed per BS5839-1:2017 recommendations: -
The panel should be close to the main entrance of the building, so that it can be viewed by any fire-fighting personnel entering the
building.
•It should be fitted to a sturdy wall that will not flex unnecessarily.
•It should ideally be mounted at eye level, for it to be viewed without need of a ladder.
•It should be installed in a dry, weatherproof place, preferably NOT in direct sunlight.
•It should be easily accessible, so that the responsible person can perform their regular fire alarm checks.
The panel must be in a clean, dry position, which is not subject to excessive shock or vibration and at least 2 meters away from pager
systems or any other radio transmitting equipment. The operating temperature range is -5°C (23°F) to 40°C (104°F); maximum humidity
is 95%. The panel will withstand vibrations between 5 & 150 Hz.
Mounting the Enclosure
Fix the enclosure to the wall using all the mounting points provided:
SMART6: 4 x Mounting Points. See Fig 1
SMART10: 4 x Mounting Points See Fig 2
SMART26: 6 x Mounting Points. See Fig 3
Check the build and condition of the wall to decide a suitable screw fixing. The mounting holes are designed for No 8 roundhead or
countersunk woodscrews (or similar). Remove any debris from the enclosure. Take care not to damage the FACP during installation.
Mounting Hole Dimensions
Fig 1
ATTENTION: DO NOT DRILL ANY ENTRY HOLES INTO THE PSU SECTION OF THE ENCLOSURE WHICH IS LOCATED ON THE LEFT-
HAND SIDE OF THE CONTROL PANEL CABINET.

Smart Connect Multi-loop Installation Manual
www.zetaalarmsystems.com
12
Fig 2
Fig 3

Smart Connect Multi-loop Installation Manual
www.zetaalarmsystems.com
13
Planning Cable Entry
The Knock-out cable entries can be easily removed by tapping with a suitable screwdriver or chisel from outside the control panel box.
Alternatively, the entry can be drilled out, using a 20mm hole cutter. Care should be taken if using a drill. Consider removing the PCBs
to prevent damaging them.
The SMART Connect Multi-loop comes with many cable entry holes. If another entry hole is required, it is strongly recommended that
the panel door is removed to avoid accidental damage. Also, the power supply and termination board should be removed and stored in
a safe place. This would also help while fixing the back box to the wall.
Cable Grounding
The panel is provided earth bars located along the top of the panel for grounding incoming wiring if needed.
The SMART6 panel has 1 x 12 way Earth bar
The SMART10 panel has 2 x 12 way Earth bar
The SMART26 panel has 3 x 12 way Earth bar
Mains Wiring
ATTENTION: DO NOT DRILL ANY ENTRY HOLES INTO THE PSU SECTION OF THE ENCLOSURE.
Note: The AC (mains) input wiring, and the back-up battery connections are non-power-limited. All other connections on the
SMART connect multi-loop panel are power limited. Ensure that a minimum ¼” separation exists between non-power-limited and
power-limited circuits.

Smart Connect Multi-loop Installation Manual
www.zetaalarmsystems.com
14
Recommendations
The Mains supply to the FACP is fixed wiring, using Fire resisting 3-core cable (Between 1 mm² and 2.5mm²), or equivalent, fed from an
isolating double pole switch fused spur, and fused at 5A. This should be secure from unauthorized operation and be marked ‘FIRE
ALARM: DO NOT SWITCH OFF’. The supply must be exclusive to the Fire Panel.
Connecting the Mains Power
The AC Live (L), Earth (E) and Neutral (N) connections are marked on the power supply cage. It is essential that the mains Earth cable is
connected to the PSU’s Earth terminal. The incoming mains cable should be kept separate from the loop card cables to help minimise
mains interference.
It is advisable to apply power to the panel before connecting any devices, to check for correct operation, and to familiarise yourself
with the fire alarm panels controls.
If a knockout is removed, fill the hole with a suitable cable gland. If any knockout is removed, but subsequently not used, it should be
covered up.
The AC Mains cable must be fed into the enclosure via one of the cable entries at the top left corner of the back box (Refer to Figure 3
below).
ATTENTION: MAKE SURE ANY SPARE ENTRY HOLES THAT HAVE BEEN OPENED, BUT NOT USED ARE COVERED WITH SUITABLE
GROMMETS OR BLANKING SCREWS.

Smart Connect Multi-loop Installation Manual
www.zetaalarmsystems.com
15
Figure 3: Wiring the mains power supply
Panel
Input Voltage
Input
Frequency
PSU Cage
Size
Max Input Current
Max Surge current
Fuse
Installed
SMART6
120-230V AC
47-63 Hz
400W
3.6Amax@120Vac & Full-Load,
2.0Amax@220Vac & Full-Load
65A peak, 1.2ms duration,
<0.25A2s@230Vac, Cold Start
3.15A (230
V AC)
SMART10
120-230V AC
47-63 Hz
400W
3.6Amax@120Vac & Full-Load,
2.0Amax@220Vac & Full-Load
65A peak, 1.2ms duration,
<0.25A2s@230Vac, Cold Start
3.15A (230
V AC)
SMART26
120-230V AC
47-63 Hz
400W
3.6Amax@120Vac & Full-Load,
2.0Amax@220Vac & Full-Load
65A peak, 1.2ms duration,
<0.25A2s@230Vac, Cold Start
3.15A (230
V AC)
Battery Wiring
The SMART Connect Multi-loop panel uses two 12 Volt batteries, wired in series to give a 24 Volt back-up supply.
The +ve of one battery is connected to the red battery lead.
The –ve of the other battery is connected to the black battery lead.
The –ve of the first battery is connected to the +ve of the second battery using the link wire supplied.
Recommended Battery Types:
Panel
Recommended Battery size
SMART6
2 x Powersonic 12V,14Ah
SMART10
2 x Powersonic 12V,38Ah
SMART26
2 x Powersonic 12V,38Ah
To calculate the required backup battery capacity, use the information in Appendix B
Other makes and sizes of battery may be suitable. Calculate the standby requirements to determine the most suitable size of batteries.
Figure 4: Battery location and connection

Smart Connect Multi-loop Installation Manual
www.zetaalarmsystems.com
16
Panel
Charger Boost
Voltage
Charger Float
Voltage
PSU Cage Size
Max Charger Current
Max Battery Size
Fuse
Installed
SMART6
29.5V DC
27.6V DC
400W
1.1A
2 x 12V, 14 Ah
5A
SMART10
29.5V DC
27.6V DC
400W
2.2A
2 x 12V, 38 Ah
8A
SMART26
29.5V DC
27.6V DC
400W
2.2A
2 x 12V, 38 Ah
15A
Securing the batteries
The SMART Connect Multi-loop has been designed so that the batteries are secured in the panel with Velcro strips.

Smart Connect Multi-loop Installation Manual
www.zetaalarmsystems.com
17

Smart Connect Multi-loop Installation Manual
www.zetaalarmsystems.com
18
Assembling the panel
The SMART Connect Multi-loop is a modular panel, designed to be flexible to install. It will normally be supplied as the base panel with
a number of expansion modules packed separately. The Modules are Din Rail Mounted, and connect to the panel’s motherboard with a
small RJ45 cable (supplied with the module). The Base panel is available in 3 sizes:
SMART6 SMART10
SMART26
The above diagrams show the port addresses for each panel size
A typical panel set up would include:-
At least one module for initiating devices (Either a conventional zone module [SCM-ZMM], or an addressable loop module [SCM-LCM])
At least one module for warning devices (Either a conventional sounder circuit module [SCM-ACM], or an addressable loop module
[SCM-LCM])

Smart Connect Multi-loop Installation Manual
www.zetaalarmsystems.com
19
Initial Power Up
It is recommended to initially power up the panel with no modules connected to confirm that the base panel is functioning as
expected. To do this:-
1. Check that the AC cable is connected correctly and the proper grounding has been made (as per BS5839-1:2017).
2. Close the panel door
3. Turn on the mains power. The following will be observed:-
a. Power, Fault and System Fault LEDs will light for around 6 seconds
b. Fault and System Fault LEDs will turn off. Power LED will blink a few times
c. LCD will show touch for calibration. Press the screen within 3 seconds to perform a screen calibration. (The screen is
calibrated at the factory, so this step is not usually required)
d. The LCD shows the Zeta logo for a few seconds, while it checks to see what modules are fitted. (Note: the usual
“System Healthy” banner is not shown during the module check.)
e. If the panel finds no modules, it displays “No Modules” on its LCD
f. The panel has passed its power on test. It can now be turned off and the modules can be fitted.
Module Installation
The Smart Multi-loop panel uses the expansion port number to reference modules. It is recommended that any Loop Card modules are
fitted first to the first expansion ports, so that the loop circuit numbers follow a logical sequence (loop 1 in port 1, loop 2 in port 2 etc.)
1. Ensure that the installation area is free from any cables or wires that may get caught, and that there is enough space on the
DIN rail to mount the module. Also ensure that the DIN clip underneath the module is in the open position.
2. Place the module onto the DIN rail, hooking the metal earth clip underneath onto the rail first.
3. Once the earth clip is hooked, push the bottom of the module onto the rail so that the module sits flat.
4. Push the plastic DIN clip (located at the bottom of the module) upwards to lock and secure the module into position.
5. Once the module is secured to the DIN rail, simply connect the supplied CAT5E cable to the module’s RJ45 port.
6. Connect the other end of CAT5E cable to the nearest unoccupied RJ45 port on the termination PCB.
ATTENTION: THE PANEL MUST BE POWERED DOWN, AND DISCONNECTED FROM THE BATTERIES BEFORE INSTALLING OR
REMOVING ANY MODULES.
*Viewed from the side*

Smart Connect Multi-loop Installation Manual
www.zetaalarmsystems.com
20
TRM RJ45 Port Address Designation
Each RJ45 port on the SMART Connect Multi-loop termination PCB has its own unique port address. This port address is important to
keep note of as it is displayed on Alarm/Fault messages and is used when configuring or setting up cause and effects on the panel (See
operation manual GLT-261-7-11).
Securing the modules
The modules are designed to clip together to make them more secure. In addition, the SMART Connect Multi-loop panel is supplied
with DIN rail end stoppers. These should be fitted before the first module, and after the last module on each rail.
Before Powering the Panel On
1. To prevent the risk of a spark, do not connect the batteries. Only connect the batteries after powering on the system from its
main AC supply.
2. Check that all external field wiring is clear from any open, shorts and ground faults.
3. Check that all the modules have been installed properly, with correct connections and placement
4. Check that all switches and jumper links are at their correct settings.
5. Check that all interconnection cables are plugged in properly, and that they are secure.
6. Check that the AC power wiring is correct.
7. Ensure that the panel chassis has been correctly earth grounded (See BS5839-1:2017 recommendations).
8. Before powering on from the main AC supply, make sure that the front panel door is closed.
This manual suits for next models
5
Table of contents
Other Zeta Alarm Systems Control Panel manuals