Prosense PPS Manager User manual

2
PRS-UM-PPSM-EN-Rev.03-10.04.2020
WARNING
This user guide must be carefully read by all persons who are or will have the responsibility for
installing, using or servicing this product. This product must be installed, used and serviced in
accordance with the manufacturer's directives. Otherwise it could fail to perform its functions as
designed and persons who rely on this product for their safety could suffer severe personel injury or
death.
Properly installed panel can be used without any problem and covered under Prosense warranty. The
warranties made by Prosense with respect to this product are voided if the product is not installed,
used and serviced in accordance with the instructions in this user manual.
WARNING
Inductive or capacitive loads like motors,ventilation, eg. should not be directly connected to the
panel directly. In such cases, auxiliary external relays should be use to drive these loads.

3
PRS-UM-PPSM-EN-Rev.03-10.04.2020
CONTENTS
1.INTRODUCTION .................................................................................................................................... 4
1.1 Technical Specifications............................................................................................................... 4
1.2 Panel Dimensions .............................................................................................................................. 5
2. INSTALLATION..................................................................................................................................... 5
3. FUNCTIONS AND DETAILS.................................................................................................................... 7
3.1 LCD Screen:........................................................................................................................................ 8
4. MAIN BOARD AND CONNECTIONS...................................................................................................... 9
4.1 Main Board Details:........................................................................................................................... 9
4.2 Backup Battery Connection ............................................................................................................. 10
4.3 Main Power Connection.................................................................................................................. 11
4.4 Detector Connections...................................................................................................................... 11
4.5 PPS Series Detectors Connections................................................................................................... 13
4.5 Relay Outputs .................................................................................................................................. 15
5. FIRST RUN.......................................................................................................................................... 15
5.1 Automatic Test ................................................................................................................................ 16
5.2 LED Test ........................................................................................................................................... 16
6. PROGRAMMING ................................................................................................................................ 16
6.1 Set FAN1 Relay Level: ...................................................................................................................... 16
6.2 Set FAN2 Relay Level: ...................................................................................................................... 17
6.3 Set Alarm Relay Level: ..................................................................................................................... 18
6.4 Set Alarm Activation Type: .............................................................................................................. 18
6.5 Set Gas Type: ................................................................................................................................... 19
6.6 Set Language: .................................................................................................................................. 20
6.7 Scan Detectors:................................................................................................................................ 21
6.8 Show Detector:................................................................................................................................ 21
7. ALARM STATUS.................................................................................................................................. 22
7.1 What to do in case of alarm ............................................................................................................ 22
8. FAULT CODES................................................................................................................................. 23
Declaration ............................................................................................................................................ 24
Warranty Statement.............................................................................................................................. 25

4
PRS-UM-PPSM-EN-Rev.03-10.04.2020
1.INTRODUCTION
Prosense PPS Control Panel is produced specially for carparking area. Prosense PPS control Panel is
able to provide automatic gas concentration reading for gases CO, NO and LPG that mostly exist on
car parking areas. PPS Control Panel permanently transmits the gas concentration measurement
from detectors to the control unit. Before the gas concentration in the atmosphere reaches the LEL
or toxic PPM level, the control panel is able to shut off a gas valve, cut off power and turn on an
alarm via activating relays.
Prosense PPS Control Panel can have up to 4 zone modules that each can monitor up to 32 detectors.
A fully configured PPS Panel can handle managing 128 detectors. PPS Panel can be configured
depending on detectors used in each project with one, two, three or four zone modules.
Prosense PPS Panel has three relays on each zone module those are two level fan relays (F1 and F2)
and one alarm relay. Fan relays are not alarm relays. They will be activated after 60 seconds once the
defined threshold level exceeded and deacticvated after 240 seconds than the alarm status returned
to normal. The PPS Panel has one power module that can provide power to all zone modules. This
power module has also two relays which are fault and alarm. These relays will be activated if any one
of the zone modules generates fault and or alarm status.
Prosense PPS Control panel can manage up to 128 addressable detectors via RS485 serial
communication protocol. PPS Panel has an 2x8 LCD display to adjust measurement and alarm levels.
This LCD screen and menu keys allow user to set correct properties for each detector like gas
concentrations by gas type, measument type, range and alarm levels.
1.1 Technical Specifications
Power Source
220VAC +/-10%
Power Consumption
27VDC/200mA – 5.4W max. (without connected detectors)
Inputs (Internal)
4 x 32 detectors via RS485 serial input
Relay outputs
Fan1, Fan2, Alarm for each zone
Fault and Alarm for overal status
Contacts rating
3A, 24VDC or 3A 120VAC
Display
Graphic LCD (2x8)
LED indicators
Fan1, Fan2, Alarm
Power/ON, Fault, Alarm LEDs
Backup battery
2 x 12V 7A/h (Optional)
Operating Temp.
0-50C
0
Humidity
15-85% non condensing
Housing
ABS IP66 (366 X 276 X 186 mm)
Weight
5,5 kg
Main power fuse
2A
Backup battery fuse
2A
Table 1 : Technical specifications

5
PRS-UM-PPSM-EN-Rev.03-10.04.2020
1.2 Panel Dimensions
Panel dimensions are explained in Diagram 1:
Diagram 1: Dimensions (mm)
2. INSTALLATION
The PPS Control Panel box should never be placed in an explosive atmosphere and should be readily
accessible. It is necessary to drill holes for cable glands either on the top or bottom of the control
unit, depending on which side the electric cables are running in. Before drilling any holes you can
unscrew and remove the electronic parts to avoid accidentally damaging it. PPS Control panel should
not be placed near by high voltage cables or power cable, coaxial cables or transmitters, welding
stations or frequency regulators.
The PPS Control Panel box produced based on IP66 standard specifications. Always use the screw
holes to mount it and do not pierce panel from any other side. Always use cable glands to make cable
entries.
The PPS Control Panel has 4 plastic screws on the front of panel. Use a flat screwdriver to loose them
and remove the cover part on the front. Please take care and remove the connectors on the
electronic card while removing the cover. Fix the panel on the wall via using 4 screw holes after
removing the front cover. Reattached the front cover and tighten 4 plastic screws when wall
mounting completed.

6
PRS-UM-PPSM-EN-Rev.03-10.04.2020
Diagram 2: Panel cover plastic screw
To prepare cable entries, remove plastic covers from top or bottom of the panel. Then drill the holes
for cable entry and install cable glands to the holes you made it. Make sure you are using an
adequate IP66 rate cable gland to assure the box ingress protection is not compromised. The panel
box is modular and can be used with different assemblies. Prosense recommends having cable
entries from the lower side. Electronic board is located in the front cover of the panel. The power
supply is located at the back of panel box. The power must be connected to this power supply. If the
installation requires the connection to a backup battery, place the battery to lover right side of the
panel inside.
Diagram 3: Panel body
Plastic screws
Plastic screws
Backup battery connectors and fuse
Wall mounting hole
Power supply
N L G V-V+
Wall mounting hole
Wall mounting hole
Wall mounting hole
Main power entry and fuse
Space for backup
batteries
Power supply LED
Power supply output
adjustment switch

7
PRS-UM-PPSM-EN-Rev.03-10.04.2020
3. FUNCTIONS AND DETAILS
The front panel has the following LEDs for each zone as shown in Diagram 4:
Sign
Meaning
ON
Panel is in operation
FAN1
FAN1 relay status
FAN2
FAN2 relay status
ALARM
ALARM status
FAULT
Fault condition in at least one of the zone module
Table 2 : Front panel signs and meanings
There are four buttons near by LCD screen to perform configuration and display the detector details.
Their functions are given in table (The key assignments may vary depending on the menu page):
Key
Function For Configuration
Function For Display Operation
Enter to panel configuration
OK - Select key
T
Test button
Return back
↑
Go up
Go to next channel
↓
Go down
Go to next channel
Table 3 : Panel buttons and functions
Diagram 4: Front panel signs LCD and LEDs
There is a front plastic cover to protect panel from outer shells, water and dust. To reach to panel
first you need to open plastic cover via pressing both sides of the latches on the front.

8
PRS-UM-PPSM-EN-Rev.03-10.04.2020
Press to open
Diagram 5: Front cover
If panel ordered with keys a key needed to open plastic cover. In order to make panel connection,
you need to open the front cover using the key at right bottom side of front panel. The key works
clockwise and vice versa.
Diagram 6: Front cover with key
Diagram 7: Locker
3.1 LCD Screen:
PPS Panel has 2x8 LCD display on each zone module to show detector address, measurement level
and range as well as detector gas type.
Sign sample
Meaning
CO
Measured gas type
0
Gas level measured by detector
P
Measurement range (PPM)
D01
Detector address
Table 4 : LCD screen details
If there is no detector connected to channel, LCD screen will show fault status on channel (FLT) and
fault LED will be activated. That channel should be closed (deactivated) via using menu steps.
Locker

9
PRS-UM-PPSM-EN-Rev.03-10.04.2020
4. MAIN BOARD AND CONNECTIONS
4.1 Main Board Details:
PPS Control panel has one power module and main power connection from power supply to control
panel made on this board. This board provides power to zone modules.
Diagram 8: Control panel main board
As shown in the picture, power module has its own fuse. Power module equipped with two relay
modules as fault and alarm. Fault relay will be activated when any of the detector goes in to fault
status and alarm relay will be activated when any of the zone modules raise the alarm status.
Each zone module works independantly with the detectors connected to them. The connection made
by the V+, V-, A and B ports on zone module. Each zone module has three relays which are Alarm,
Fan 1 and Fan 2.
Connections to Zone modules
Fuse
Main power input
Backup
battery input
Fault relay
output
Alarm relay
output

10
PRS-UM-PPSM-EN-Rev.03-10.04.2020
Diagram 9: Control panel zone module board
4.2 Backup Battery Connection
To contiue operation in case of main power failure two backup batteries (12V 7Ah) must be serially
connected to the system. Take extra care to use correct poles while connecting the batteries. The
cables or main board can be damaged in case of mixing pins or making short circuits. Backup
batteries must be connected as shown in Diagram 10 below.
Diagram 10: Backup battery connection
Panel battery input
V+
V-
V+
V-
Battery 1/ 12V 7Ah
Battery 2/ 12V 7Ah
V-
V+
V+ A B V-
Detector connections
Alarm FAN2 FAN1
Relay outputs

11
PRS-UM-PPSM-EN-Rev.03-10.04.2020
4.3 Main Power Connection
Connection must be made three-wire 1.5mm2cross section cable to the main supply terminal entries
and fixed by using cable fastener on the terminal. Make sure all the detectors connected properly
before applying the power.
Name
Usage
L
Phase
Gnd
Ground
N
Neutral
Table 5 : Main power connection details
4.4 Detector Connections
Each PPS panel zone module can manage up to 32 PPS series detectors via RS485 serial conneciton.
V+, V-(GND), A and B ports must be connected via using four-wire cable. Detector connections supply
12-24VDC power to detector and read the output signal of detector from A and B ports. Thus
connections should be made correctly with extra care to do not mix ports and not cause any damage
on the detectors. Detector power connection should be done with 1.5mm2cross section cable. The
total distance between control panel and detectors should not exceed 800m. Detector connections
should be made with 4 core cable wire that 2 for power and 2 for RS485 and pin definitions are as
follows:
V+
output
+24VDC (Only for panel and detectors, do not use for any other device)
A
input
RS485 port A
B
input
RS485 port B
V-
Output
-VDC (GND)
Table 6 : Connection pin definitions
The wiring for detectors utilized with RS485 board should be done by using connection cable EIA
RS485 2 core wires with section 0.22 / 0.35 mm2 and shielded. Nominal capacity between the wires
< 50pF/m and nominal impedance 120 Ohms.
The V+, V- ports and A,B ports are located on same socket in PPS panel zone module. These ports are
formed together on Prosense PPS series detectors on detector main board. The connections should
be done with care to do not mix power and RS485 ports. All detectors will be connected through one
cable via hopping one detector to another till the last detector on the line.

12
PRS-UM-PPSM-EN-Rev.03-10.04.2020
The connection schema given in Diagram 11:
Diagram 11: Panel to detector connections
There should be one master device and up to 32 slave devices in RS485 communication. The master
is DP32 control panel and detectors will be the slave devices:
Diagram 12: RS485 communication
Each detector connected to same PPS panel should have unique address. Detectors having same
address would not be recognised by control panel. PPS panel can communicate up to 32 detectors. In
case less then 32 detectors connected, control panel would not show non-existent detectors. Unused
detectors should be deactivated on channel settings menu steps.
The last detector at the RS485 serial line should have the end of line resistor to enable the total
communication line. Otherwise control panel may not communicate to all, some or none of the
detectors. The end of line resistor controlled by end of line pins located on Prosense PPS series
detectors and can be enabled via putting the jumper on end of line pins. Details are given in section
4.5.
Detector 1
Detector 2
V-
B
A
V+
PPS
Panel
Max 32
Detector
V+ A B V-
V+ A B V-
V-
B
A
V+

13
PRS-UM-PPSM-EN-Rev.03-10.04.2020
4.5 PPS Series Detectors Connections
Prosense PPS series detectors has onboard RS485 Modbus serial communication module. The
board has 4 ports thus the detector connection should be made by 4 wire that 2 for power and 2
for RS485. The total lenght of the connection line should not exceed 1000 meters.
Diagram 13: PPS series detector board
The wiring for detectors utilized with RS485 board should be done by using connection cable EIA
RS485 2 core wires with section 0.22 / 0.35 mm2 and shielded. Nominal capacity between the wires
< 50pF/m and nominal impedance 120 Ohms.
Detectors will be wired in daisy chain (bus) mode. We recommend not to use star mode connection
due to negative impact of interference. Each detector should have uniqe address number in the
chain. The detectors would not be recognised by control panel if same address given to them. The
address of detector can be adjusted via using DIP-Switch set on the board:
DIP Switch to set detector address
V+ A BV-
Detector connection pins

14
PRS-UM-PPSM-EN-Rev.03-10.04.2020
Diagram 14: RS485 Modbus serial communication address and switch position
The last detector in the chain should have 120 Ohms RS485 termination resistor. The resistor is
already implemented on the board by default but not activated. User should activate the
termination resistor via using the termination pin once the installation completed:
Diagram 15: RS485 Modbus serial communication module end of line jumper
Important : Only the last detector on the serial bus should have end of line pin.
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
29
25
26
27
30
31
32
28
End of Line jumper enabled

15
PRS-UM-PPSM-EN-Rev.03-10.04.2020
4.5 Relay Outputs
PPS panel has two relays which are fault and alarm on main power module.
Fault: This relay will be activated when any of the zone modules in the system raise fault status.
Alarm: This relay will be activated when any of the zone modules in the system will exceed the
programmed alarm level.
Each zone module has three relays which are Alarm, Fan1 and Fan2. Their activation mechanism as
follows:
Alarm: This relay will be activated when the defined gaz level threshold exceed depending of the
activity type defined for related zone.
Fan 1: This relay will be activated after 30 seconds when any of the detectors will exceed the
programmed F1 level in related zone. This relay will be deactivated after 240 seconds when the
status returned to normal.
Fan 2: This relay will be activated after 30 seconds when any of the detectors will exceed the
programmed F2 level in related zone. This relay will be deactivated afte 240 seconds when the status
returned to normal.
The relays are configured as NO (Normally Open) by default at factory. The relay configurations
cannot be adjusted to NC (Normally Closed)
Important: Relays should not be connected to high current or 220V AC loads. The relay outputs
should be used as control signal and external relays should be used to drive such devices as relay on
main board cannot handle high load.
5. FIRST RUN
After power applied to PPS panel it will start illuminating the On LED. The LCD display shpw
“Sacnning Detector” at same time while panel tries to initialize the detectors connected to it:
Scanning will take at least 2 minutes. After two minutes each zone module installed on teh PPS panel
will report the number of detectors they recognized:
If all detectors working fine then LCD display will show the status of detectors: at first line the
number of detectors and average gas measurement level, at the bottom the detector address which
is measuring the highest gas level and the measurement level.
Scanning
Detector
Detector
01
CO:000P
D21:000P

16
PRS-UM-PPSM-EN-Rev.03-10.04.2020
In case an error the fault LED will be activated together with fault relay at same time. Fault details
can be seen via pressing up and down buttons. The fault codes and details given in section XXX.
5.1 Automatic Test
Prosense PPS Manager simultaneously monitor all detectors connected to it. The FAULT relay and
LED will be activated in case any problem. Alarm and fault status can be monitored on the screen.
5.2 LED Test
Prosense PPS Manager has special function to test LEDs on front panel at any time. Press T button to
initiate test operation. Panel will activate all LEDs for moment and turn off all of them except on LED
as it is always blinking.
6. PROGRAMMING
The panel is already programmed and ready for using when shipped. User should adjust the gas type,
alarm settings for each detector. Each detector should be defined independently. These adjustments
can be done via using the keys near by LCD screen. The menu content includes below items:
Menu Item
Function
Set Ext1
Set fan1 relay alarm level
Set Ext2
Set fan2 relay alarm level
Set Alrm
Set alarm level
Actv Typ
Set alarm raising method
Gas Type
Set gas type of the detector
Language
Set Language
Scan Det
Start scanning detectors
Show Det
Show each detector status
Table 7: Menu structer
6.1 Set FAN1 Relay Level:
To set alarm level for FAN1 press menu button to see menu items. The first item on menu is Set Ext1
to set level for FAN1:
Set Ext1

17
PRS-UM-PPSM-EN-Rev.03-10.04.2020
Press menu button again to start adjustment. It will ask the gas type :
Gas type can be changed via pressing up and down arrow buttons. There are three gas type
supported by PPS Manager which are CO, NO2, LPG. Once decided press Menu button to continue. It
will show the current level:
Alarm level can be increased or decreased via pressing up and down arrow buttons. For CO gas levels
will increase or decrease by steps 10PPM while for NO2 1PPM and for LPG 1LEL steps. Once the level
set use T button to return back to main menu or press again to exit from menu. FAN1 level cannot be
adjusted higher than the FAN2 relay level or Alarm relay alarm level. Thus user should adjust first the
FAN2 level or Alarm level.
6.2 Set FAN2 Relay Level:
To set alarm level for FAN2 press menu button to see menu items. The second item on menu is “Set
Ext2 “ to set level for FAN2. Thus up and down arrow buttons should be used to reach to “Set Ext2 “
menu item:
Press menu button again to start adjustment. It will ask the gas type :
Gas type can be changed via pressing up and down arrow buttons. There are three gas type
supported by PPS Manager which are CO, NO2, LPG. Once decided press Menu button to continue. It
will show the current level:
Sel Gas
CO
Ext1 Lv:
040
Set Ext2
Sel Gas
CO
Ext2 Lv:
100

18
PRS-UM-PPSM-EN-Rev.03-10.04.2020
Alarm level can be increased or decreased via pressing up and down arrow buttons. For CO gas levels
will increase or decrease by steps 10PPM while for NO2 1PPM and for LPG 1LEL steps. Once the level
set use T button to return back to main menu or press again to exit from menu. FAN2 level cannot be
adjuster higher than the Alarm relay level. Thus user should adjust first the Alarm level.
6.3 Set Alarm Relay Level:
To set alarm level for FAN2 press menu button to see menu items. The third item on menu is “Set
Alrm “ to set level for Alarm relay. Change the menu item via up and down arrow buttons to reach
“Set Alrm “ menu item:
Press menu button again to start adjustment. It will ask the gas type :
Gas type can be changed via pressing up and down arrow buttons. There are three gas type
supported by PPS Manager which are CO, NO2, LPG. Once decided press Menu button to continue. It
will show the current level:
Alarm level can be increased or decreased via pressing up and down arrow buttons. For CO gas levels
will increase or decrease by steps 10PPM while for NO2 1PPM and for LPG 1LEL steps. Once the level
set use T button to return back to main menu or press again to exit from menu.
6.4 Set Alarm Activation Type:
PPS Manager can activate relay in two mode. Either it can use each detectors gas measurement level
independently and activate alarms when any one of the detectors reached the adjusted level or it
can collect each gas detectors gas measurement level and calculate average gas measurement level
at the time of the reading to activate alarms. To set alarm activation type press menu button to see
menu items. The fifth item on menu is “Actv Typ“ to adjust alarm activation method. Change the
menu item via up and down arrow buttons to reach “Actv Typ“ menu item:
Set Alrm
Sel Gas
CO
Alrm Lv:
150
Actv Typ

19
PRS-UM-PPSM-EN-Rev.03-10.04.2020
Press menu button again to start adjustment. It will show default method :
Activation method can be changed via up and down arrow buttons:
Once decided use T button to return back to main menu or press again to exit from menu.
6.5 Set Gas Type:
PPS Manager can work together simultaneously three different gas type which are CO, NO2 and LPG.
Althugh PPS Manager can automatically recognize the connected detectors, it asks user to confirm
gas type. The reason is to make sure whether user connected the detector by mistake or real usage
as different gas types have different behaviours. To set gas type of the detector press menu button.
The sixth item on menu is “Gas Type“ to set gas type of the detector. Change the menu item via up
and down arrow buttons to reach “Gas Type“ menu item:
Press menu button again to start adjustment. It will show each gas type by order:
If the gas type is incorrect change the answer from “Yes” to No” via using up and down arrow
buttons:
Alm Typ
Avrg Val
Alm Typ
Max Val
Gas Type
CO
Yes
CO
No

20
PRS-UM-PPSM-EN-Rev.03-10.04.2020
Once confirmed use T button to return back to main menu. If you the gas type is not the gas shown
on the menu, change the gas type via pressing to menu button.
Then press again to see other option:
The fault LED will be activated in case user given “Yes” answer for two different gas type as detectors
in this series can measure only one type of gas. Once gas type set use T button to return back to main
menu or press again to exit from menu.
6.6 Set Language:
PPS Manager currently supports two languages which are English and Turkish. User can change the
language via seventh menu item “Language”. Press menu button and use up and down arrow
buttons to reach “Language“ menu item:
Press menu button again to start adjustment. It will show current language on screen:
To change Language use up and down arrow buttons:
Once confirmed use T button to return back to main menu.
NO2
No
LPG
No
Language
English
Language
Language
Turkce
Table of contents
Other Prosense Control Panel manuals
Popular Control Panel manuals by other brands

Siemens
Siemens MJ-XL Installation and operation manual

Protege
Protege LCD User Station user manual

BFT
BFT ALENA SW2 CPEM installation manual

Hydor
Hydor Bespoke Installation and maintenance instructions

Siemens
Siemens SXL-EX Operation, installation, and maintenance manual

Nortek Control
Nortek Control 2GIG GC2e installation guide

SALUPO
SALUPO RAIN PLUS 1 Instruction and installation manual

AMX
AMX ProLink PRO-DP8 quick start guide

Microm
Microm FX-3500 Installation and operation manual

Fike
Fike FIK-5496 Installation & operation manual

WhisperPower
WhisperPower WhisperTouch WP-TOUCH 5 User & installation manual

Philips
Philips RSAT 2 Customer's manual