Visonic PowerMaster-33 G2 Assembly instructions

D-304267 PowerMaster-33 G2 Installer's Guide 1
PowerMaster-33 G2
Version 18
Installer’s Guide
Table of Contents
1. INTRODUCTION ................................................. 2
1.1 System Features .......................................... 2
2. CHOOSING THE INSTALLATION LOCATION .. 6
3. POWERMASTER-33 G2 INSTALLATION .......... 7
3.1 PowerMaster-33 G2 Wiring Diagram........... 7
3.2 Opening the PowerMaster-33 G2 Control
Panel and Bracket Mounting ............................. 8
3.3 Connecting to the Telephone Line (detail
"K" in Figure 3.1)................................................ 8
3.4 Connecting Wired Zone and Siren (detail
"B" in Figure 3.1)................................................ 9
3.5 GSM Module and SIM Installation (detail
"L" in Figure 3.1) .............................................. 10
3.6 PGM-5 Installation (located in place of
detail "E" in Figure 3.1).................................... 11
3.7 Installing the PowerLink3 .......................... 12
3.8 Optional Expander Module (detail "I" in
Figure 3.1)......................................................... 13
3.9 Connecting Power to the Control Panel ... 15
3.9.1 Battery Insertion................................. 16
3.9.2 Connect AC Power to the Unit ........... 16
3.10 Closing the PowerMaster-33 G2 Control
Panel ................................................................. 17
4. VISUAL INDICATIONS, FIRST KEYPAD
ENROLLMENT AND USING PROX TAG..............18
4.1 PowerMaster-33 LED Indications ..............18
4.2 Enrollment of the First KP-250 PG2 Keypad
...........................................................................18
4.3 Using the Prox Tag .....................................19
5. MAINTENANCE.................................................19
5.1 Dismounting the Control Panel .................19
5.2 Replacing the Backup Battery ...................19
5.3 Fuse Replacement ......................................19
5.4 Replacing/Relocating Detectors ................19
5.5 Annual System Check ................................19
APPENDIX A. Specifications ...............................20
A1. Functional...................................................20
A2. Wireless ......................................................20
A3. Electrical .....................................................20
A4. Communication ..........................................21
A5. Physical Properties....................................21
A6. Peripherals and Accessory Devices .........21
APPENDIX B. Compliance with Standards ..........22
Quick User Guide to Main Alarm Control
Operations by KP-250 PG2 Keypad ....................23

2 D-304267 PowerMaster-33 G2 Installer's Guide
1. INTRODUCTION
PowerMasteris a PowerG-enabled professional all-in-one wireless security, fire and safety system supporting advanced
applications and Visonic's PowerG™ Two-Way, Time Division Multiple Access (TDMA) and Frequency Hopping Spread
Spectrum (FHSS) wireless technology. This offers unmatched wireless robustness, superior range and long battery life; a
perfect and user friendly solution for both monitoring service providers and professional installers.
The system consists of the PowerMaster-33 G2 control panel that does not include a built-in keypad and that operates
in conjunction with a wireless keypad display device (KP-250 PG2). The control panel accommodates all control
circuitry and operation software for a programmable 64-zone alarm system, while the keypad display unit enables the
installer and the user to enter their commands and provides visual and audible feedback.
This manual refers to PowerMaster-33 G2 v18 and above. The most updated manuals can be downloaded from the
Visonic Web site http://www.visonic.com.
Note: "Pmaster" is used as an abbreviation for "PowerMaster".
The system is supplied with 3 instruction manuals:
PowerMaster-33 G2 Installer's Guide (this manual) –for use of system installer during system installation.
KP-250 PG2 Installer’s Guide -–for use of system installer during KP-250 PG2 installation and PowerMaster-33 G2
configuration.
KP-250 PG2 User’s Guide -–also for use of system installer during system installation and configuration, but also for
the master user of the system, once installation is completed. Hand over this manual to the master user of the system.
1.1 System Features
The following table lists the PowerMaster features with a description of each feature and how to use it.
Feature
Description
How to configure and use
Visual Alarm
Verification
The PowerMaster when used with Next CAM
PG2 PIR-camera detector and GPRS
communication is able to provide the
Monitoring Station with clips captured in
alarm situations. The system sends the clips
to the Monitoring Station automatically for
burglary alarms and, depending on setup,
also for fire and personal emergency alarms.
1. Setup GPRS communication: see GSM
Module Installation section 3.5)
2. Configure camera settings:refer to the
Next CAM PG2 Installation Instructions
3. Enable fire and personal alarm
verification:see KP-250 PG2 Installer’s
Guide, section 3.6.6 Configuring Motion
Cameras for Video Alarm Verification
On demand clips from
cameras
The PowerMaster can provide images from
the Next CAM PG2 by demand from a
remote PowerManage server. Pictures are
taken based on a command from the
monitoring station. To protect customers'
privacy, the system can be customized to
enable the "On Demand View" only during
specific system modes (i.e. Disarm, Home &
Away) and also to a specific time window
following an alarm event.
1. Setup the On demand feature:see
KP-250 PG2 Installer’s Guide, section 3.6.6
Configuring Motion Cameras for Video Alarm
Verification
2. To request and view images:refer to the
PowerManage User's Guide, Chapter 5
Viewing and Handling Events
Easy Enrollment
PowerG devices are enrolled from the control
panel. "Pre-enrollment" can also be
performed by entering the PowerG device ID
number and then activating the device in the
vicinity of the panel.
To enroll or pre-enroll devices: see
KP-250 PG2 Installer’s Guide, section 3.4.2
Adding New Wireless Devices or Wired
Sensors

D-304267 PowerMaster-33 G2 Installer's Guide 3
Device Configuration
Device parameters and related system
behavior can be configured from the KP-250
PG2 keypad or from a remote location.
Each PowerG device has its own settings
which can be configured through the KP-250
PG2 keypad by entering the "DEVICE
SETTINGS" menu.
To configure devices from the KP-250
PG2: see KP-250 PG2 Installer’s Guide,
Chapter 3 Programming and also the
individual device's Installation Instructions.
To configure devices from a remote
location: refer to the PowerManage User's
Guide Chapter 3 Working with Panels and to
the Remote Programmer PC software User's
Guide, Chapters 6 and 7.
Diagnostics of the
control panel and
peripherals
You can test the function of all wireless
sensors deployed throughout the protected
area, to collect information about the
received signal strength from each
transmitter and to review accumulated data
after the test.
To perform diagnostics and to obtain
signal strength indication: see KP-250
PG2 Installer’s Guide, section 3.9
Diagnostics
Conducting periodic
tests
The system should be tested at least once a
week and after an alarm. The periodic test
can be conducted locally or from a remote
location (with the assistance from a non-
technical person in the house).
To conduct a walk test locally: see KP-250
PG2 Installer’s Guide, Chapter 4 Periodic
Test by Installer Code or KP-250 PG2 User’s
Guide, Chapter 8 Periodic Test by User
Code
To conduct a walk test from remote
location: refer to the Remote Programmer
PC software User's Guide, Chapter 6 Data
Details Tables.
Partitions
The partitioning feature, when enabled,
divides your alarm system into distinct areas
each of which operates as an individual
alarm system. Partitioning can be used in
installations where shared security systems
are more practical, such as a home office or
warehouse building.
1. Enable partitioning:see KP-250 PG2
Installer’s Guide, section 3.13 Partitioning
2. Setup partition association for each
device: see KP-250 PG2 Installer’s Guide,
section 3.4.2 Adding New Wireless Devices
or Wired Sensors
To understand more about partitioning:
see KP-250 PG2 Installer’s Guide,
APPENDIX B. Working with Partitions.
Device configuration
templates
The default parameters with which a new
device is enrolled into the system can be set
before you enroll devices. This default
template saves time on device configuration.
1. Define enrollment defaults for devices:
see KP-250 PG2 Installer’s Guide, section
3.4.7 Defining Configuration Defaults for
"Device Settings"
2. Enroll or pre-enroll devices: see KP-250
PG2 Installer’s Guide, section 3.4.2 Adding
New Wireless Devices or Wired Sensors
SirenNet - distributed
siren using Smoke
detectors
All PowerG smoke detectors are able to
function as sirens, alerting on any of 4 types of
alarm in the system: burglary, gas, fire or
flood.
Enable and configure SirenNet for each
smoke detector:refer to the SMD-426 PG2
/ SMD-427 PG2 Installation Instructions
Wired Siren outputs
The control panel can operate a wired siren
and strobe devices
Install and connect wired siren: see
section 3.8 Optional Expander Module

4 D-304267 PowerMaster-33 G2 Installer's Guide
Wired zones and
programmable
outputs (PGM)
The control panel can support wired detectors
and control automation devices with
programmable wired outputs.
1. Connect a wired zone or PGM device: see
section 3.4 Adding a Wired Zone and Siren.
2. Program the wired zone: see KP-250
PG2 Installer’s Guide, section 3.4.2 Adding
New Wireless Devices or Wired Sensors
3. Program PGM outputs behavior: see
KP-250 PG2 Installer’s Guide, section 3.7
PGM Output.
Reporting to Private
Users and/or
Monitoring Station by
telephone, SMS and
IP communication
The PowerMaster system can be
programmed to send notifications of alarm
and other events to 4 private telephone
subscribers by voice*and also to 4 SMS
cellular phone numbers and to report these
events to the Monitoring Station by SMS,
PSTN or IP communication.
To configure notifications to Private
phones:see KP-250 PG2 User’s Guide,
Chapter 6, section B.12 Programming
Private Phone and SMS Reporting
To configure reporting to the Montioring
Station:see KP-250 PG2 Installer’s Guide,
section 3.6.4 Configuring Events Reporting
to Monitoring Stations
Quick installation with
link quality indication
With PowerG devices, there is no need to
consult the KP-250 PG2 keypad when
mounting a wireless device, because
PowerG devices include a built-in link quality
indicator. Choosing the mounting location is
a quick and easy process.
To choose the ideal location to mount a
wireless device, see Chapter 2 Choosing the
Installation Location.
Device Locator
Helps you to easily identify the actual device
displayed on the KP-250 PG2 LCD display.
To read more on the Device Locator: see
KP-250 PG2 User’s Guide, Chapter 3,
Arming and Disarming the System
To use the device locator when bypassing
a zone or when clearing a bypassed zone:
see KP-250 PG2 User’s Guide, Chapter 6,
section B.1 Setting the Zone Bypass Scheme
To use the device locator when conducting
the periodic test: see KP-250 PG2 Installer’s
Guide, Chapter 4 Periodic Test by Installer
Code or KP-250 PG2 User’s Guide, Chapter 8
Periodic Test by User Code.
Guard key-safe
PowerMaster is able to control a safe that
holds site keys that are accessible only to the
site's guard or Monitoring Station's guard in
the event of an alarm.
1. Connect the safe to the panel: see
section 3.8 Optional Expander Module
Mounting, Figure 3.8b
2. Configure the safe's zone type to
"Guard Zone": see KP-250 PG2 Installer’s
Guide, section 3.4.2 Adding New Wireless
Devices or Wired Sensors
3. Setup guard code: see KP-250 PG2
Installer’s Guide, section 3.3 Setting Installer
Codes
Arming key
External system may control arming and
disarming of the PowerMaster system
Connect the external system output to the
panel: see section 3.8 Optional Expander
Module Mounting, Figure 3.8b
*
Supported in specific PowerMaster-33 G2 variants (for further details, please contact your Visonic representative).

D-304267 PowerMaster-33 G2 Installer's Guide 5
System Architecture:
Security Detectors and Transmitters
Control Panel and Display
Keypad
Keyfobs, Keypad and
Keyprox
Next CAM
PG2 Motion
Detector
with Camera
Next PG2
Motion
Detector
MC-302 PG2
Magnetic
Contact
TOWER-30AM
PG2
Mirror Detector
PowerMaster-33 G2
KP-250 PG2
KF-234 PG2
KF-235 PG2
Two-way
Keyfobs
KP-140 PG2
Two-way
Keypad
Safety Detectors
KP-160 PG2 Keyprox
SMD-426 PG2
Smoke Detector
SMD-427 PG2
Smoke & Heat
Detector
TMD-560 PG2
Temperature
Detector
GSD-441 PG2
Gas (Methane)
Detector
GSD-442 PG2
Carbon Monoxide (CO)
Detector
FLD-550 PG2
Flood
Detector
Sirens
SR-730 PG2
Outdoor
Siren
SR-720 PG2
Indoor Siren

6 D-304267 PowerMaster-33 G2 Installer's Guide
2. CHOOSING THE INSTALLATION LOCATION
To ensure the best possible mounting location of the PowerMaster control panel, the following points should be
observed:
The selected location should be approximately in the center of the installation site between all the transmitters,
preferably in a hidden location.
In close proximity to an AC source
In close proximity to a telephone line connection (if PSTN is used)
Where there is good cellular coverage, if GSM-350 PG2 is used
Far from sources of wireless interference, such as:
oComputers or other electronic devices, power conductors, cordless phones, light dimmers, etc.
oLarge metal objects (such as metal doors or refrigerators)
Note: A distance of at least 1 meter (3 ft) is recommended.
When mounting wireless devices:
Make sure that the signal reception level for each device is either "Strong" or "Good", but not "Poor".
Wireless magnetic contacts should be installed in a vertical position and as high up the door or window as possible.
Wireless PIR detectors should be installed upright at the height specified in their Installation Instructions
Repeaters should be located high on the wall in mid-distance between the transmitters and the control panel.
WARNING! To comply with FCC and IC RF exposure compliance requirements, the control panel should be located at
a distance of at least 20 cm from all persons during normal operation. The antennas used for this product must not be
co-located or operated in conjunction with any other antenna or transmitter.
Customer Premises Equipment and Wiring
A
B
C
D
E
F
G
H
I
E
E
H
J
A. Network Service Provider's Facilities
F. Alarm Dialing Equipment
B. Telephone Line
G. Answering System
C. Network Demarcation Point
H. Unused RJ-11 Jack
D. RJ-31X Jack
I. Fax Machine
E. Telephone
J. Computer
Note: The REN is used to determine the number of devices that may be connected to a telephone line. Excessive RENs on a telephone line
may result in the devices not ringing in response to an incoming call. In most but not all areas, the sum of RENs should not exceed five (5.0).
To be certain of the number of devices that may be connected to a line, as determined by the total RENs, contact the local telephone
company.
Connection to telephone company provided coin service is prohibited. Connection to party lines service is subject to state tariffs.
The installer should verify line seizure. Be aware of other phone line services such as DSL. If DSL service is present on the
phone line, you must install a filter. It is suggested to use the DSL alarm filter model Z-A431PJ31X manufactured by
Excelsus Technologies, or equivalent. This filter simply plugs into the RJ-31X jack and allows alarm reporting without
breaking the internet connection.

D-304267 PowerMaster-33 G2 Installer's Guide 7
3. POWERMASTER-33 G2 INSTALLATION
Required tool: Philips screwdriver #2.
PowerMaster-33 G2 mounting process is shown in Figures 3.1 - 3.10.
3.1 PowerMaster-33 G2 Wiring Diagram
A. Expander Module Flat
Cable
B. Wired Zone / Special
Siren Terminal Block
C. Battery Connector
D. ENROLL button
E. Front Unit
F. PGM-5 Module
G. Expander Module Wiring
Terminal Blocks
H. Back Unit
I. Power Supply
J. Expander Module
K. Power Connector
L. Phone Wiring Connectors
M.GSM-350 PG2
* or External Power Supply Unit
** or External Power Connector
*** or Terminal Block in North American Panels
Figure 3.1 –PowerMaster-33 G2 Wiring Diagram

8 D-304267 PowerMaster-33 G2 Installer's Guide
3.2 Opening the PowerMaster-33 G2 Control Panel and Bracket Mounting
To Mount the Unit:
1. Release the screws
2. Remove the front cover
3. Mark 5 drilling points on the mounting surface, then
drill 5 holes and insert wall anchors and then fasten
the back unit with 4 screws
A. Mounting surface
B. Back unit
C. 5 screws
* For back tamper
Figure 3.2 –Back Unit Mounting
3.3 Connecting to the Telephone Line (detail "K" in Figure 3.1)
PHONE WIRING
Connect the telephone cable to the SET connector and connect the telephone line cable to the LINE connector
(through the desired wiring cable entry).
Note: The telephone cable should be no longer than 3 meters.
A. LINE B. SET C. Tel line wall jack
Figure 3.3a –Phone Wiring

D-304267 PowerMaster-33 G2 Installer's Guide 9
PHONE WIRING IN NORTH AMERICA
A. LINE
B. SET
C. RJ-31X cord
D. 8-position RJ-31X plug
E. Brown
F. Red
G. Green
H. Gray
I. RJ-31X jack
J. Line from street
K. House phones
Figure 3.3b –Phone Wiring in North America
Phone wiring in the UK: Line terminals must be connected to pins 2 and 5 of the wall jack.
For all installations: If DSL service is present on the phone line, you must route the phone line through a DSL filter
(refer to MESSAGE TO THE INSTALLER on page 2 for further details).
3.4 Connecting Wired Zone and Siren (detail "B" in Figure 3.1)
If an expander module is not used, one wired zone and one low voltage siren can be connected directly to the front
panel PCB.
WIRED ZONE
*
&SIREN WIRING
A. GND
B. Wired Zone
C. Siren
D. For future use
E. Site external siren MG electronics
MG441PDS or equivalent 6-12VDC,
150 mA Max
F. Magnetic contact or any other contact
(not a detector)
G. Alarm N.C.
Figure 3.4 –Wired Zone and Siren Wiring
*
Wired zones can be enrolled in any zone in the PowerMaster-30 G2 control panel from 01 to 64

10 D-304267 PowerMaster-33 G2 Installer's Guide
3.5 GSM Module and SIM Installation (detail "L" in Figure 3.1)
Plug in the GSM module and fasten it as shown in the above
drawing making sure that the two leading slots on both sides of
the GSM module slide along the two leading ribs on the front
unit.
A. GSM module
B. Leading ribs
C. Leading slot (1 of 2)
D. Front unit
Caution! Do not install or remove the GSM module when the
system is powered by AC power or backup battery.
Insert the SIM card into the GSM module as shown in
the above drawing.
1. Slide top cover.
2. Open cover
3. Align SIM card in cover (note cover orientation)
4. Slide SIM card into cover
5. Rotate cover to close
6. Lock cover to close
IMPORTANT! Do not insert or remove SIM card when
the control panel is powered by AC power or battery.
Figure
3.5 –Optional GSM Module Mounting and SIM Card Insertion

D-304267 PowerMaster-33 G2 Installer's Guide 11
3.6 PGM-5 Installation (located in place of detail "E" in Figure 3.1)
PGM-5 is an output interface module designed to provide alarm, trouble events and status signals to external devices
such as long range wireless monitoring transmitters, CCTV systems, home-automation systems and LED annunciation
panels (for further details see the PGM-5 Installation Instructions).
The PGM-5 provides 5 solid state relay contact outputs and is designed to be used as a plug-in internal add-on module
with the PowerMaster-33 G2 control panel.
Mount the PGM-5 module as shown in Figure 3.6.
1. Press downward on the PGM-5 module (C), located in the back panel, between its 2 clips.
2. Connect the PGM-5 module flat cable (F) to the front panel receptacle (marked “IP”) and to the flat cable receptacle
of the PGM-5 (G).
Caution! The connector with strain relief clip (F1) is for the front unit –do not connect it to the back unit!
Notes:
The PGM-5 will be active only if the PGM-5 option was enabled in the control panel (see section 4.7.6, “PGM Output
Configuration”.
For wiring instructions, refer to the PGM-5 Installation Instructions included in the module's package.
Caution! When mounting the PGM-5 module it is strongly recommended to route the wiring cable (E) as shown in
Figure 3.6) to prevent interference which may occur if routed too close to the control panel antennas.
A. Front panel receptacle
(marked “IP”)
B. Front unit
C. PGM-5 Module
D. Back unit
E. Wiring Cable
F. Flat cable
F1. This side for front unit
F2. This side for back unit
G. PGM-5 flat cable receptacle
Figure 3.6 –PGM-5 Module Mounting

12 D-304267 PowerMaster-33 G2 Installer's Guide
3.7 Installing the PowerLink3
The PowerLink3 is used to view and control the PowerMaster system over the Internet.
Perform the following instructions for the PowerLink3 installation.
Note: PowerLink3 operation is not backed up by
the control panel’s battery and it is shut down
during AC failure.
1. Mount the internal PowerLink3 into the back
unit and fasten it with 2 screws.
2. Connect the flat cable (B) from the front panel
to the PowerLink3, as follows: Connector B1
to the front panel; connector B2 to the
PowerLink3.
3. Connect the Cat-5 cable from the PowerLink3
to the home router.
Note: In order to prevent interference to the
antenna, do not route the Cat-5 cable through
the cable entry knockout on the right side of
the panel.
A. Cat-5 cable to home router
B. Flat cable
B1. This side for front unit
B2. This side for PowerLink3
Figure 3.7 –PowerLink3 Mounting

D-304267 PowerMaster-33 G2 Installer's Guide 13
3.8 Optional Expander Module (detail "I" in Figure 3.1)
The Expander module is an optional module. If this optional module is used, the wired zone or special siren on the front
panel should not be used.
Mount the Expander module as shown in Figure 3.8a.
1. Press downward on the Expander module (located in the back panel) between its 2 clips.
2. Connect the Expander module flat cable to the front panel Expander receptacle.
Caution! The receptacle with strain relief clip is for the front unit –do not connect it to the back unit!
A. 2 clips
B. Flat cable with one strain relief clip
B1. This side for front unit
B2. This side for back unit
Figure 3.8a –Expander Module

14 D-304267 PowerMaster-33 G2 Installer's Guide
OPTIONAL EXPANDER MODULE, ZONES, SIRENS, AUDIO BOX AND WIRED DETECTORS WIRING
A. Back Unit
B. Expander
C. Internal siren or strobe 6-12 VDC,
150 mA Max.
D. External siren MG441PDS or similar siren 12 VDC
(nominal) 350 mA Max.
E. Connect wired detectors as illustrated.
Note:
The wired detector should be installed at least 2
meters away from the control panel.
Regarding the two wired zones, the control panel
classifies the events according to the resistance it
measures as shown in the table below.
E.O.L or Arming Key Resistance
Range
Zone
Arming Key
0 kΩ 1.76 kΩ
Tamper
Tamper
1.76 kΩ 2.64 kΩ
Normal
Arm
2.64 kΩ 3.52 kΩ
Tamper
Tamper
3.52 kΩ 5.26 kΩ
Alarm
Disarm
5.26 kΩ ∞
Tamper
Tamper
F. Detector without tamper switch or arming key
G. Detector with tamper switch or arming key's tamper
H. PGM device
I. Wired zone A or B
J. Ground (GND)
Figure 3.8b –Zone
and Siren Wiring
Notes for EXPANDER module wiring:
* Wired zone
terminals can be connected to a normally closed contact of a detector, switch (for example a Tamper
switch of any device), or a pushbutton, via a 2.2 K
resistor. The 12V terminal can be used to supply 12V (up to
36mA) to a detector (if necessary).
** The EXT terminal can be used to trigger an external siren.
The INT terminal can be programmed for an "internal siren" or "strobe" (see par. 4.7).
The 12V and "GND" terminals can be connected to a siren (for constant DC power supply).
*** The.12V supply to the PGM device is fused. Current is limited to 100 mA.
WARNING! When plugging terminals back into place, be sure to align them carefully with the pins on the PCB.
Misaligned or reverse insertion of terminals may damage internal PowerMaster-33 G2 circuits!
IMPORTANT! The terminals for internal and external sirens are DC outputs intended for 12V sirens. Connecting a
loudspeaker to any of these outputs will cause a short circuit and will damage the unit.

D-304267 PowerMaster-33 G2 Installer's Guide 15
3.9 Connecting Power to the Control Panel
Note: This equipment should be installed in accordance with Chapter 2 of the National Fire Alarm Code, ANSI/NFPA 72.
Connect the power cable and close the control panel as shown in Figures 3.9a –3.10.
POWER CABLE CLAMP EXTRACTION AND POWER CONNECTION FOR INTERNAL POWER SUPPLY
Perform steps 1 & 2 on a workbench before mounting.
1. Thick cable entry: Pull out a desired wiring plastic
cap (1 of 4).
2. Extract cable clamp (I) for use in the next step.
3. Insert the power cable through the desired wiring
channel (A). Route it to the power supply unit (E) and
remove the safety cover (D). Connect the 2 wires of
the power cable to the power supply terminal block
(F) with a screwdriver. Fasten the screws tightly.
Fasten the power cable by its clamp (B or C) and
close the safety cover (D).
4. Connect the power supply output cable (G) to the
power connector (H) in the front panel.
A. Optional wiring channels
B. For thin cable
C. For thick cable (reversed clamp)
D. Safety cover
E. Power supply unit
F. Power supply terminal block
G. Power supply output cable
H. Power connector
(*) Do not route wiring in this area, to enable proper
closure of the control panel.
I. Cable clamp.
Figure 3.9a –Power Cable Clamp Extraction and Power Connection for Internal Power Supply

16 D-304267 PowerMaster-33 G2 Installer's Guide
EXTERNAL POWER CONNECTION
Connect the power adaptor to the front panel power connector.
Figure 3.9b –External Power Connection
3.9.1 Battery Insertion
Open battery compartment cover.
Insert one 6-battery pack or 8-battery
pack and connect its connector as
shown in Figure 3.8c.
A. Front unit
B. Battery cable
C. Battery cable connector
D. Slot for battery cable
Figure 3.9c –Battery Insertion
3.9.2 Connect AC Power to the Unit
Connect power to the PowerMaster-33 G2 to mains power outlet (see Figures 3.8a and 3.8b).
Disregard any “trouble” indications pertaining to lack of battery or lack of telephone line connection.
For Europe Safety Compliance:
a. The model shall be installed according to the local electrical code.
b. The circuit breaker shall be readily accessible.
c. The rating of the external circuit breaker shall be 16A or less.

D-304267 PowerMaster-33 G2 Installer's Guide 17
3.10 Closing the PowerMaster-33 G2 Control Panel
Control panel final closure is shown below.
To Close the Control Panel:
1. Connect the flat cables, between front and back units, in their
respective connectors (up to 3, according to options).
2. Make sure that the "Power" indicator on the control panel lights
green.
3. Close the panel and fasten the 2 screws.
Figure 3.
10 - Final Closure

18 D-304267 PowerMaster-33 G2 Installer's Guide
4. VISUAL INDICATIONS, FIRST KEYPAD
ENROLLMENT AND USING PROX TAG
4.1 PowerMaster-33 LED Indications
The following table provides a detailed description of the LED indications on the PowerMaster-33 panel.
Color
Definition
LED Operation
Green
Local Power indication
STEADY: Indicates that system has mains power
BLINKING: Low battery state
NO LIGHT: AC failure
Green
Ready / Not Ready
Indication
STEADY: All partitions are ready
NO LIGHT: Not Ready / at least one partition is Not Ready
Red
System Arming State
Indication
STEADY: AWAY / At least one partition is AWAY
BLINKING: HOME / At least one partition is HOME and no
partitions are in AWAY
NO LIGHT: The system is presently in the disarmed state
Orange
System Not Online
Indication
STEADY: System is unavailable (Sync/Updating/In-menu)
NO LIGHT: System is available
Orange
System Trouble indication
STEADY: System has trouble
NO LIGHT: No trouble –all is well
4.2 Enrollment of the First KP-250 PG2 Keypad
The PowerMaster-33 G2 is designed to operate wirelessly with the KP-250 PG2 keypad installed anywhere within the
protected premises.
The first keypad is always enrolled as Keypad no. 1.
Note: The enrollment procedure described here is for the first KP-250 PG2 keypad only. The enrollment of additional
keypads is performed via the first enrolled KP-250 PG2 keypad (for instructions, refer to the KP-250 PG2
Installer’s Guide, section 3.4.2).
Step
Action
1
Press the "ENROLL" button (physically located inside the front unit of the PowerMaster-33 G2 control panel
–see Figure 3.1) for 2 seconds. If no keypad exists in the first location, the "ENROLL" LED on the
PowerMaster-33 G2 blinks slowly for 1 minute (go to step 3).
If a keypad already exists in the first location, the "ENROLL" LED on the PowerMaster-33 G2 control panel
lights steady for 10 seconds (go to step 2).
Note: Pressing the "ENROLL" button takes the system out of any menu mode (Installer Mode, User
Settings and Periodic Test).
2
Press the "ENROLL" button again within the timeout period (10 seconds). Any keypad that was enrolled in
keypad no. 01 is deleted from the system.
The "ENROLL" LED on the PowerMaster-33 G2 blinks slowly for 1 minute.
3
During this 1 minute period, hold the button for 5-7 seconds, until the LED on the keypad lights
red, and release*. The "ENROLL" LED on the PowerMaster-33 G2 will indicate the result of the enrollment
procedure.
PowerMaster-33 G2 "ENROLL" LED indication Result
Blinks fast for 5 sec. Successful enrollment of keypad
Lights steadily for 5 sec. Wrong device type
4
Upon completion of the enrolling procedure, the keypad is ready for immediate use even if the system is
currently in the Armed state.
Note: If the keypad was previously enrolled, it will be relocated automatically to Keypad no. 1. However, all
of the configured parameters will be lost and the keypad will revert to the default parameters.
*
If the KP-250 PG2 unit is battery-powered: first press any button on the KP-250 PG2 keypad momentarily to take the KP-250 PG2
keypad out of sleep mode and then hold the button for 5-7 seconds, until the LED on the keypad lights red, and release.

D-304267 PowerMaster-33 G2 Installer's Guide 19
4.3 Using the Prox Tag
Proximity tags enable authorized people to enter
restricted areas. Presenting a valid proximity tag to the
tag reader (as shown in the drawing) while the system is
armed causes the system to disarm. Presenting a valid
proximity tag to the tag reader while the system is
disarmed causes the system to be armed in AWAY
(optional HOME) mode. To enroll / delete proximity tags,
refer to the KP-250 PG2 User’s Guide.
Notes:
1. Use of the Proximity tags is optional.
2. Proximity tags are not compatible for use when partition
is enabled.
5. MAINTENANCE
5.1 Dismounting the Control Panel
A. Remove the screw that fastens the front unit to the back unit, see Figure 3.2.
B. Remove the 4 screws that fasten the back unit to the mounting surface - Figure 3.2 - and remove the control panel.
5.2 Replacing the Backup Battery
Replacement and first-time insertion of battery pack is similar, see Figure 3.9c.
With a fresh battery pack, correct insertion and tightened battery compartment lid, the TROUBLE indicator on the kp-
250 PG2 keypad should extinguish. However, the “MEMORY” message will now blink in the display (caused by the
“tamper” alarm you triggered when opening the battery compartment lid). Clear it by arming the system and
immediately disarming.
5.3 Fuse Replacement
The PowerMaster-33 G2 has two internal fuses that has automatic reset. Therefore, there is no need to replace the
fuses.
When over current condition occurs, the fuse cuts off the circuit current. Upon fault current being removed for several
seconds, the fuse is automatically reset and allows current flow through the circuit again.
5.4 Replacing/Relocating Detectors
Whenever maintenance work involves replacement or re-location of detectors, always perform a full diagnostic test
according to the KP-250 PG2 User’s Guide, section 12.9.
Remember! A "poor" signal is not acceptable.
5.5 Annual System Check
Note: The PowerMaster system must be checked by a qualified technician at least once every three (3) years
(preferably every year).
The annual system check is designed to ensure proper operation of the alarm system by performing the following checks:
Periodic test
Arm/disarm function
No trouble messages are displayed on control panel
The clock displays the correct time
Reporting: generating an event to be transmitted to the Monitoring Station and to the user.

20 D-304267 PowerMaster-33 G2 Installer's Guide
APPENDIX A. Specifications
A1. Functional
Zones Number
Up to 64 wireless zones, (including 2 hard-wired inputs).
Hard-wired Zone Requirements
2.2 kE.O.L. resistance (max. resistance of wires 220
Maximum Loop Current
1.5 mA
Maximum Loop Voltage
3.3 V
Loop Shorted
0 –1.47 V (0 –1.770 Ω)
Loop Normal
1.47 –1.8 V and 2.02 –2.3 V
Loop Open
2.3 –3.3 V (5.06 - ∞ Ω)
Installer and User Codes
1 master installer (9999 by default)*
1 installer (8888 by default)*
1 master user, no. 1 (1111 by default)
Users nos. 2 - 48
* Codes must not be identical
Control Facilities
- Integral keypad, wireless keyfobs and keypads
- SMS commands via optional GSM/GPRS module.
- Remote control by telephone.
Arming Modes
AWAY, HOME, AWAY-INSTANT, HOME-INSTANT, LATCHKEY, FORCED, BYPASS.
Alarm Types
Silent, personal panic/emergency, burglary, gas, fire and flood.
Siren Signals
Continuous (intrusion / 24 hours / panic); triple pulse –short pause - triple pulse... (fire);
four pulses –long pause –four pulses... (gas);
long pulse –long pause –long pulse... (flood).
Siren (bell) Timeout
Programmable (4 min. by default)
Internal Sounder Output
At least 85 dBA at 10 ft (3 m)
Supervision
Programmable time frame for inactivity alert
Special Functions
- Chime zones
- Diagnostic test and event log.
- Local and Remote Programming over Telephone, GSM /GPRS connections.
- Calling for help by using an emergency transmitter.
- Tracking inactivity of elderly, physically handicapped and infirm people.
- Message center (recording and playback)
Data Retrieval
Alarm memory, trouble, event log
Real Time Clock (RTC)
The control panel keeps and displays time and date. This feature is also used for the log
file by providing the date and time of each event
Battery Test
Once every 10 seconds
A2. Wireless
RF Network
PowerG –2-way synchronized Frequency Hopping (TDMA / FHSS)
Frequency bands (MHz)
433 –434
868 - 869
912 - 919
Hopping frequencies
8
4
50
Region
Worldwide
Europe
North America and
selected countries
Encryption
AES-128
A3. Electrical
External AC/AC adaptor
NA
External AC/DC adaptor
External (wall-mounted) switching power supply 100VAC to 240VAC, 50/60 Hz, 0.5A
/ 12.5 VDC, 1.2A
Internal AC/DC
Internal switching power supply:
Input: 100-240VAC, 0.75A
Output: 12.5 VDC, 1.6A.
Current Drain
Approx. 260 mA standby at the beginning (power ON) and then goes down to 60 mA,
1400 mA max. current drain during alarm.
Low Battery Threshold
7.2 V (6-cell battery pack)
9.6 V (8-cell battery pack)
Backup Battery Pack
Backup Battery Options:
Backup
period
Maximum external devices current (1)
1300 mAh
6 Battery Pack (2)
1800 mAh
8-BatteryPack (3)
2200 mAh 8-Battery
Pack (4)
4h
180 mA
300 mA
380 mA
8h
70 mA
125 mA
160 mA
12h
35 mA
70 mA
95 mA
24h
max backup w/o
load 22 hours
12 mA
25 mA
32h
no backup
0 mA
10 mA
39h
no backup
no backup
0 mA
Other manuals for PowerMaster-33 G2
1
Table of contents
Other Visonic Control Panel manuals
Popular Control Panel manuals by other brands

Beckhoff
Beckhoff CP79 Series Installation and operating instructions

Flexit
Flexit ProTouch 118257 user manual

Honeywell
Honeywell Symphony Frequently asked questions

Mircom
Mircom FA-262 Installation and operator's manual

Victron energy
Victron energy Skylla-i Control GX manual

Nordelettronica
Nordelettronica NE274-TVDL instruction manual