
LOOP 500
6
If a finite waiting time is programmed for detector circuit double-knock operation or cross-zoning and if
during this time, no second detector or no second zone which is programmed for detector circuit double-
knock operation or cross-zoning is activated, this message is reset.
The following message appears on the display:
B e f o r e E n d F i r e Z o n e X X X M l d Y Y T T T T T T T T T T T T L 1 *
F Z Z Z
XXX - No. of the zone
YY - No. of the detector
TTT - possible customer text
ZZZ - number of fire alarms active (where a pre-alarm is not counted as a fire alarm)
2.3.1. Measures in the case of pre-alarm
−
press Cancel int. aud. sign. key
the audible signal in the control panel will be muted.
−
initiate measures in accordance with alarm organization.
2.4. Fault message
−
yellow FAULT collective display illuminates
−
additional display according to the type of fault
•
SYSTEM FAULT continuous illumination
•
CHARGING FAILURE continuous illumination or
•
FAULT/DISABLE in the PRIMARY ALARM field flashing or
FAULT in the EXT.AUD. ALARM field illuminating continuously
−
the display shows in plaintext the type of fault (not in the case of system fault)
−
internal audible signal sounds intermittently (in the case of system fault, sounds continuously)
With more than one fault alarm active, last message will always appear on the second line of the display; all
other messages are concealed, this being indicated by the yellow FAULTS LED. The concealed messages
can only be scrolled after pressing the Reveal key at the ALARMS LED (in the field of the display); approx.
20 seconds after the arrow keys were last pressed, this will appear on the first line of the display.
2.4.1 Measures in the case of a Fault message
−
press Cancel int. aud. sign. key, the audible signal in the control panel will be muted.
−
initiate measures in accordance with alarm organization.
After repair, all functions should be tested. Remedy of faults should be entered in the Operation log with
date and time of day.
2.4.2. System fault
On occurrence of a system fault, all outputs of the control panel are set to quiescent state.
Indications
−
the yellow Fault collective display illuminates
−
the yellow System Fault display illuminates
−
the internal audible signal sounds continuously
On occurrence of a fault, maintenance should be advised at once!
http://www.firealarmengineers.com