ZIEHL TR440 User manual

ZIEHL industrie –elektronik GmbH + Co KG
Daimlerstraße 13, D –74523 Schwäbisch Hall
Temperature Relays and MINIKA® Mains Monitoring Digital Panelmeters MINIPAN® Switching Relays and Controls Measuring Transducers Grid- and Plant Protection
Operating Manual TR440
updated: 140407 Sc
TR440 12310-0702-04 Seite
1
/ 24 www.ziehl.de
- Transformer protection temperature relay

TR440 12310-0702-04 Seite
2
/ 24 www.ziehl.de
Table of contents
1Use and brief description....................................................................................................................... 3
2Overview of the functions...................................................................................................................... 3
3Connection diagram............................................................................................................................... 3
4Display and controls .............................................................................................................................. 5
5Important information ............................................................................................................................ 6
6Programs................................................................................................................................................. 7
7Installation .............................................................................................................................................. 7
8Start-up operation (commissioning) ..................................................................................................... 8
8.1 General instructions on operating .................................................................................................. 8
8.2 Display mode................................................................................................................................. 8
8.3 Menu mode.................................................................................................................................... 9
8.4 Configuration mode ....................................................................................................................... 9
8.5 Short operating diagram [Program 1]........................................................................................... 10
8.6 Short operating diagram [Program 2]........................................................................................... 11
8.7 Short operating diagram [Program 3]........................................................................................... 12
8.8 Short operating diagram [Program 4]........................................................................................... 13
8.9 Overview of commissioning......................................................................................................... 14
8.10 Selection of program number....................................................................................................... 14
8.11 Switch on device.......................................................................................................................... 14
8.12 Configure the sensors.................................................................................................................. 14
8.13 Configure the alarms ................................................................................................................... 15
8.14 Configure the relay test on K1...................................................................................................... 16
8.15 Configure the Modbus RS 485 interface (option)......................................................................... 17
8.16 Sensor simulation........................................................................................................................ 17
8.17 Code block................................................................................................................................... 18
8.18 Tips on operating......................................................................................................................... 18
8.19 Possible indications in display...................................................................................................... 19
9Factory settings.................................................................................................................................... 20
10 Maintenance and repair........................................................................................................................ 21
11 Trouble shooting.................................................................................................................................. 21
11.1 Display of program number, measurand and software version..................................................... 22
12 Technical data ...................................................................................................................................... 23
13 Mounting type SE 2 .............................................................................................................................. 24

TR440 12310-0702-04 Seite
3
/ 24 www.ziehl.de
1 Use and brief description
Temperature relay to protect transformers against excess temperature and to control a fan.
The temperatures in the windings are monitored with three Pt 100 sensors. The core temperature can be
monitored with a fourth sensor.
The 4 alarms/output relays are used to control the fan, to signal an advance warning and to switch-off the
transformer. Various programs facilitate using the alarm ideally for each application. Depending on the
program, e.g. an extra relay is available for the fault message or for triggering due to exceeding the
maximum core temperature.
Other uses: Alternatively, with the fourth sensor the temperature of the room the transformer is located in
can be monitored and, with the alarm, the room ventilation can be controlled. The device can also be used
for other tasks for temperature monitoring
e.g., for motors.
2 Overview of the functions
4 Sensor inputs Pt 100 (RTD), 2 or 3-wire connection
Large monitoring range -199…+850°C / -199...+999°F
4 Alarms / Relays
3-digit digital display (resolution 1°C / 1°F)
4 LEDs sensor
4 LEDs relay
4 LEDs alarm
1 LED error
Control voltage AC/DC 24-240 V
Clear displays and simple programming
Min and max sensor values can be saved
Code block against unintended / unauthorised changes to the settings
Optional RS 485 interface with Modbus RTU protocol
EasySimulation for simple sensor value simulation
3 Connection diagram
There are various connection possibilities depending on the four adjustable programs.

TR440 12310-0702-04 Seite
4
/ 24 www.ziehl.de
Program 1:
Program 2:
3 sensors in the windings:
3 sensors in the windings and 1 sensor in the
transformer core:
Fan/FAN (with cyclic test)
Advance warning 8alr8
Shutdown 8trp8
Malfunction (sensor error)
Fan/FAN (with cyclic test)
Advance warning (winding + core) 8alr8
Shutdown (winding + core) 8trp8
Malfunction (sensor error)
For the sensors in the windings and for the sensor
in the core, various limits can be set for each.
Program 3:
Program 4:
3 sensors in the windings and 1 sensor in the
transformer core:
3 sensors in the windings and 1 sensor in the
transformer core:
Fan/FAN (with cyclic test)
Advance warning (winding) / malfunction
combined 8alr8
Shutdown (winding) 8trp8
Shutdown (core) 8Cor8
Shutdown (core) 8Cor8
Advance warning (winding) 8alr8
Shutdown (winding) 8trp8
Malfunction (sensor error)
Alarm 2 simultaneously to reach the advance
warning temperature and the fault message.

TR440 12310-0702-04 Seite
5
/ 24 www.ziehl.de
4 Display and controls
1 Digital display (3 digits)
Display of sensor value
Display of error codes
Display of menu and configuration
mode
2 Right-hand decimal point
Off: The device is in the display
mode
Illuminated: The device is in the
menu mode
Flashes: The device is in the
configuration mode
3, 5 Up key / Down key (in display mode, normal state)
Change into the menu mode (see Operating instructions Point 8.3)
Press for 2 s: Displays min/max measurement of the selected sensor
Additionally pressing key set ≥ 2s deletes all min/max values
Press Up and Down ≥ 2s: EasySimulation, jumps into simulation mode for the sensors 1T
.. 3T (display 8S1-38)
4 Set/Reset key (in display mode, normal state)
Press briefly: Displays the next sensor (sensor LED illuminates)
Press for 2 s: Reset function, deletes a locked alarm
(=> [Delay time Alarm off] must have expired)
Press for 5 s: Displays the program number (e.g. 8PR38)
Press for 8 s: Displays the measurand (e.g. 8°C8)
Press for 10 s: Displays the software version (e.g. 8-008)
6 LED (red) error
Illuminated: Sensor error in one sensor circuit or an internal
device fault has occurred
7 LEDs (yellow) sensors
Illuminated:Displays the sensor value belonging to the LED in the
digital display
Flashes: Sensor error in the corresponding sensor circuit
8 LEDs (red) alarm
Illuminated: Alarm (1-4) has occurred
Flashes quickly (1:4): [Delay time Alarm on] running
Flashes long (4:1): [Delay time Alarm off] running
Flashes uniformly (1:1): Ready for reset, reset with key
Press "SET/RESET" ≥ 2s
9 LEDs (yellow) relay state
Illuminated:The relay belonging to the LED is operating
Off: The relay belonging to the LED is released
Table of contents
Other ZIEHL Transformer manuals
Popular Transformer manuals by other brands

Uhlenbrock Elektronik
Uhlenbrock Elektronik 28000 manual

FONESTAR
FONESTAR CV-1720 quick start guide

Delta Electronics
Delta Electronics Current Sense Transformers TCE1906H specification

Hobart
Hobart 6T28-600CL Operation and maintenance manual

Shinkawa
Shinkawa LS Series instruction manual

Huawei
Huawei JUPITER-3000K-H1 user manual