Zip HydroTap G4 Series User manual

1
Installation instructions
803341 V3.00 June 2019 - Zip G4 tap range
Technical support
Australia Ph: 1800 460 222 , UK Tel: 0345 6 005 005 email: service@zipindustries .co.uk
®
Installation instructions
Zip
HydroTap G4
Tap range.
Model number:
(See table of contents for specific models).

02 Installation instructions
803341 V3.00 June 2019 - Zip G4 tap range
Technical support
Australia Ph: 1800 460 222 , UK Tel: 0345 6 005 005 email: service@zipindustries .co.uk
Tap options
The G4 series offers a range of interchangeable taps to suit the customer's needs.
Classic range
Arc / Cube range
Elite range
Classic All-in-One
Mixer range
These standalone taps offer instant boiling, chilled
and sparkling water* and are directly compatible
with the G4 Command-Centre.
The All-in-One taps may be used as alternatives to
the above HydroTap and mixer tap combinations*.
The mains and vented mixer tap range may be
used in conjunction with any of the above to
provide mixed hot and cold water for sanitary
use*.
Celsius range
The Celsius range offer instant boiling, chilled
and sparkling / boiling and chilled / boiling and
ambient / chilled and sparkling / chilled or boiling*
water together with the an integral mixer to
provide mixed hot and cold water from the mains.
*Dependant upon model purchased.
Celsius All-in-One

03
Installation instructions
803341 V3.00 June 2019 - Zip G4 tap range
Technical support
Australia Ph: 1800 460 222 , UK Tel: 0345 6 005 005 email: service@zipindustries .co.uk
Table of contents
Tap options .............................................................................................................................................2
Generic installation instructions .............................................................................................................4
Min / Max water supply pressure requirements .....................................................................................4
Special tool requirements .......................................................................................................................4
Hole & tap positioning ............................................................................................................................5
Clearance envelope.................................................................................................................................6
Command Centre connection table .......................................................................................................6
Tap installation
Section 1 - Classic and Elite HydroTap G4 installation.............................................................................7
Section 2 - Arc / Cube HydroTap G4 installation ....................................................................................8
Section 3 - Vented Classic Mixer tap installation ....................................................................................11
Section 4 - Mains Arc & Cube Mixer tap installation...............................................................................12
Section 5 - Vented Arc & Cube Mixer tap installation .............................................................................13
Section 6 - Mains All-in-One tap installation ..........................................................................................15
Section 7 - Vented All-in-One tap installation ........................................................................................18
Section 8 - Mains Celsius tap installation ................................................................................................21
Section 9 - Mains All-in-One Celsius Arc tap installation........................................................................24
Product information
End of life disposal ..................................................................................................................................27
Contact details ........................................................................................................................................28

04 Installation instructions
803341 V3.00 June 2019 - Zip G4 tap range
Technical support
Australia Ph: 1800 460 222 , UK Tel: 0345 6 005 005 email: service@zipindustries .co.uk
Generic installation instructions
Arc / Cube
Elite Classic Classic
All-in-
One
Celsius
Min / Max water supply pressure requirements
HydroTaps and Mains All-in-One & Celsius taps sparkling models.............0.30 MPa (3.0 bar) - 0.7 MPa (7.0 bar)
HydroTaps and Mains All-in-One & Celsius taps non-sparkling models........0.17 MPa (1.7 bar) - 0.5 MPa (5.0bar)
Vented All-in-One sparkling models............................................................0.25 MPa (2.5 bar) - 0.5 MPa (5.0 bar)
Mixer taps and Vented All-in-One non-sparkling model taps.....................0.25 MPa (2.5bar) - 0.5 MPa (5.0 bar)
Using these instructions
These instructions are provided primarily to demonstrate how to install HydroTap G4 taps
and do not provide sufficient information to install and commission complete HydroTap G4
systems.
Please refer to all safety and installation requirements detailed in the Quick start guide
provided with the Command-Centre, and Command-Centre installation instructions found
online prior to any change to the complete system.
Arc Cube
All-in-One
Celsius Arc
!
HydroTaps All in One taps Mixer taps
Before commencing the installation, download & read the Command Centre
installation instruction manual, which can be found online at:
(Australia) www.zipwater.com
(UK) www.zipwater.co.uk
Tap installation special tool requirements In addition to normal tools, the following
(or equivalent equipment) will be required.
For the HydroTap G4, Celsius and mixer taps (for All-in-One Celsius Arc see below).
• 35mm diameter sheet metal hole punch for sinks (not supplied).
• 35mm diameter hole saw for worktops (not supplied).
• Nut runner tube spanner (supplied for all but Celsius & mixer taps) for fixing the tap assembly.
For the All-in-One tap & All-in-One Celsius Arc.
•50mm diameter sheet metal hole punch for sinks (not supplied).
•50mm diameter hole saw for worktops (not supplied).
•Nut runner tube spanner (not supplied for All-in-One Celsius Arc) for fixing tap assembly.
Font installation special tool requirements
•Hole saw or equivalent to suit surface being cut. Ø140m for Arc / Cube and Ø108mm for Classic and Elite.
!
Be aware of the risks of hazards which could cause harm when using tools.
Assess the risks before starting the installation.

05
Installation instructions
803341 V3.00 June 2019 - Zip G4 tap range
Technical support
Australia Ph: 1800 460 222 , UK Tel: 0345 6 005 005 email: service@zipindustries .co.uk
Tap Recommended
dispensing
distance (mm)
Elite 116
HydroTap Classic 116
HydroTap Arc/Cube 171 (-174 extended)
All-in-One 211
Celsius All-in-One
Arc 220
Celsius - Arc/Cube 220
Mixer - Arc 220
Mixer - Classic 270
Mixer - Cube 220
HydroTap G4 Classic
116
Note
• Celsius, All-in-One and mixer taps have spouts that swivel.
• All images are for illustrative purposes, to aid understanding
of the system configuration, and are not prescriptive of tap
positioning.
• Ensure that the taps are mounted in a position that allows the
water to safely drain to waste throughout the positional range.
Hole positioning
• Position the tap such that it dispenses into the sink bowl with ample clearance for a cup or tea pot.
Alternatively, the tap could be mounted away from the sink using a Zip Font, available as an accessory.
Tap positioning
125
225 with extension
Generic installation instructions
!
Ensure that taps are positioned to minimise the risks of scalding by dispensing
boiling water while using the mixer tap.

06 Installation instructions
803341 V3.00 June 2019 - Zip G4 tap range
Technical support
Australia Ph: 1800 460 222 , UK Tel: 0345 6 005 005 email: service@zipindustries .co.uk
Generic installation instructions
Clearance envelope
• See adjacent diagram.
• A clearance envelope around all Command-Centres must be
provided to allow adequate ventilation for the safe and effective
use of the HydroTap G4 system.
• The tap must have adequate clearance to correctly dress tubes
and hoses without kink or sagging.
• Allow space for the threaded boss and the connection pipes.
Clearance
envelope
535mm
min. 300mm
335mm
All plastic pipes / silicone tubes must be trimmed to size. They must have a constant fall to the Command-
Centre.
The connection tubes supplied with the tap head assembly CANNOT be lengthened.
Command Centre connection table - for reference
Mains In Mains water supply. Wholesome (cat 1).
Mains power IEC power lead, 230V AC 50Hz 13A socket.
USB Connect to the Tap—make sure they click together and are secured up off
the floor of the cupboard.
CO2IN Connect the 1/4’ connection from the CO2cylinder.
Boiling out Cut to length Red hose from tap. No kinks, bends or loops. Must fall from tap
directly to Command Centre.
Chilled out Connect the JG 1/4’ pipe to this push fit outlet. There is another push fit JG
fitting for the tap.
Vent Cut to length clear hose from tap. No kinks, bends or loops. Must fall from
tap directly to Command Centre.
Sparkling out Connect a piece of JG 1/4’ pipe to this outlet. Fit the carbonation valve to the
pipe, then connect valve to tap.
Bypass in Only used for Booster (supplied with 240/175 models) & scale filter. Braided
hose from Booster outlet (or scale filter).
Bypass out Only used for Booster (supplied with 240/175 models) & scale filter. Braided
hose from Booster inlet (or scale filter).
Mixer in
Only used when supplied with a special 3 hose mixer tap from Zip. Leave the
red dust caps on if not used.
If using a mixer tap connect to the blue marked braided hose from mixer tap.
Mixer out
Only used when supplied with a special 3 hose mixer tap from Zip. Leave the
red dust caps on if not used.
If using a mixer tap connect to the red marked braided hose from mixer tap.
Cut hoses to length, no clamps are required on silicone hoses.

07
Installation instructions
803341 V3.00 June 2019 - Zip G4 tap range
Technical support
Australia Ph: 1800 460 222 , UK Tel: 0345 6 005 005 email: service@zipindustries .co.uk
SECTION 1 Classic & Elite HydroTap G4 installation
• Apply a light smearing of silicone sealant on the
underside of the spacer to ensure a watertight fit.
1.2 Cut the hole & fit the spacer
• Cut a Ø35mm hole in the worktop / sink.
Note Make sure the tap location will allow the tap
spout to drain into the sink.
Ø35mm
EliteClassic
1.1 Configure the tap
All thread rod
Stainless steel
spacer
Spider
clamp
Nut
Black plastic
spacer
Blue chilled pipe
(chilled models)
Red boiling pipe
USB lead
Clear vent pipe
(boiling models)
Black
plastic spacer
1.3 Mount the tap
• Pass the tubes and USB cable through
the Ø35mm hole.
Ø35mm hole
1.4 Secure the tap
• Fit the stainless steel washer & spider clamp.
• Secure with nut.
• Feed each of the tubes and USB cable evenly
in between the legs of the spider clamp during
installation.
Nut
Spider clamp
Stainless steel
washer
1.5 Connect the water supply (detail shown,
assembled and disassembled)
Note correct filter orientation. Valves and
fittings must be sealed with PTFE tape.
!
Filter
(supplied)
via Isolation valve
(not supplied)
Incoming mains
ambient water
supply
Male - Female
adaptor
(supplied)
Braided hose
to Command
-Centre
(supplied)
Connect together Isolation valve
1/2” BSP
(G 1/2)
Australia UK
15mm
- 1/2” BSP
(G 1/2)
Ambient mains water supply

08 Installation instructions
803341 V3.00 June 2019 - Zip G4 tap range
Technical support
Australia Ph: 1800 460 222 , UK Tel: 0345 6 005 005 email: service@zipindustries .co.uk
Scalding risk, Position *A should not be selected with boiling water models.
!
2.2 Adjust the height & angle (fixed position options, see below)
225mm
175mm
*A *A
2.3 Cut the hole & mount the tap
• Cut a Ø35mm hole in the worktop / sink.
Ø35mm
• Slide o-rings in place.
• Mount tap in position on Ø35mm hole.
• Slide lower rubber washer & metal washer over
threaded boss, tighten the tap nut to secure in place.
• Do not over tighten.
Upper o-ring
Base ring
Lower o-ring
Rubber washer
Metal washer
Nut
Spout locating
screws
Undercut
for USB
Upper locating
positions
Spring clip
Lower locating
positions Dimples
Spring clip
The Arc / Cube have spouts that may be fixed in 1 of 6 angular positions and 1 of 2 height
positions. The spout is fixed and does not swivel.
Arc / Cube
2.1 Configure the tap (see diagram below)
• Remove spout locating screws, lower spout to expose the plastic spring clip.
• To reposition spout, prise open spring clip.
• Slide spring clip up/down to engage selected holes.
• Ensure dimples engage simultaneously with the two selected holes.
• Raise the spout (ensure USB lead fits in undercut and open ends of the clip).
• Align clip with locating holes, & refit the 2 x locating screws.
SECTION 2 Arc & Cube HydroTap installation

09
Installation instructions
803341 V3.00 June 2019 - Zip G4 tap range
Technical support
Australia Ph: 1800 460 222 , UK Tel: 0345 6 005 005 email: service@zipindustries .co.uk
2.5 John Guest fittings (insertion and removal)
• Ensure cut tube has a clean, square & straight edge.
• Remove any residual material.
• Ensure tube remains round, without distortion.
• See adjacent diagram for fitting & removal.
2.4 Fit the tube kit (The L/H & R/H positions of the three way silicone tube are interchangeable) refer to
instruction supplied with the tube kit, and the configuration diagrams below .
SECTION 2 Arc & Cube HydroTap installation
Blue / White
LLDPE
Red
Silicone
Boiling, chilled
& sparkling
Boiling &
ambient
Blue
LLDPE
Red
Silicone Clear
Silicone
Chilled and
sparkling
Blue / White LLDPE
Chilled
Blue
Silicone
Red
Silicone Clear
Silicone
Blue
Silicone
Boiling
Red
Silicone Clear
Silicone
Three way
silicone tube
S/S tube
20mm
insertion
Clamp Herbie
clip near the
end of the
three way
silicone tube
• Check the insertion depth as shown above.
• Ensure the Herbie clip is clamped close to the end of the three way silicone tube and aligned with the
central axis, as shown above.
• Compress with pliers for tight fit.
Axial alignment
of clips
Herbie clip
orientation:
align with axis
2.7 Attach the label Area 1
Area 2
BOILING
CHILLED
SPARKLING
BOILING
CHILLED
BOILING
AMBIENT BOILING CHILLED
SPARKLING CHILLED
• Clean tap, select correct label.
• Trim to size if required & fit to tap as indicated, see adjacent diagram.
2.6 Secure the tube kit
Vent connector
Note Fit the vent connector in ALL installations (to stabilise the tube assembly)
Boiling &
chilled

10 Installation instructions
803341 V3.00 June 2019 - Zip G4 tap range
Technical support
Australia Ph: 1800 460 222 , UK Tel: 0345 6 005 005 email: service@zipindustries .co.uk
SECTION 2 Arc & Cube HydroTap installation
Filter
(supplied)
Incoming mains
ambient water
supply
Male - Female
adaptor
(supplied)
Connect together
Braided hose to
Command -Centre
(supplied)
2.8 Connect the water supply (detail shown, assembled and disassembled)
Note correct filter orientation. Valves and
fittings must be sealed with PTFE tape.
!
via Isolation valve
(not supplied)
Isolation valve
1/2” BSP
(G 1/2)
Australia UK
15mm
- 1/2” BSP
(G 1/2)
Ambient mains water supply

11
Installation instructions
803341 V3.00 June 2019 - Zip G4 tap range
Technical support
Australia Ph: 1800 460 222 , UK Tel: 0345 6 005 005 email: service@zipindustries .co.uk
SECTION 3 Vented Classic mixer tap installation
3.1 Configure the tap
Braided
hose x 3
Nut
Lower rubber
washer
Upper rubber washer
Washer
Classic
3.2 Cut the hole & mount the tap
Nut
Lower rubber
washer
Upper rubber
washer
Washer
White or plain marking -
mains supply
Blue marking - MIXER IN
on Command-Centre
Red marking - MIXER OUT
on Command-Centre
Note Make sure the tap location will allow the
tap spout to drain into the sink.
• Slide upper rubber washer in place.
• Mount tap in position on Ø35mm hole.
• Slide lower rubber washer, metal washer then tap
nut over thread extension.
• Tighten the tap nut to secure in place, do not
over tighten.
• Match the braided hose and tap extension colour
markings, attach the braided hoses.
• Ensure the seals on the end of the hoses are
lubricated, do not over tighten.
• Cut a Ø35mm hole in the worktop / sink.
Ø35mm
3.3 Fit the braided hoses (see 3.2)
3.4 Connect the water supply (detail shown,
assembled and disassembled)
Note correct filter orientation. Valves and
fittings must be sealed with PTFE tape.
!
Isolation valve
1/2” BSP (G 1/2)
Australia UK
15mm - 1/2” BSP(G 1/2)
Flow restrictor
(supplied)
T-piece
(supplied)
Male - male
adaptor
(supplied)
Incoming
mains ambient
water supply
Connect together
via Isolation valve
(not supplied)
Ambient mains water supply
Plain braided
hose to mixer
tap
Braided hose
to Command
-Centre mains
inlet

12 Installation instructions
803341 V3.00 June 2019 - Zip G4 tap range
Technical support
Australia Ph: 1800 460 222 , UK Tel: 0345 6 005 005 email: service@zipindustries .co.uk
Arc Cube
4.1 Configure the tap
Braided
hose x 2
Nut
Lower rubber
washer
Upper rubber
washer
Washer
4.2 Cut the hole & mount the tap
Note Make sure the tap location will allow the
tap spout to drain into the sink.
• Slide upper rubber washer in place.
• Mount tap in position on Ø35mm hole.
• Slide lower rubber washer, metal washer then
tap nut over threaded boss, then tighten the
tap nut to secure in place, do not over tighten.
• Match the braided hose and tap extension
colour markings. Attach the braided hoses.
• Ensure the seals on the end of the hoses are
lubricated.
• Do not over tighten.
• Cut a Ø35mm hole in the worktop / sink.
Ø35mm
Nut
Lower rubber
washer Upper rubber
washer
Washer
Section 4 Mains Arc & Cube mixer tap installation
Blue marking - Ambient
mains supply
Red marking - Hot mains
supply
4.3 Fit the braided hoses (See 4.2)
4.4 Connect the water supply (detail shown,
assembled and disassembled)
Note correct filter orientation. Valves and
fittings must be sealed with PTFE tape.
!
Isolation valve
1/2” BSP
(G 1/2)
Australia UK
15mm
- 1/2” BSP
(G 1/2)
Incoming
mains water
supply
Male - Female
adaptor
(supplied)
Blue marking -
Braided
hose
to tap
Red marking -
Braided
hose
to tap
Connect together
HotAmbient

13
Installation instructions
803341 V3.00 June 2019 - Zip G4 tap range
Technical support
Australia Ph: 1800 460 222 , UK Tel: 0345 6 005 005 email: service@zipindustries .co.uk
Section 5 Vented Arc & Cube mixer tap installation
Arc Cube
5.1 Configure the tap
• See adjacent diagram.
5.2 Low pressure installation
Replace the supplied Aerator with a 94732 flow
straightener in the spout of the v
ented Zip mixer tap.
Replacement
94732
Supplied
aerator
Braided
hose x 3
Nut
Lower rubber
washer
Upper rubber washer
Washer
5.3 Cut the hole & mount the tap, fit the braided hoses
Note Make sure the tap location will allow the
tap spout to drain into the sink.
• Slide upper rubber washer in place.
• Mount tap in position on Ø35mm hole.
• Slide lower rubber washer, metal washer then
tap nut over threaded boss, then tighten the
tap nut to secure in place, do not over tighten.
• Match the braided hose and tap extension
colour markings. Attach the braided hoses.
• Ensure the seals on the end of the hoses are
lubricated.
• Do not over tighten.
• Cut a Ø35mm hole in the worktop / sink.
Ø35mm
Nut
Lower rubber
washer
Upper rubber
washer
Washer
Plain hose, no marking -
Ambient mains supply
Blue marking - MIXER IN
on Command-Centre
Red marking - MIXER OUT
on Command-Centre

14 Installation instructions
803341 V3.00 June 2019 - Zip G4 tap range
Technical support
Australia Ph: 1800 460 222 , UK Tel: 0345 6 005 005 email: service@zipindustries .co.uk
Section 5 Vented Arc & Cube mixer tap installation
5.4 Connect the water supply (detail shown, disassembled and assembled)
Plain braided
hose to mixer
tap
Braided hose
to Command
-Centre
inlet
T-piece
(supplied)
Male - female
adaptor
(supplied)
Incoming
mains ambient
water supply
Connect together
Filter
(supplied)
Filter
(supplied)
Male - female
adaptor
(supplied)
Flow restrictor
(supplied)
Note correct filter orientation. Valves and
fittings must be sealed with PTFE tape.
!
Isolation valve
1/2” BSP (G 1/2)
Australia UK
15mm - 1/2” BSP(G 1/2)
via Isolation valve
(not supplied)
Ambient mains water supply

15
Installation instructions
803341 V3.00 June 2019 - Zip G4 tap range
Technical support
Australia Ph: 1800 460 222 , UK Tel: 0345 6 005 005 email: service@zipindustries .co.uk
Section 6 Mains All-in-One tap installation
O-ring
Base block
spider
Base block nut
Note Make sure the tap location will allow the tap
spout to drain into the sink.
6.2 Cut the hole & mount the tap
6.1 Configure the tap
• See adjacent diagram.
• Cut a Ø50mm hole in the worktop / sink.
Ø50mm
• Fit the o-ring to the underside of the tap.
• Pass tubes and cable through the Ø50mm hole.
• Feed each of the tubes and USB cable evenly between the legs of
the base block spider (see section 6.3).
• Locate the base block spider to the underside of the tap.
• Clamp in position using the base block nut.
• Do not over-tighten.
Note All silicone tubes must be cut to size. They must
have a constant fall back to the Command-Centre.
All-in-One
mains
USB cable

16 Installation instructions
803341 V3.00 June 2019 - Zip G4 tap range
Technical support
Australia Ph: 1800 460 222 , UK Tel: 0345 6 005 005 email: service@zipindustries .co.uk
Section 6 Mains All-in-One tap installation
6.4 Connect the tap
6.3 Position tubes, hoses & base block spider
Blue marking Red marking
USB cable
Red silicone
tube
Clear silicone tube
Blue marked
braided hose
(viewed from underneath)
Red silicone tube -To
BOILING OUTLET on
Command-Centre
Clear silicone
tube - To VENT on
Command-Centre
Blue silicone
tube -To
CHILLED
OUTLET on
Command-
Centre
Blue marked
braided hose to
blue marked pipe
on tap
USB plug, connect
to Command-
Centre
Blue silicone
tube
Red marked
braided hose
Red marked
braided hose to
red marked pipe
on tap
• Connect the tap using the
adjacent diagram.
• Match the braided hoses &
extension tubes colour markings.
• Attach the braided hoses
(lubricate seals).
• Do not over tighten.
• For sparkling HydroTaps, connect
the supplied Y connector to the
blue silicone tube, then 1/4” blue
and white pipes as shown.
• For ambient HydroTaps, connect
the supplied connector to the
blue silicone tube, then 1/4” blue
pipe as shown.
• Attach the USB connector to the
Command-Centre.
White pipe
to SPARKLING
OUTLET on
Command-
Centre
Blue pipe
to CHILLED
OUTLET on
Command-
Centre
Blue pipe to
AMBIENT
OUTLET on
Command-
Centre
SPARKLING
models
OR
OR
AMBIENT
models
Red marked braided
hose to hot mains
water supply
Blue marked braided
hose to ambient mains
water supply

17
Installation instructions
803341 V3.00 June 2019 - Zip G4 tap range
Technical support
Australia Ph: 1800 460 222 , UK Tel: 0345 6 005 005 email: service@zipindustries .co.uk
Section 6 Mains All-in-One tap installation
6.5 Connect the water supply (detail shown, disassembled and assembled)
Blue marked
Braided hose
to mixer tap
Braided hose
to Command
-Centre inlet
Male - Female
adaptor
(supplied)
T-piece
(supplied)
Male - Male
adaptor
(supplied)
Incoming
mains ambient
water supply
Red marked
Braided hose
to mixer tap
Filter
(supplied)
Connect together
Note correct filter orientation. Valves and
fittings must be sealed with PTFE tape.
!
Isolation valve
1/2” BSP (G 1/2)
Australia UK
15mm - 1/2” BSP(G 1/2)
via Isolation valve
(not supplied)
Incoming
mains hot
water supply
via Isolation valve
(not supplied)
Ambient mains water supply
Hot mains water supply

18 Installation instructions
803341 V3.00 June 2019 - Zip G4 tap range
Technical support
Australia Ph: 1800 460 222 , UK Tel: 0345 6 005 005 email: service@zipindustries .co.uk
Section 7 Vented All-in-One tap installation
7.1 Configure the tap
• See adjacent diagram.
O-ring
Base block
spider
Base block nut
USB cable
Note Make sure the tap location will allow the tap
spout to drain into the sink.
7.2 Cut the hole & mount the tap
• Cut a Ø50mm hole in the worktop / sink.
Ø50mm
• Fit the o-ring to the underside of the tap.
• Pass tubes, hoses and cable through the Ø50mm hole.
• Feed each of the tubes and USB cable evenly between
the legs of the base block spider (see section 7.3).
• Fit the base block spider to the underside of the tap.
• Clamp in position using the base block nut.
• Do not over tighten.
Note All silicone tubes must be cut to size. They must
have a constant fall back to the Command-Centre.
All-in-One
vented

19
Installation instructions
803341 V3.00 June 2019 - Zip G4 tap range
Technical support
Australia Ph: 1800 460 222 , UK Tel: 0345 6 005 005 email: service@zipindustries .co.uk
Section 7 Vented All-in-One tap installation
Red marked braided
hose to MIXER OUT
on Command-Centre
Blue marked
braided hose to
MIXER IN on
Command-Centre
7.3 Position tubes, hoses & base block spider
White marking Blue marking
USB cable
Blue silicone
tube
Red silicone
tube
Clear silicone tube
White marked
braided hose
Blue marked
braided hose
Red
marked
braided
hose
(viewed from underneath)
7.4 Connect the tap
• Connect the tap using the
adjacent diagram.
• Match the braided hoses
& extension tubes colour
markings.
• Attach the braided hoses
(lubricate seals).
• Do not over tighten.
• For sparkling HydroTaps,
connect the supplied Y
connector to the blue silicone
tube, then 1/4” blue and white
pipes as shown.
• For ambient HydroTaps,
connect the supplied
connector to the blue silicone
tube, then 1/4” blue pipe as
shown.
• Attach the USB connector to
the Command-Centre.
White pipe
to SPARKLING
OUTLET on
Command-
Centre
Blue pipe
to CHILLED
OUTLET on
Command-
Centre
SPARKLING
models
Red silicone tube -To
BOILING OUTLET on
Command-Centre
Clear silicone
tube - To VENT on
Command-Centre
Blue silicone tube
-To CHILLED
OUTLET on
Command-Centre
Blue marked
braided hose to
blue marked pipe
on tap
USB plug, connect
to Command-Centre
Red marked braided
hose to red marked
pipe on tap
Plain or white
marked Braided hose
- Flow restrictor
on ambient mains
supply
Plain or white
marked braided
hose to white
marked pipe on tap
AMBIENT
models
Blue pipe to
AMBIENT
OUTLET on
Command-
Centre
OR
OR

20 Installation instructions
803341 V3.00 June 2019 - Zip G4 tap range
Technical support
Australia Ph: 1800 460 222 , UK Tel: 0345 6 005 005 email: service@zipindustries .co.uk
Section 7 Vented All-in-One tap installation
7.5 Connect the water supply (detail shown, disassembled and assembled)
T-piece
(supplied)
Male - Female
adaptor
(supplied)
Filter
(supplied)
Incoming
mains ambient
water supply
Braided hose
to Command
-Centre
mains inlet
Male - Male
adaptor
(supplied)
Male - Male
adaptor
(supplied)
Filter
(supplied)
Flow restrictor
(supplied)
Male - Female
adaptor
(supplied)
Plain
Braided hose
to mixer tap
Connect together
Note correct filter orientation. Valves and
fittings must be sealed with PTFE tape.
!
Isolation valve
1/2” BSP (G 1/2)
Australia UK
15mm - 1/2” BSP(G 1/2)
Ambient mains water supply
via Isolation valve
(not supplied)
Other manuals for HydroTap G4 Series
5
This manual suits for next models
8
Table of contents
Other Zip Kitchen & Bath Fixture manuals
Popular Kitchen & Bath Fixture manuals by other brands

METHVEN
METHVEN Aio Shower Mixer with Fastflow installation guide

Stream33
Stream33 S331HKPO15-CH installation manual

Gessi
Gessi RIFLESSI 44879 manual

Hans Grohe
Hans Grohe Metris Select 2-Spray 73822 1 Series Installation/User Instructions/Warranty

Spectrum Brands
Spectrum Brands Pfister Saxton 016-GL1 Quick installation guide

Lefroy Brooks
Lefroy Brooks M1-5400 Installation, operating, & maintenance instructions