© 2022 Carrier. All rights reserved. 1 / 4 P/N 20-8030-501-2103-08 • ISS 13JUN22
D1073-5
ZP787-3 Addressable Outdoor Manual Call Point
Installation Sheet
1
2
3
4
2 / 4 P/N 20-8030-501-2103-08 • ISS 13JUN22
D1073-5
5
Description
The ZP787-3 Addressable Outdoor Manual Call Point (MCP) is
used to manually initiate a fire alarm. It is designed for outdoor
use and features an IP67 enclosure.
Available models are shown in the table below.
Table 1: Available models
Number
Description
ZP787
-3 Addressable Outdoor Manual Call Point (MCP), Ziton
ZP787
-3S30 Addressable Outdoor Manual Call Point (MCP)
, Chubb
The MCP is shipped with a four-way connector, a test key, and
an EN 54 universal glass.
A red LED on the front of the unit displays its status:
• Off = normal
• Flashing = active
Figures
Figure
1: Product illustration
Figure
2: Wiring diagram
(1) Loop + IN
(2)
Loop − IN
(3) Loop + OUT
(4) Loop − OUT
(5)
Shield
Figure 3: Installing the front housing
(1) Front housing assembly
(2) Backbox
Figure
4: Removing the front housing
Figure 5: Test-reset and glass or resettable element replacement
(1) Test and reset procedure
(2) Replacing the glass or resettable element
Installation
Caution: This product must be installed by qualified personnel
adhering to the CEN/TS 54-14 standard and any applicable
local regulations or ordinances.
This product is designed for surface mounting and cannot be
flush mounted.
P/N 20-8030-501-2103-08 • ISS 13JUN22 3 / 4
D1073-5
To install the MCP, follow these general steps.
1. Set the device address
2. Install the backbox
3. Wire the MCP
4. Install the MCP
Setting the device address
Use the seven-segment DIP switch (SW1) to assign the device
address. Each switch segment represents the value shown
below. The address is the sum of all the switch segments in
the ON position. The switch is used to set the device address
in binary code. The switch may be set to represent any
address from 1 to 127.
For example, to select a device address of 007, set SW1-1,
SW1-2, and SW1-3 to the ON position and the remaining
switch segments to the OFF position.
Installing the backbox
The MCP is designed for surface mounting only. The unit is
comprised of a front housing and a backbox, as shown in
Figure 3.
1. Install the backbox using the screws provided.
2. Bring the field wiring into the backbox.
3. Use the plugs provided to cover unused holes in the
backbox.
Wiring
Make the wiring connections shown in Figure 2.
Installing the front housing
1. Slide the front housing onto the backbox, and then press
to snap them together as shown in Figure 3.
2. For additional security, the front housing can be secured
at the top and bottom using the four screws provided.
3. Test the MCP for proper operation using the test key
shown in Figure 5, item 1.
Removing the front housing
1. If the front housing is secured to the backbox using
screws, remove the four screws (two at the top and two at
the bottom).
2. Insert a screwdriver into the slot as shown in Figure 4, and
then twist the screwdriver to separate the housing from the
backbox.
Maintenance
Figure 5, item 1 illustrates how to perform a test and reset for
the device. Use the supplied test key to perform routine testing
without breaking the glass element. Insert the key to simulate
breaking the glass element; remove the key to reset the call
point automatically.
Figure 5, item 2 shows how to replace the glass or resettable
element.
Caution: When changing the resettable element from glass to
flexi, press the element after installation to confirm the
operation.
Specifications
Oper
ating voltage 19.5 to 20.5 VDC pulsed
Current consumption
Standby
Alarm
0.400 mA
0.450 mA
Addressing method
Seven segment DIP switch
Mounting
Surface
Wiring
Two-core loop
Construction
Material
IP rating
Colour
Weight
Dimensions (H x W x D)
Moulded ABS
IP67
Red
187 g
97.5 × 93 × 27.5 mm
Operating environment
Temperature
Storage temperature
Relative humidity
−25°C to +70°C
−20 to +70°C
10 to 95% noncondensing
Regulatory information
This section provides a summary on the declared performance
according to the Construction Products Regulation
(EU) 305/2011 and Delegated Regulations (EU) 157/2014 and
(EU) 574/2014.
For detailed information, see the product Declaration of
Performance (available at firesecurityproducts.com).
Conformity
Notified/Approved
body 2831 0832
Manufacturer
Honeywell Life Safety – Romania,
Str Salmilor, Nr 2 bis.,
Lugoj, Romania RO 305500.
Authorized EU manufacturing
representative:
Carrier Fire & Security B.V.,
Kelvinstraat 7, 6003 DH Weert,
Netherlands.
Year of first CE marking
19
Year of first
UKCA marking 22
Declaration of Performance
number
360-4211-0799
EN 54
EN 54-11
Product type
Type A: for outdoor use
ON
1 2 3 4 5 6 7
SW1
1 2 4 8 16 32 64
4 / 4 P/N 20-8030-501-2103-08 • ISS 13JUN22
D1073-5
Product identification
See model number on product
identification label
Intended use
See the product Declaration of
Performance
Declared performance/s
See the product Declaration of
Performance
2012/19/EU (WEEE Directive): Products
marked with this symbol cannot be
disposed of as unsorted municipal waste
in the European Union. For proper
recycling, return this product to your local
supplier upon the purchase of equivalent
new equipment, or dispose of it at
designated collection points. For more
information see: recyclethis.info.
Contact information and product
documentation
For contact information or to download the latest product
documentation, visit firesecurityproducts.com.

Other Ziton Security System manuals

Ziton ZP755V Assembly instructions

Ziton

Ziton ZP755V Assembly instructions

Ziton ZP755HAV-2 Assembly instructions

Ziton

Ziton ZP755HAV-2 Assembly instructions

Ziton ZP880 Series User manual

Ziton

Ziton ZP880 Series User manual

Popular Security System manuals by other brands

Photo Sentinel MINI quick start guide

Photo Sentinel

Photo Sentinel MINI quick start guide

Q-See QC308 Specifications

Q-See

Q-See QC308 Specifications

Paradox Esprit 748 Express Programming guide

Paradox

Paradox Esprit 748 Express Programming guide

HIK VISION Blazer Express 16 quick start guide

HIK VISION

HIK VISION Blazer Express 16 quick start guide

Easy@Home IN03E instruction sheet

Easy@Home

Easy@Home IN03E instruction sheet

Security Command XR500 Series user guide

Security Command

Security Command XR500 Series user guide

Phase3 SECURITY SYSTEM manual

Phase3

Phase3 SECURITY SYSTEM manual

GSM Activate GSM 4G AUTO DIALLER PLUS manual

GSM Activate

GSM Activate GSM 4G AUTO DIALLER PLUS manual

Multi-COM MC5P Installer manual

Multi-COM

Multi-COM MC5P Installer manual

HIK VISION AX PRO Series Training

HIK VISION

HIK VISION AX PRO Series Training

B.F. Goodrich TCAS791 pilot's guide

B.F. Goodrich

B.F. Goodrich TCAS791 pilot's guide

Paradox Digiplex DGP-848 Programming guide

Paradox

Paradox Digiplex DGP-848 Programming guide

Stonesoft stonegate 5.2 installation guide

Stonesoft

Stonesoft stonegate 5.2 installation guide

Tyco PG9938 installation instructions

Tyco

Tyco PG9938 installation instructions

Biamp Vocia CI-1 Operation manual

Biamp

Biamp Vocia CI-1 Operation manual

TECO Astra-2331 user guide

TECO

TECO Astra-2331 user guide

Radio Shack 49-1011 user manual

Radio Shack

Radio Shack 49-1011 user manual

SkyLink DIAL-ALERT AD-433S Guide

SkyLink

SkyLink DIAL-ALERT AD-433S Guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.