P/N 20-8030-501-2103-08 • ISS 13JUN22 3 / 4
D1073-5
To install the MCP, follow these general steps.
1. Set the device address
2. Install the backbox
3. Wire the MCP
4. Install the MCP
Setting the device address
Use the seven-segment DIP switch (SW1) to assign the device
address. Each switch segment represents the value shown
below. The address is the sum of all the switch segments in
the ON position. The switch is used to set the device address
in binary code. The switch may be set to represent any
address from 1 to 127.
For example, to select a device address of 007, set SW1-1,
SW1-2, and SW1-3 to the ON position and the remaining
switch segments to the OFF position.
Installing the backbox
The MCP is designed for surface mounting only. The unit is
comprised of a front housing and a backbox, as shown in
Figure 3.
1. Install the backbox using the screws provided.
2. Bring the field wiring into the backbox.
3. Use the plugs provided to cover unused holes in the
backbox.
Wiring
Make the wiring connections shown in Figure 2.
Installing the front housing
1. Slide the front housing onto the backbox, and then press
to snap them together as shown in Figure 3.
2. For additional security, the front housing can be secured
at the top and bottom using the four screws provided.
3. Test the MCP for proper operation using the test key
shown in Figure 5, item 1.
Removing the front housing
1. If the front housing is secured to the backbox using
screws, remove the four screws (two at the top and two at
the bottom).
2. Insert a screwdriver into the slot as shown in Figure 4, and
then twist the screwdriver to separate the housing from the
backbox.
Maintenance
Figure 5, item 1 illustrates how to perform a test and reset for
the device. Use the supplied test key to perform routine testing
without breaking the glass element. Insert the key to simulate
breaking the glass element; remove the key to reset the call
point automatically.
Figure 5, item 2 shows how to replace the glass or resettable
element.
Caution: When changing the resettable element from glass to
flexi, press the element after installation to confirm the
operation.
Specifications
ating voltage 19.5 to 20.5 VDC pulsed
Standby
Alarm
0.400 mA
0.450 mA
Seven segment DIP switch
Surface
Two-core loop
Material
IP rating
Colour
Weight
Dimensions (H x W x D)
Moulded ABS
IP67
Red
187 g
97.5 × 93 × 27.5 mm
Temperature
Storage temperature
Relative humidity
−25°C to +70°C
−20 to +70°C
10 to 95% noncondensing
Regulatory information
This section provides a summary on the declared performance
according to the Construction Products Regulation
(EU) 305/2011 and Delegated Regulations (EU) 157/2014 and
(EU) 574/2014.
For detailed information, see the product Declaration of
Performance (available at firesecurityproducts.com).
body 2831 0832
Honeywell Life Safety – Romania,
Str Salmilor, Nr 2 bis.,
Lugoj, Romania RO 305500.
Authorized EU manufacturing
representative:
Carrier Fire & Security B.V.,
Kelvinstraat 7, 6003 DH Weert,
Netherlands.
19
UKCA marking 22
Declaration of Performance
number
360-4211-0799
EN 54-11
Type A: for outdoor use
ON
1 2 3 4 5 6 7
SW1
1 2 4 8 16 32 64