© 2022 Carrier. All rights reserved. 1 / 4 P/N 20-8030-501-2103-08 • ISS 13JUN22
D1073-5
ZP787-3 Addressable Outdoor Manual Call Point
Installation Sheet
1
2
3
4
2 / 4 P/N 20-8030-501-2103-08 • ISS 13JUN22
D1073-5
5
Description
The ZP787-3 Addressable Outdoor Manual Call Point (MCP) is
used to manually initiate a fire alarm. It is designed for outdoor
use and features an IP67 enclosure.
Available models are shown in the table below.
Table 1: Available models
Number
Description
ZP787
-3 Addressable Outdoor Manual Call Point (MCP), Ziton
ZP787
-3S30 Addressable Outdoor Manual Call Point (MCP)
, Chubb
The MCP is shipped with a four-way connector, a test key, and
an EN 54 universal glass.
A red LED on the front of the unit displays its status:
• Off = normal
• Flashing = active
Figures
Figure
1: Product illustration
Figure
2: Wiring diagram
(1) Loop + IN
(2)
Loop − IN
(3) Loop + OUT
(4) Loop − OUT
(5)
Shield
Figure 3: Installing the front housing
(1) Front housing assembly
(2) Backbox
Figure
4: Removing the front housing
Figure 5: Test-reset and glass or resettable element replacement
(1) Test and reset procedure
(2) Replacing the glass or resettable element
Installation
Caution: This product must be installed by qualified personnel
adhering to the CEN/TS 54-14 standard and any applicable
local regulations or ordinances.
This product is designed for surface mounting and cannot be
flush mounted.
P/N 20-8030-501-2103-08 • ISS 13JUN22 3 / 4
D1073-5
To install the MCP, follow these general steps.
1. Set the device address
2. Install the backbox
3. Wire the MCP
4. Install the MCP
Setting the device address
Use the seven-segment DIP switch (SW1) to assign the device
address. Each switch segment represents the value shown
below. The address is the sum of all the switch segments in
the ON position. The switch is used to set the device address
in binary code. The switch may be set to represent any
address from 1 to 127.
For example, to select a device address of 007, set SW1-1,
SW1-2, and SW1-3 to the ON position and the remaining
switch segments to the OFF position.
Installing the backbox
The MCP is designed for surface mounting only. The unit is
comprised of a front housing and a backbox, as shown in
Figure 3.
1. Install the backbox using the screws provided.
2. Bring the field wiring into the backbox.
3. Use the plugs provided to cover unused holes in the
backbox.
Wiring
Make the wiring connections shown in Figure 2.
Installing the front housing
1. Slide the front housing onto the backbox, and then press
to snap them together as shown in Figure 3.
2. For additional security, the front housing can be secured
at the top and bottom using the four screws provided.
3. Test the MCP for proper operation using the test key
shown in Figure 5, item 1.
Removing the front housing
1. If the front housing is secured to the backbox using
screws, remove the four screws (two at the top and two at
the bottom).
2. Insert a screwdriver into the slot as shown in Figure 4, and
then twist the screwdriver to separate the housing from the
backbox.
Maintenance
Figure 5, item 1 illustrates how to perform a test and reset for
the device. Use the supplied test key to perform routine testing
without breaking the glass element. Insert the key to simulate
breaking the glass element; remove the key to reset the call
point automatically.
Figure 5, item 2 shows how to replace the glass or resettable
element.
Caution: When changing the resettable element from glass to
flexi, press the element after installation to confirm the
operation.
Specifications
Oper
ating voltage 19.5 to 20.5 VDC pulsed
Current consumption
Standby
Alarm
0.400 mA
0.450 mA
Addressing method
Seven segment DIP switch
Mounting
Surface
Wiring
Two-core loop
Construction
Material
IP rating
Colour
Weight
Dimensions (H x W x D)
Moulded ABS
IP67
Red
187 g
97.5 × 93 × 27.5 mm
Operating environment
Temperature
Storage temperature
Relative humidity
−25°C to +70°C
−20 to +70°C
10 to 95% noncondensing
Regulatory information
This section provides a summary on the declared performance
according to the Construction Products Regulation
(EU) 305/2011 and Delegated Regulations (EU) 157/2014 and
(EU) 574/2014.
For detailed information, see the product Declaration of
Performance (available at firesecurityproducts.com).
Conformity
Notified/Approved
body 2831 0832
Manufacturer
Honeywell Life Safety – Romania,
Str Salmilor, Nr 2 bis.,
Lugoj, Romania RO 305500.
Authorized EU manufacturing
representative:
Carrier Fire & Security B.V.,
Kelvinstraat 7, 6003 DH Weert,
Netherlands.
Year of first CE marking
19
Year of first
UKCA marking 22
Declaration of Performance
number
360-4211-0799
EN 54
EN 54-11
Product type
Type A: for outdoor use
ON
1 2 3 4 5 6 7
SW1
1 2 4 8 16 32 64
4 / 4 P/N 20-8030-501-2103-08 • ISS 13JUN22
D1073-5
Product identification
See model number on product
identification label
Intended use
See the product Declaration of
Performance
Declared performance/s
See the product Declaration of
Performance
2012/19/EU (WEEE Directive): Products
marked with this symbol cannot be
disposed of as unsorted municipal waste
in the European Union. For proper
recycling, return this product to your local
supplier upon the purchase of equivalent
new equipment, or dispose of it at
designated collection points. For more
information see: recyclethis.info.
Contact information and product
documentation
For contact information or to download the latest product
documentation, visit firesecurityproducts.com.

Other Ziton Security System manuals

Ziton ZP880 Series User manual

Ziton

Ziton ZP880 Series User manual

Ziton ZP755V Assembly instructions

Ziton

Ziton ZP755V Assembly instructions

Ziton ZP755HAV-2 Assembly instructions

Ziton

Ziton ZP755HAV-2 Assembly instructions

Popular Security System manuals by other brands

Mircom Flex-Net Phase II Application guide

Mircom

Mircom Flex-Net Phase II Application guide

Klaxon Nexus AC Sounder & Sounder-Beacon installation instructions

Klaxon

Klaxon Nexus AC Sounder & Sounder-Beacon installation instructions

Swann DVR9-4200 Specifications

Swann

Swann DVR9-4200 Specifications

Dahua PZC-421 user manual

Dahua

Dahua PZC-421 user manual

BT Redcare UC-351GP/E-UK Installation, maintenance and operation manual

BT Redcare

BT Redcare UC-351GP/E-UK Installation, maintenance and operation manual

Bosch ICP-AMAX4-P2-EN quick start guide

Bosch

Bosch ICP-AMAX4-P2-EN quick start guide

goSmarthome X1-3G-RC-101 user manual

goSmarthome

goSmarthome X1-3G-RC-101 user manual

Bosch D1260 Series owner's manual

Bosch

Bosch D1260 Series owner's manual

Pyronix Enforcer 64 installation guide

Pyronix

Pyronix Enforcer 64 installation guide

Panasonic 1735 Technical description

Panasonic

Panasonic 1735 Technical description

CDVI SOLARKPW installation manual

CDVI

CDVI SOLARKPW installation manual

Honeywell L5200 Series user guide

Honeywell

Honeywell L5200 Series user guide

HailBrain ProGuard800 Series Quick installation guide

HailBrain

HailBrain ProGuard800 Series Quick installation guide

Abrams TORNADO 3 Installation and configuration manual

Abrams

Abrams TORNADO 3 Installation and configuration manual

Vanderbilt SPCV440 manual

Vanderbilt

Vanderbilt SPCV440 manual

Bunker Hill Security 62368 Owner's manual & safety instructions

Bunker Hill Security

Bunker Hill Security 62368 Owner's manual & safety instructions

Britax BF920 Series Installation & operation manual

Britax

Britax BF920 Series Installation & operation manual

Electronics Line Summit 3208GLD user manual

Electronics Line

Electronics Line Summit 3208GLD user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.