Zte ZXDU58 B900 Technical specifications

ZXDU58B900
DCPowerSystem
ProductDescription
Version:V4.5R01M01
ZTECORPORATION
NO.55,Hi-techRoadSouth,ShenZhen,P .R.China
Postcode:518057
Tel:+86-755-26771900
Fax:+86-755-26770801
URL:http://ensupport.zte.com.cn
E-mail:[email protected]

LEGALINFORMATION
Copyright©2012ZTECORPORATION.
Thecontentsofthisdocumentareprotectedbycopyrightlawsandinternationaltreaties.Anyreproductionor
distributionofthisdocumentoranyportionofthisdocument,inanyformbyanymeans,withoutthepriorwritten
consentofZTECORPORATIONisprohibited.Additionally,thecontentsofthisdocumentareprotectedby
contractualcondentialityobligations.
Allcompany,brandandproductnamesaretradeorservicemarks,orregisteredtradeorservicemarks,ofZTE
CORPORATIONoroftheirrespectiveowners.
Thisdocumentisprovided“asis”,andallexpress,implied,orstatutorywarranties,representationsorconditions
aredisclaimed,includingwithoutlimitationanyimpliedwarrantyofmerchantability,tnessforaparticularpurpose,
titleornon-infringement.ZTECORPORATIONanditslicensorsshallnotbeliablefordamagesresultingfromthe
useoforrelianceontheinformationcontainedherein.
ZTECORPORATIONoritslicensorsmayhavecurrentorpendingintellectualpropertyrightsorapplications
coveringthesubjectmatterofthisdocument.ExceptasexpresslyprovidedinanywrittenlicensebetweenZTE
CORPORATIONanditslicensee,theuserofthisdocumentshallnotacquireanylicensetothesubjectmatter
herein.
ZTECORPORATIONreservestherighttoupgradeormaketechnicalchangetothisproductwithoutfurthernotice.
UsersmayvisitZTEtechnicalsupportwebsitehttp://ensupport.zte.com.cntoinquirerelatedinformation.
TheultimaterighttointerpretthisproductresidesinZTECORPORATION.
RevisionHistory
RevisionNo.RevisionDateRevisionReason
R1.02012-12-05Firstedition
SerialNumber:SJ-20121116145308-001
PublishingDate:2012-12-05(R1.0)
SJ-20121116145308-001|2012-12-05(R1.0)ZTEProprietaryandCondential

Contents
AboutThisManual.........................................................................................I
Chapter1SystemOverview......................................................................1-1
1.1SystemIntroduction............................................................................................1-1
1.2SystemFeatures................................................................................................1-1
Chapter2SystemStructureandComponents........................................2-1
2.1SystemStructure................................................................................................2-1
2.2ZXD030S480Rectier.......................................................................................2-3
2.3CentralizedSupervisionUnit...............................................................................2-5
2.4SignalInterfacesontheSIB................................................................................2-6
Chapter3SystemSpecications..............................................................3-1
3.1EnvironmentSpecications.................................................................................3-1
3.2T echnicalSpecications......................................................................................3-1
3.3ComplianceStandards.......................................................................................3-3
Chapter4ZXD030S480RectierSpecications.....................................4-1
4.1T echnicalSpecications......................................................................................4-1
4.2InternalProtectionFunctions...............................................................................4-2
4.3OutputPowerControl.........................................................................................4-5
Chapter5CongurationList.....................................................................5-1
Chapter6AlarmList..................................................................................6-1
AppendixAElectricalConnectionDiagram...........................................A-1
Glossary..........................................................................................................I
I
SJ-20121116145308-001|2012-12-05(R1.0)ZTEProprietaryandCondential

II
SJ-20121116145308-001|2012-12-05(R1.0)ZTEProprietaryandCondential

AboutThisManual
Purpose
ThismanualappliestotheZXDU58B900(V4.5R01M01)DCPowerSystem(the
ZXDU58B900systemforshort).TheZXDU58B900systemprovidespowerfor-48V
communicationsequipment.
Thismanualdescribesthestructure,characteristics,andspecicationsoftheZXDU58
B900system.
IntendedAudience
Thismanualisintendedfor:
lPlanningengineers
lMaintenanceengineers
WhatIsinThisManual
Thismanualcontainsthefollowingchapters/appendices:
Chapter/AppendixSummary
1,SystemOverviewIntroducestheZXDU58B900systemanddescribesthe
systemfeatures.
2,SystemStructureandComponentsDescribesthesystemstructure,theZXD030S480rectier,
theCentralizedSupervisionUnit(CSU),andsignalinterfaces
ontheSignalInterfacesBoard(SIB).
3,SystemSpecicationsDescribesenvironmentspecications,technical
specications,andcompliancestandards.
4,ZXD030S480Rectier
Specications
Describesthetechnicalspecications,internalprotection
functions,andoutputpowercontroloftheZXD030S480
(V1.0)rectier.
5,CongurationListDescribesthesystemconguration.
6,AlarmListDescribesthealarmnames,defaultalarmlevels,andoutput
relays.
A,ElectricalConnectionDiagramProvidestheelectricalconnectiondiagramoftheZXDU58
B900system.
I
SJ-20121116145308-001|2012-12-05(R1.0)ZTEProprietaryandCondential

Conventions
Thismanualusesthefollowingtypographicalconventions:
TypefaceMeaning
ItalicsVariablesincommands.Itmayalsorefertootherrelatedmanualsand
documents.
BoldMenus,menuoptions,functionnames,inputelds,optionbuttonnames,check
boxes,drop-downlists,dialogboxnames,windownames,parameters,and
commands.
Note:providesadditionalinformationaboutacertaintopic.
II
SJ-20121116145308-001|2012-12-05(R1.0)ZTEProprietaryandCondential

Chapter1
SystemOverview
TableofContents
SystemIntroduction....................................................................................................1-1
SystemFeatures........................................................................................................1-1
1.1SystemIntroduction
TheZXDU58B900systemisdesignedtobeinstalledinacabinet.Itis19inchesinwidth
and3Uinheight.
lThesystemcanprovidepowerfor-48Vcommunicationsequipment.
lACinputmode:Single-phasethree-wire(L/N/PE),220V(phasevoltage)
lDCoutputcurrent
Whenfullycongured,thesystemisequippedwiththreeZXD030S480rectiersand
canprovideamaximumoutputcurrentof90A.
FortheappearanceanddimensionsoftheZXDU58B900system,seeFigure1-1.
Figure1-1ZXDU58B900Appearance
1.2SystemFeatures
TheZXDU58B900systemhasthefollowingfeatures:
lAwiderangeofinputphasevoltage(90VAC-264VAC)makesthesystemsuitable
forareaswithunstablevoltage.
lTheZXDU58B900chassiscontainsthepowerdistributionunit,rectiers,andCSU.
lTheZXDU58B900systemsupportsmultiplenetworkingmodes,suchasRS232,
RS485.
lHot-pluggablerectiers.
lIntelligentCSU.
lHighreliabilitywithMeanTimeBetweenFailures(MTBF)≥2.2×105h.
1-1
SJ-20121116145308-001|2012-12-05(R1.0)ZTEProprietaryandCondential

ZXDU58B900ProductDescription
lCompactstructuredesign.TheZXDU58B900chassisis3Uinheightand19inches
inwidth.Itisdesignedtobeinstalledintoacabinet.
1-2
SJ-20121116145308-001|2012-12-05(R1.0)ZTEProprietaryandCondential

Chapter2
SystemStructureand
Components
TableofContents
SystemStructure........................................................................................................2-1
ZXD030S480Rectier...............................................................................................2-3
CentralizedSupervisionUnit......................................................................................2-5
SignalInterfacesontheSIB.......................................................................................2-6
2.1SystemStructure
ForthestructureoftheZXDU58B900system,seeFigure2-1.
Foradescriptionofthesystemcomponents,refertoT able2-1.
Figure2-1StructureoftheZXDU58B900System
1.Powerdistributionunit
2.ZXD030S480rectifiers
3.CentralizedSupervision
Unit(CSU)
4.Electricalconnection
terminals
5.SignalInterfaceBoard
(SIB)
Table2-1SystemComponentDescription
S.N.ComponentDescription
1PowerdistributionunitProvidesACpowerdistributionandDCpower
distributiontothesystem.
2-1
SJ-20121116145308-001|2012-12-05(R1.0)ZTEProprietaryandCondential

ZXDU58B900ProductDescription
S.N.ComponentDescription
2ZXD030S480rectiersConvertACtoDC.
Forfurtherdetails,referto2.2ZXD030S480
Rectier.
3CentralizedSupervisionUnit(CSU)Collectsthesystemoperationdataandmanages
thesystem.
Forfurtherdetails,referto2.3Centralized
SupervisionUnit.
4ElectricalconnectionterminalsConnectACinput,ACoutput,DCinput,andDC
outputcables.
5SignalInterfaceBoard(SIB)Providesinterfacesforsupervisionand
networking.
Forfurtherdetails,referto2.4SignalInterfaces
ontheSIB.
ThepowerdistributionunitisshowninFigure2-2.Foradescriptionofthepower
distributionunit,refertoTable2-2.
Figure2-2PowerDistributionUnit
1.ACinputcircuitbreaker
2.ACoutputcircuitbreaker
3.ACSPD
4.DCoutputcircuitbreakers
5.Batterycircuitbreaker
Table2-2PowerDistributionUnitDescription
S.N.ItemDescription
1ACinputcircuitbreakerlToturnon/offACinputlivewires.
lWhentheACinputbreakeristurnedon,therectiers
automaticallyturnon.
2ACoutputcircuitbreakerT oturnon/offACoutputofZXDU58B900.
3ACSPDProvidesACinputsurgeprotection.
4DCoutputcircuitbreakersToturnon/offDCoutputwithoverloadprotection.
5BatterycircuitbreakerToturnon/offbatteryinput.
TheelectricalconnectionterminalsareshowninFigure2-3.Foradescriptionofthe
electricalconnectionterminals,refertoT able2-3.
2-2
SJ-20121116145308-001|2012-12-05(R1.0)ZTEProprietaryandCondential

Chapter2SystemStructureandComponents
Figure2-3ElectricalConnectionTerminals
1.Batteryinputconnection
terminals(-48V)
2.DCoutputconnection
terminals(-48V,+)
3.Batteryinputconnection
terminals(+)
4.ACoutputconnection
terminal(L)
5.ACinputconnection
terminal(L)
6.ACinput/outputconnection
terminal(N)
7.ACinputconnection
terminal(PE)
Table2-3ElectricalConnectionTerminalsDescription
S.N.ItemDescription
1Batteryinputconnectionterminals(-48V)Connectbatteryinput(-48V)cables.
2DCoutputconnectionterminals(-48V,+)ConnectDCoutputcables.
3Batteryinputconnectionterminals(+)Connectbatteryinput(+)cables.
4ACoutputconnectionterminal(L)ConnectsACoutputlivewire.
5ACinputconnectionterminal(L)ConnectsACinputlivewire.
6ACinput/outputconnectionterminal(N)ConnectsACinput/outputneutralwire.
7ACinputconnectionterminal(PE)ConnectsACinputPEwire.
2.2ZXD030S480Rectier
ThissetionisapplicabletoZXD030S480(V1.0)rectier.
TheZXD030S480rectiersconvertACtoDC,powerDCloadsandchargethebatteries.
Appearance
FortheappearanceoftheZXD030S480rectier,seeFigure2-4.
2-3
SJ-20121116145308-001|2012-12-05(R1.0)ZTEProprietaryandCondential

ZXDU58B900ProductDescription
Figure2-4ZXD030S480(V1.0)Rectier
Indicators
Theindicatorsdisplaytheoperationalstatusoftherectier.Fortheindicatorsofthe
rectier,seeFigure2-5.Foradescriptionoftheworkingstatusoftheindicators,refer
toTable2-4.
lNormally,onlythepowerindicatorislit.
lIncasethatoutputcurrentlimitoccurs,thepowerindicatorashes.
lIncasethatasystemfaultoccurs,thealarmindicatorislit.Forexample,incaseof
under-voltageprotection,thepowerindicatorisnotlitandthealarmindicatorislit.
lIncasearectierfaultoccurs,thefaultindicatorislit.
lWhenthepowerandalarmindicatorsashatthesametime,aprogramisbeing
downloaded.
Figure2-5RectierIndicators
Table2-4StatusIndication
IndicatorNormalStatusAbnormal
Status
Indication
NotlitNoACinputortheACinputvoltageislower
than75V.
Power(green)
Lit
FlashingOutputcurrentlimit
2-4
SJ-20121116145308-001|2012-12-05(R1.0)ZTEProprietaryandCondential

Chapter2SystemStructureandComponents
IndicatorNormalStatusAbnormal
Status
Indication
LitlACinputover/under-voltage
lPFCoutputover/under-voltage
lOver-temperature
Alarm(yellow)
Notlit
FlashinglFastashing:Thecommunication
betweentherectierandtheCSUis
interrupted.
lSlowashing:Therectierisinthe
sleepmode.
Fault(red)
NotlitLitlDCoutputover-voltage/current
lOutputfuseblows
lFanfault
lOtherfault
2.3CentralizedSupervisionUnit
TheCentralizedSupervisionUnit(B900-CSU)managesthepowerdistributionunit,
rectiersandbatteriesoftheZXDU58B900system.
Functions
lGivesanaudibleandvisualalarmandprovidestheprotectionfunctionwhenthe
systemisfaulty.
lCollectstheoperationaldataandmonitorstheoperationsofthesystem.
lPerformsadvancedbatterymanagementwithprotectionfunctions.
lTransmitsdatatothebackgroundSupervisionCenter(SC)andreceivescommands
fromtheSC.Inthisway,thesystemcanbemonitoredremotely.
Appearance
FortheappearanceoftheCSU,seeFigure2-6.
Figure2-6CentralizedSupervisionUnit(B900-CSU)
1.LED2.Indicators3.Resetbutton
2-5
SJ-20121116145308-001|2012-12-05(R1.0)ZTEProprietaryandCondential

ZXDU58B900ProductDescription
4.Buttons
5.Powerswitch
6.Handle(Fasteningscrew)
7.Interface
Indicators
IndicatorsdisplaytheworkingstatusoftheCSUandthesystem.Fortheappearanceof
theindicators,seeFigure2-7.Foradescriptionofindicators,refertoT able2-5.
Figure2-7CSUIndicators
Table2-5CSUIndicators
IndicatorStatusIndication
PWR
Power
Lit(green)TheCSUispoweredon
RUN
Run
Flash(green)TheCSUisoperatingnormally
EQU
Equalizedcharge
Lit(green)Thebatteryequalizedchargeisintheprocess
COMM1
Communication1Flash(green)TheCSUiscommunicatingwiththerectiers
COMM2
Communication2Flash(green)TheCSUiscommunicatingwiththebackgroundsupervision
center
ALM
AlarmFlash(red)Afaultoccurstothesystem
ButtonsandLCD
ThebuttonsandtheLCDoftheCSUenabletheuserstoqueryoperationaldataofthe
ZXDU58B900system,setparameters,andcontroltheoperationoftheZXDU58B900
system.
Thebuttonnamesareasfollows:
l▲/▼:up/down
lEnter:enter
lEsc:escape
lRST:resetstheCSU
2.4SignalInterfacesontheSIB
TheSignalInterfaceBoard(SIB)providescommunicationinterfacesandsignalinterfaces.
2-6
SJ-20121116145308-001|2012-12-05(R1.0)ZTEProprietaryandCondential

Chapter2SystemStructureandComponents
Figure2-8showstheSIB.Table2-6describestheSIBinterfaces.
Figure2-8SIBInterfaces
Table2-6SIBInterfaceDescription
InterfaceDescription
Batterydetectioninterfacesandenvironmentdetectioninterfaces
X1BatterytemperatureConnectstotemperaturesensorofbatterypack.
X3AmbienttemperatureConnectstoenvironmenttemperaturesensor.
X4DoorstatusalarmConnectstodoorentrancedetectsensor.
X5FloodalarmConnectstoooddetectsensor.
X6SmokealarmConnectstosmokedetectsensor.
Inputandoutputrelayinterfaces
2-7
SJ-20121116145308-001|2012-12-05(R1.0)ZTEProprietaryandCondential

ZXDU58B900ProductDescription
InterfaceDescription
X7Inputrelay1and2
X8Inputrelay3and4
Thefourinputrelayscanbecustomizedbytheuserforalarm
input.
ThedefaultalarmstatusoftheinputrelaysintheCSUare
“close”.
Outputrelay1-Output
relay7
lTheoutputrelays1to7correspondtothesoftwarecodes
A1toA7intheCSU.
lForthedefaultoutputrelaysforthealarms,refertothe
AlarmList.
lUserscancustomizetheseoutputrelaysforalarmoutput.
X9
Outputrelay8ThisoutputrelayisreservedforCSUfault.
Communicationinterfaces
X10RS485/RS422TheinterfaceforRS485/RS422communication.
X11RS232TheinterfaceforRS232communication.
2-8
SJ-20121116145308-001|2012-12-05(R1.0)ZTEProprietaryandCondential

Chapter3
SystemSpecications
TableofContents
EnvironmentSpecications........................................................................................3-1
TechnicalSpecications.............................................................................................3-1
ComplianceStandards...............................................................................................3-3
3.1EnvironmentSpecications
ForthedescriptionofenvironmentspecicationsoftheZXDU58B900system,referto
Table3-1.
Table3-1EnvironmentSpecications
ItemSpecication
Operationaltemperature-5℃to+45℃,(+15℃to+25℃,recommended)
Storagetemperature-40℃to+70℃
Relativetemperature10%to90%(non-condensing),40%to60%recommended
Altitudel0to2000m:100%outputpower
l2000mto3000m:Thepowerderatingpercentageis
1%whenthealtitudeincreasesby100m.
OtherrequirementslIndoors
lThecabinetshouldbestableanderect.
lNoexplosionhazard,noshakeorjolt.
lNeverinstalltheequipmentwherethereisariskofliquid
orobjectsfallingintothetopoftheequipment.
lNoconductivedustorcorrosivegas.
lNostrongElectromagneticInterference(EMI).
3.2TechnicalSpecications
TheZXDU58B900systemsatisesthefollowingtechnicalspecications.
lForadescriptionofthesystemspecications,refertoT able3-2.
lForadescriptionoftheACelectricalspecications,refertoT able3-3.
lForadescriptionoftheDCelectricalspecications,refertoT able3-4.
lForadescriptionofthestructurespecications,refertoT able3-5.
3-1
SJ-20121116145308-001|2012-12-05(R1.0)ZTEProprietaryandCondential

ZXDU58B900ProductDescription
Table3-2SystemSpecications
ItemSpecication
Ratedoutputcurrent90A(whenfullycongured)
Systemefciency≥93%
Noise≤55dB(A)
MonitoringnetworkingmodeRS232/RS485serialport,andtransparenttransmissionwiththe
communicationequipment
MeanTimeBetween
Failures(MTBF)
≥2.2×105h
Table3-3ACElectricalSpecications
ItemSpecication
ACinputmodeSingle-phasethree-wire(L/N/PE)
ACinputvoltagelRatedinputvoltage:100VAC-240VAC
lRange:90VAC-264VAC
ACinputfrequency50Hz/60Hz
MaximumACinputcurrent50A
ACinputpowerfactor≥0.99(withfullload)
ACSPDClassC,Imax=40kA(8/20µs)
ACprotectionfeatureslACinputover-voltageprotection
lACinputunder-voltageprotection
lACinputover-currentprotection
Table3-4DCElectricalSpecications
ItemSpecication
DCoutputvoltagelRatedoutputvoltage:-53.5V
lRange:-42Vto-58V(adjustableintheCSU)
DCSPDImax=15kA(8/20µs)
Sourceeffect≤0.1%
Loadeffect≤0.5%
Weightednoisevoltage<1mV
Peak-peaknoisevoltage≤100mV(20MHzbandwidth)
Regulatedvoltageprecision≤0.6%
DCvoltagedropinsidethe
cabinet
<500mV
3-2
SJ-20121116145308-001|2012-12-05(R1.0)ZTEProprietaryandCondential

Chapter3SystemSpecications
ItemSpecication
DCprotectionfeatureslDCoutputover-voltageprotection
lDCoutputunder-voltageprotection
lBatteryunder-voltageprotection
Batteryunder-voltage
protection
lLLVD1
lLLVD2
Table3-5StructureSpecications
ItemDescription
Chassisdimensions133mm×483mm×320mm(H×W×D)
ChassisweightApproximately11.5kg(excludingtherectiersandCSU)
ZXD030S480Rectier
weight
1.6kg/set,threesets(whenfullycongured)
CSUweight1.6kg
InstallationmodeInstallationinacabinet/rack
3.3ComplianceStandards
EMCStandards
ThissystemisincompliancewiththefollowingElectromagneticCompatibility(EMC)
standards:
lDIN/EN55022
lIEC61000
SafetyStandards
ThissystemisincompliancewiththeUL/IEC/EN60950standards.
OtherStandards
Thissystemisalsoincompliancewiththefollowingstandards:
lCE
lTheRestrictionofHazardousSubstances(RoHS)directive(2002/95/EC)ofthe
EuropeanUnion.
lThisdevicecomplieswithPart15oftheFCCRulesandissubjecttothefollowing
twoconditions:(1)thisdevicemaynotcauseharmfulinterference,and(2)this
devicemustacceptanyinterferencereceived,includinginterferencethatmaycause
undesiredoperations.
3-3
SJ-20121116145308-001|2012-12-05(R1.0)ZTEProprietaryandCondential

ZXDU58B900ProductDescription
Thispageintentionallyleftblank.
3-4
SJ-20121116145308-001|2012-12-05(R1.0)ZTEProprietaryandCondential
Table of contents
Other Zte Power Supply manuals