manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Absolute Process Instruments
  6. •
  7. Industrial Equipment
  8. •
  9. Absolute Process Instruments API 1400 G User manual

Absolute Process Instruments API 1400 G User manual

Input: 2 or 3 Wire RTD
Output: One 8 Amp DPDT Relay or Two 8 Amp SPDT Relays
OAutomatic Leadwire Compensation
OField Adjustable Setpoints
OPlug-In Design for Fast Installation
OInput LoopTracker®and Alarm Status LEDs
OAlarm Test Button
QProcess Limit Backup Alarm
QTemperature Alarm
QOver, Under, Out-of-Range Alarm
Model Input Standard Alarm Configuration Power
API 1400 G Factory ranged, specify
RTD type,
RTD curve,
temperature range in °F or °C
Single setpoint one DPDT relay
HI alarm, normal acting
115 VAC
API 1400 G A230 230 VAC
API 1400 G P 85-265 VAC or 60-300 VDC
API 1400 G D 9-30 VDC
API 1420 G Factory ranged, specify
RTD type,
RTD curve,
temperature range in °F or °C
2 setpoints, 2 SPDT relays
HI/LO alarms, normal acting
115 VAC
API 1420 G A230 230 VAC
API 1420 G P 85-265 VAC or 60-300 VDC
API 1420 G D 9-30 VDC
Temperature Input
Factory configured, please specify the following
Resistance at 0°C, curve, temperature range
RTD types: 10 Ωto 2000 Ωincluding 100 Ω0.00385
DIN, 100 Ω0.003916, 100 Ω0.00392,
10 ΩCu, 1000 ΩNi-Fe, 120 ΩNi
Temp. range: °F or °C
100°F (55°C) min. span or consult factory
Leadwire Compensation
< ±0.05% of span per 1 Ωchange in leadwire resistance
Excitation Current
10 Ω: 10 mA 100 Ω: 5 mA
1000 Ω: 0.5 mA 2000 Ω: 0.2 mA
LoopTracker
Variable brightness LED indicates input level and status
API 1400 G Relay Output
Two SPDT form C contact sets operating in unison as one
DPDT contact set
One setpoint, 12 turn potentiometer, 0-100% of span
Factory configured alarm type
Normal acting alarm
Standard: HI alarm
Optional: LO alarm
API 1420 G Relay Output
Two independent SPDT form C contact sets
Two setpoints, two 12 turn potentiometers, 0-100% of span
Normal acting alarms
Standard: HI/LO alarm
Options: LO/LO, HI/HI, LO/HI alarms
Internal jumpers for HI/LO, LO/LO, HI/HI, LO/HI
Relay Contact Rating
8 A @ 240 VAC resistive load or 30 VDC resistive load
See graph on other side for relay load ratings
Caution: Do not exceed socket voltage rating
Use an RC snubber for inductive loads
Deadband
Alarm trip/reset window is symmetrical about the setpoint
API 1400 G 1.0 to 100% of span, 12 turn potentiometer.
API 1420 G Fixed at 1% of span, standard
API 1420 G A Adjustable deadbands, 1.0 to 100% of span,
1 turn potentiometer for each setpoint
Output Test Button
Toggles relay(s) to opposite state when pressed
Response Time
70 milliseconds typical
Ambient Temperature Range and Stability
–10°C to +60°C operating ambient
Better than ±0.04% of span per °C stability, calculated, not
tested
Housing and Sockets
IP 40, requires installation in panel or enclosure
API 011 or API 011 FS socket
Socket mounts to 35 mm DIN rail or can be surface mounted
Power
Standard: 115 VAC ±10%, 50/60 Hz, 2.5 W max.
Poption: 85-265 VAC 50/60 Hz, 60-300 VDC, 2.5 W typ.
A230 option: 230 VAC ±10%, 50/60 Hz, 2.5 W max.
Doption: 9-30 VDC, 2.5 W typical
Options—add to end of model number
L1400 G with LO trip. Alarm trips on decreasing signal.
HH 1420 G with HI/HI trip. Alarms trip at their respective
trip points on increasing signal.
LL 1420 G with LO/LO trip. Alarms trip at their respective
trip points on decreasing signal.
LH 1420 G with LO/HI trip instead of HI/LO.
A1420 G with adjustable deadbands.
UConformal coating for moisture resistance
Accessories—order as a separate line item
API 011 11-pin socket, DIN rail or surface mount
API 011 FS 11-pin finger safe socket, DIN rail or surface mount
API CLP1 Module hold-down spring for high vibration or
mobile applications
RTD Input Alarm Trips, Factory Ranged API 1400 G, API 1420 G
Applications
Description
The API 1400 G and API 1420 G are factory configured for an
RTD input and provide alarm contact outputs. Heavy duty relay
contacts allow the module to directly control high capacity
loads.
The API 1400 G provides a single setpoint adjustment and
DPDT relay contacts. The normal acting alarm output can
be factory configured for HI or LO operation. Top-accessible
potentiometers are used to adjust the alarm setpoint and
deadband.
The API 1420 G contains two independent setpoints with
two SPDT relay contact outputs. The normal acting alarm
output can be factory configured for HI/HI, HI/LO, LO/HI or
LO/LO operation. Top-accessible potentiometers are used to
adjust each alarm setpoint. Deadband is fixed at 1% of span.
Adjustable deadbands are optional.
LoopTracker and Alarm Status LEDs
API exclusive features include a LoopTracker LED that varies in
intensity with changes in the RTD input signal.
A red/green bi-color alarm status LED (two on the API 1420
G) visually indicate alarm status. These LEDs provide a quick
visual picture of your process at all times.
Output Test
API’s exclusive functional test button can be used to verify the
alarm and system operation. Press the Test button to toggle
the alarm relay(s) to the opposite state. The output test but-
ton greatly aids in saving time during initial startup and/or
troubleshooting.
Free Factory
I/O Setup!
Quick Link
api-usa.com/1400
API 1400 G
Variable Brightness Input LED
Bi-Color Relay LED
Deadband Adjustment
Setpoint Adjustment
Output Test Button
2.38"
1.75"
API 1420 G
AOption Deadband Adjustments
2.38"
1.75"
Variable Brightness Input LED
Bi-Color Relay 2 LED
Bi-Color Relay 1 LED
Setpoint 2 Adjustment
Setpoint 1 Adjustment
Output Test Button
API 1420 G P 001 001
115 VAC
Your Required Input
Your Alarm Configuration
2.75"
HHHHHH
HHHHH
HHHHHH
HHHHH
HHHHHH
HHHHH
HHHHHH
HHHHH
HHHHHH
Made in USA
Hot Swappable
Plug-In Design
API 011
300 V Rating
API 011 FS
300 V Rating API CLP1
© 09-21
api-usa.com
1220 American Way Libertyville, IL 60048
Phone: 800-942-0315 Fax: 800-949-7502
AABSOLUTEBSOLUTE PPROCESSROCESS IINSTRUMENTSNSTRUMENTS
Installation and Setup API 1400 G, API 1420 G
Precautions
WARNING! All wiring must be performed by a qualified electrician
or instrumentation engineer. See diagram for terminal designa-
tions and wiring examples. Consult factory for assistance.
WARNING! Avoid shock hazards! Turn signal input, output, and
power off before connecting or disconnecting wiring, or remov-
ing or installing module.
Précautions
ATTENTION! Tout le câblage doit être effectué par un élec-
tricien ou ingénieur en instrumentation qualifié. Voir le dia-
gramme pour désignations des bornes et des exemples de
câblage. Consulter l’usine pour assistance.
ATTENTION! Éviter les risques de choc! Fermez le signal
d’entrée, le signal de sortie et l’alimentation électrique avant
de connecter ou de déconnecter le câblage, ou de retirer ou
d’installer le module.
Alarm Configuration
API 1400 G relay operation is factory configured. The default
configuration is HI alarm normal acting. See model/serial num-
ber label for optional relay configurations.
API 1420 G relay operation is factory configured, but internal
jumpers can be used to modify the alarm type as follows.
1. Unplug the module from the socket.
2. Remove the 4 screws from the module bottom and remove
the plastic case.
3. Unplug the circuit board with the test button from the base.
4. Note location of jumper block at top left of circuit board next
to test button. See diagram at right.
5. Place jumpers as indicated for desired alarm operation.
The standard HI/LO setting is with one jumper across the
two top pins or with no jumper at all. Never place a jumper
across the two bottom pins!
6. Replace board, cover, and screws.
Socket and Mounting
Install module in a protective panel or enclosure. Allow space
around module for air flow. Use API 011 or API 011 FS socket.
See specifications for maximum allowable socket voltages. The
socket clips to a standard 35 mm DIN rail or can be mounted to
a flat surface.
Input
The input is factory configured (at 24°C ±1°C). See the model/
serial number label for input type, range, and options.
Correct wiring of 3-wire RTDs must be observed.
Connect 2-wire sensors to terminals 4 and 5 and run a jumper
wire from terminal 2 to 5.
Relay Output
See wiring diagram for connections. The module does not
provide power to the relay contacts.
Inductive loads (motors, solenoids, contactors, etc.) will greatly
shorten relay contact life unless an appropriate RC snubber
is installed.
Module Power
Check model/serial number label for module operating voltage
to make sure it matches available power.
When using DC power, polarity must be observed. The positive
(+) must be wired to terminal 1 and negative (–) must be wired
to terminal 3.
Setpoint
This multi-turn potentiometer (one for each setpoint on the API
1420 G) allows the operator to adjust the level at which the
alarm is activated. This control is adjustable from 0 to 100%
of the input range.
Deadband
The API 1400 G deadband potentiometer allows the alarm trip/
reset window to be adjusted symmetrically about the setpoint
from 1 to 100% of the span.
The deadband is fixed at 1% of span on the API 1420 G. The API
1420 G A with adjustable deadband option allows deadbands
to be adjusted symmetrically about each setpoint from 1 to
100% of the span.
Deadband allows the operator to fine tune the point at which
the alarm trips and resets. The deadband is typically used to
prevent chattering of the relays or false trips when the process
signal is unstable or changes rapidly.
Adjustments
To calibrate the alarm section, set the deadband control to the
minimum (counterclockwise). The deadband will be 1.0% of
input span in this case.
Set the signal source to a reference that represents the desired
trip point.
Adjust the setpoint control to the point at which the relay
changes state from a non-alarm to an alarm condition.
If a larger amount of deadband is desired turn the deadband
potentiometer clockwise. The deadband is symmetrical about
the setpoint; both transition points will change as deadband
is increased.
Alternately set the setpoint and deadband until the desired trip/
reset points are set.
Output Test Function
The functional test button toggles the alarm status independent
of the input when depressed. It verifies the alarm and system
operation. When released, the relay(s) will return to their prior
states. This can be used as a diagnostic aid during initial start-
up or troubleshooting.
Operation
The green LoopTracker®input LED provides a visual indication
that a signal is being sensed by the input circuitry of the mod-
ule. It also indicates the input signal strength by changing in
intensity as the process changes from minimum to maximum.
If the LED fails to illuminate, or fails to change in intensity as
the process changes, check the module power or signal input
wiring. Note that it may be difficult to see the LEDs under bright
lighting conditions.
The bi-color alarm LED provides a visual indication of the alarm
status. In all configurations, a green LED indicates a non-alarm
condition and a red LED indicates an alarm condition.
NOTE: Although the API 1400 G has a pair of relays, these
relays will energize and de-energize in unison.
The API 1420 G will accommodate independent relay operations.
High Alarm (H or HH)
The alarm relay changes state when the input exceeds the
deadband trip point. The relay resets when the input drops
below the deadband reset point. For a high alarm, the trip point
is above the reset point.
Low Alarm (L or LL)
The alarm relay changes state when the input goes below the
deadband trip point. The relay resets when the input exceeds
the deadband reset point. For a low alarm, the trip point is below
the reset point.
Normal Acting Alarms
Normal acting alarms energize the relay coils in a non-alarm
condition and de-energize them in an alarm condition. This will
create an alarm condition if the module loses power.
Setpoint 1 = HI
Setpoint 2 = LO
(Standard)
API 1420 G
Setpoint 1 = HI
Setpoint 2 = HI
API 1420 G
Setpoint 1 = LO
Setpoint 2 = LO
API 1420 G
Setpoint 1 = LO
Setpoint 2 = HI
API 1420 G
API 1420 G Internal Alarm Configuration Jumpers
api-usa.com
1220 American Way Libertyville, IL 60048
Phone: 800-942-0315 Fax: 800-949-7502
AABSOLUTEBSOLUTE PPROCESSROCESS IINSTRUMENTSNSTRUMENTS
API maintains a constant effort to upgrade and improve its products.
Specifications are subject to change without notice. See api-usa.com for
latest product information. Consult factory for your specific requirements.
WARNING: This product can expose you to chemicals includ-
ing lead, which is known to the State of California to cause
cancer or birth defects or other reproductive harm. For more
information go to www.P65Warnings.ca.gov
When using a
2-wire sensor
install jumper
from terminal 2
to terminal 5
32111109
87654
AC or
DC–
AC or
DC+
Contact Set 1
NC C NO
Module power
See module label
for correct power!
Socket
top view
Key down
when panel
mounting
NO C NC
Contact Set 2
See
api-usa.com/accessories
for socket information
and dimensions
NO = Normally Open
C = Common
NC = Normally Closed
3-wire RTD
* Do not make connec-
tions to unused terminals!
To maintain full isolation
avoid combining power
supplies in common with
input, output, or unit
power.
API 1420 G Alarm States with Normal Action HI/LO Alarms
No Alarm
GREEN Relay 1
8NC
7Com.
6NO
Relay 2
11 NC
10 Com.
9NO
GREEN GREEN
Relay 1
8NC
7Com.
6NO
Relay 2
11 NC
10 Com.
9NO
RED
HI Alarm LO Alarm
GREEN Relay 1
8NC
7Com.
6NO
Relay 2
11 NC
10 Com.
9NO
RED
Switching Current (A)
Switching Voltage (V)
0 3 5 10 30 50 100 300 500
8
5
3
1
0.5
0.3
0.1
AC inductive load
(cos f= 0.4) AC resistive
load
DC inductive load
(L/R = 7 ms)
DC resistive
load
Relay Contact Ratings
API 1400 G Alarm States with Normal Action HI Alarm
Relay 1
8NC
7Common
6NO
Relay 2
11 NC
10 Common
9NO
GREEN
No Alarm
OFF
RED
Power Off
HI Alarm
Relay 1
8NC
7Common
6NO
Relay 2
11 NC
10 Common
9NO

This manual suits for next models

7

Other Absolute Process Instruments Industrial Equipment manuals

Absolute Process Instruments API 4058 G Series User manual

Absolute Process Instruments

Absolute Process Instruments API 4058 G Series User manual

Absolute Process Instruments API 4058 G Series User manual

Absolute Process Instruments

Absolute Process Instruments API 4058 G Series User manual

Absolute Process Instruments API 4059 G Series User manual

Absolute Process Instruments

Absolute Process Instruments API 4059 G Series User manual

Absolute Process Instruments APD 4059 Series User manual

Absolute Process Instruments

Absolute Process Instruments APD 4059 Series User manual

Absolute Process Instruments APD 4058 Series User manual

Absolute Process Instruments

Absolute Process Instruments APD 4058 Series User manual

Popular Industrial Equipment manuals by other brands

Graco Therm-O-Flow 200 instructions

Graco

Graco Therm-O-Flow 200 instructions

Huawei FDT2108D-288 Quick installation guide

Huawei

Huawei FDT2108D-288 Quick installation guide

ABB HT592133 Operation manual

ABB

ABB HT592133 Operation manual

Beck 11-439 instruction manual

Beck

Beck 11-439 instruction manual

Graco ThermoLazer 200TC Repair

Graco

Graco ThermoLazer 200TC Repair

Rockwell Automation Allen-Bradley 1718-CBL65 user manual

Rockwell Automation

Rockwell Automation Allen-Bradley 1718-CBL65 user manual

Aventics IO-Link 580 Technical manual

Aventics

Aventics IO-Link 580 Technical manual

GE AKD-20 AR Installation and maintenance manual

GE

GE AKD-20 AR Installation and maintenance manual

Beko BEKOMAT 31U IF built-in F Instructions for installation and operation

Beko

Beko BEKOMAT 31U IF built-in F Instructions for installation and operation

Baker SterilGARD II SG400STD Operator's manual

Baker

Baker SterilGARD II SG400STD Operator's manual

Welker INLOOP ACE Installation, operation and maintenance manual

Welker

Welker INLOOP ACE Installation, operation and maintenance manual

Servend DI Install instructions

Servend

Servend DI Install instructions

Krone Titan 6/50 GL operating instructions

Krone

Krone Titan 6/50 GL operating instructions

Omron sysmac FH Series Hardware setup manual

Omron

Omron sysmac FH Series Hardware setup manual

nosted Igland 42 owner's manual

nosted

nosted Igland 42 owner's manual

ABB HT584310 Operation manual

ABB

ABB HT584310 Operation manual

Bosch rexroth EL 2 Assembly instructions

Bosch

Bosch rexroth EL 2 Assembly instructions

PIETRO FIORENTINI HBC 975 manual

PIETRO FIORENTINI

PIETRO FIORENTINI HBC 975 manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.