Accent ACS Series User manual

www.a ent- ontrol. om •2101 Potshop Lane •Norristown, PA 19403 •888-265-5632
USER MANUAL
ACS Series
Multi-jet Dry Type Plasti Body
Water Meters with Conta t Output
•ACS-NM-062-R •ACS-NM-075-R
•ACS-NM-100-R •ACS-NM-150-R
www.a ent- ontrol. om •2101 Potshop Lane •Norristown, PA 19403 •888-265-5632
Multi-jet Dry Type Plasti Body
Water Meters with Conta t Output
ACS-NM-062R-150R
Internal Parts Repla ement
All the internal parts of the meter lift out as a unit,
after the top has been unscrewed. The lens can then
be removed and the internal assembly lifted out. If
necessary, turn the meter upside down and tap one
end lightly on a countertop to loosen the internals.
The assembly can be separated by hand.
improper installation, frost/freeze damage or using the
meter outside of it’s specific operating parameters
(especially temperature and flow ranges).
In no event shall Accent Control Systems be liable
for incidental or consequential damages of any kind,
including but not limited to loss of profits or revenue,
loss of use, cost of capital, cost of substitute equipment,
facilities or services, downtime costs, delays and claims
of customers of the customer or other third parties.
Warranty
ACS water meters are warranted to perform to AWWA
new meter accuracy standards, and to be free from defects
in materials and workmanship for a period of 12 months
from date of shipment. If a meter does not perform as
warranted, Accent Control Systems will repair it free of
charge subject to the terms of this warranty.
Accent Control Systems liability under this performance
warranty is expressly limited to the repair or replacement
of the meter upon the customer’s returning the complete
meter prepaid to:
A ent Control Systems
Repair Department
2101 Potshop Lane
Norristown, PA 19403
This performance guarantee shall not be applicable to
meters which have been damaged by aggressive water
conditions, foreign matter in media, mis-application,
willful misconduct, negligence, vandalism, act of God,

www.a ent- ontrol. om •2101 Potshop Lane •Norristown, PA 19403 •888-265-5632
Main Te hni al Data
Multi-jet Dry Type Plasti Body
Water Meters with Conta t Output
ACS-NM-062R-150R
General Information
ACS Series meters use the internationally-accepted
multi-jet principle. A gear train drives the register
totalizer dials. For pulse output, one of the pointers is
replaced by a magnet arm, which is detected by a reed
switch sensor attached to the outside of the lens. The
reed switch provides dry contact closure and does not
require power.
A ura y Curve
Pulse Output
Reed switch sensors respond to a magnet that rotates
on the face of the meter under the lens. The sensor
turns on and off once each time the magnet passes
under it. Sensors are designed for electronic control
loads, and should not be used to switch power loads
or line voltages. See maximum current and voltage
ratings, under specifications.
Inlet Strainer
Clean the strainer yearly, or as required, depending on
water condition. ull out the strainer or back-flush the
meter to loosen trapped particulates.
Calibration
New meters are factory-tested to meet the AWWA
C-708 Multi-Jet Meter accuracy specification.
www.a ent- ontrol. om •2101 Potshop Lane •Norristown, PA 19403 •888-265-5632
Suggested Meter Installation
• Thoroughly flush the service line upstream of the
meter to remove dirt and debris.
• Set the meter inline. Water meters are recommended
to be installed horizontally with the register facing
upwards.
• Make sure the water flow follows the arrow cast on
the meter body.
• Slowly open any upstream valves to prevent damage
to the meter.
1/2” and 3/4” meters only
1” and 1 1/2” meters only
Flow (gpm)
ring. With fingers, lift the magnet pointer off its shaft and
remove the plain pointer from the target dial. Reverse their
positions and press them firmly into place. Securely seat the
sealing ring and then replace the lens, matching the tab on the
lens to the notch on the meter so as to align the sensor with
the magnetic pointer dial. Thread the meter top on and tighten.
Changing Pulse Rates
The pulse rate is determined by the dial on which the magnet
pointer is located. To move the magnet pointer, remove
meter top and lens, taking care not to lose the sealing
Multi-jet Dry Type Plasti Body
Water Meters with Conta t Output
ACS-NM-062R-150R
Meter Size Pulse Rate Drive Gear Position Connection Dia . #
20 /G X0.01 2
10 /G X0.01 1
4 /G X0.1 1& magnet wheel
2 /G X0.1 2
1 /G X0.1 1
5 G/ X1 2
10 G/ X1 1
50 G/ X10 2
100 G/ X10 1
20 /G X0.01 2
10 /G X0.01 1
4 /G X0.1 1& magnet wheel
2 /G X0.1 2
1 /G X0.1 1
5 G/ X1 2
10 G/ X1 1
50 G/ X10 2
100 G/ X10 1
4 /G X0.1 1& magnet wheel
2 /G X0.1 2
1 /G X0.1 1
5 G/ X1 2
10 G/ X1 1
50 G/ X10 2
100 G/ X10 1
4 /G X0.1 1& magnet wheel
2 /G X0.1 2
1 /G X0.1 1
5 G/ X1 2
10 G/ X1 1
50 G/ X10 2
100 G/ X10 1
1/2”
3/4”
1”
1 1/2”
Black - Common
Red - N O
Blue - N O
Diagram 2: Dual Sensor
Reed Switch
Diagram 1: Single Sensor Di
Black - Common
Red - N O Reed Switch Reed Swi
Conne tion Diagrams
US gpm
Minimum reading US gallon
Minimum graduation US gallon
US gpm
US gpm
US gpm
062 - 1/2” 075 - 3/4” 100 - 1” 150 - 1 1/2”
20 20 50 88
10 10 25 44
1 1 3 3.5
0.25 0.25 0.75 0.88
0.01 0.01 0.1 0.1
0.005 0.005 0.1 0.1
Spe ifi ations
Temperature 105˚ F (40˚ C) max
Pressure 150 psi operating
Materials Body FR -Reinforced polyamide
Couplin s Brass couplings (Std)
Lead Free EcoBrass (Opt)
Internals Engineered thermoplastic
Ma net Alnico
Accuracy +/- 1.5% of reading
Sensor Reed switch Totalizer only
Maximum Current 20 mA n/a
Maximum Volta e 24 Vdc or Vac n/a
Cable Len th 12’ (4m) std n/a
2000’ max run

www.a ent- ontrol. om •2101 Potshop Lane •Norristown, PA 19403 •888-265-5632
Main Te hni al Data
Multi-jet Dry Type Plasti Body
Water Meters with Conta t Output
ACS-NM-062R-150R
General Information
ACS Series meters use the internationally-accepted
multi-jet principle. A gear train drives the register
totalizer dials. For pulse output, one of the pointers is
replaced by a magnet arm, which is detected by a reed
switch sensor attached to the outside of the lens. The
reed switch provides dry contact closure and does not
require power.
A ura y Curve
Pulse Output
Reed switch sensors respond to a magnet that rotates
on the face of the meter under the lens. The sensor
turns on and off once each time the magnet passes
under it. Sensors are designed for electronic control
loads, and should not be used to switch power loads
or line voltages. See maximum current and voltage
ratings, under specifications.
Inlet Strainer
Clean the strainer yearly, or as required, depending on
water condition. ull out the strainer or back-flush the
meter to loosen trapped particulates.
Calibration
New meters are factory-tested to meet the AWWA
C-708 Multi-Jet Meter accuracy specification.
www.a ent- ontrol. om •2101 Potshop Lane •Norristown, PA 19403 •888-265-5632
Suggested Meter Installation
• Thoroughly flush the service line upstream of the
meter to remove dirt and debris.
• Set the meter inline. Water meters are recommended
to be installed horizontally with the register facing
upwards.
• Make sure the water flow follows the arrow cast on
the meter body.
• Slowly open any upstream valves to prevent damage
to the meter.
1/2” and 3/4” meters only
1” and 1 1/2” meters only
Flow (gpm)
ring. With fingers, lift the magnet pointer off its shaft and
remove the plain pointer from the target dial. Reverse their
positions and press them firmly into place. Securely seat the
sealing ring and then replace the lens, matching the tab on the
lens to the notch on the meter so as to align the sensor with
the magnetic pointer dial. Thread the meter top on and tighten.
Changing Pulse Rates
The pulse rate is determined by the dial on which the magnet
pointer is located. To move the magnet pointer, remove
meter top and lens, taking care not to lose the sealing
Multi-jet Dry Type Plasti Body
Water Meters with Conta t Output
ACS-NM-062R-150R
Meter Size Pulse Rate Drive Gear Position Connection Dia . #
20 /G X0.01 2
10 /G X0.01 1
4 /G X0.1 1& magnet wheel
2 /G X0.1 2
1 /G X0.1 1
5 G/ X1 2
10 G/ X1 1
50 G/ X10 2
100 G/ X10 1
20 /G X0.01 2
10 /G X0.01 1
4 /G X0.1 1& magnet wheel
2 /G X0.1 2
1 /G X0.1 1
5 G/ X1 2
10 G/ X1 1
50 G/ X10 2
100 G/ X10 1
4 /G X0.1 1& magnet wheel
2 /G X0.1 2
1 /G X0.1 1
5 G/ X1 2
10 G/ X1 1
50 G/ X10 2
100 G/ X10 1
4 /G X0.1 1& magnet wheel
2 /G X0.1 2
1 /G X0.1 1
5 G/ X1 2
10 G/ X1 1
50 G/ X10 2
100 G/ X10 1
1/2”
3/4”
1”
1 1/2”
Black - Common
Red - N O
Blue - N O
Diagram 2: Dual Sensor
Reed Switch
Diagram 1: Single Sensor Di
Black - Common
Red - N O Reed Switch Reed Swi
Conne tion Diagrams
US gpm
Minimum reading US gallon
Minimum graduation US gallon
US gpm
US gpm
US gpm
062 - 1/2” 075 - 3/4” 100 - 1” 150 - 1 1/2”
20 20 50 88
10 10 25 44
1 1 3 3.5
0.25 0.25 0.75 0.88
0.01 0.01 0.1 0.1
0.005 0.005 0.1 0.1
Spe ifi ations
Temperature 105˚ F (40˚ C) max
Pressure 150 psi operating
Materials Body FR -Reinforced polyamide
Couplin s Brass couplings (Std)
Lead Free EcoBrass (Opt)
Internals Engineered thermoplastic
Ma net Alnico
Accuracy +/- 1.5% of reading
Sensor Reed switch Totalizer only
Maximum Current 20 mA n/a
Maximum Volta e 24 Vdc or Vac n/a
Cable Len th 12’ (4m) std n/a
2000’ max run

www.a ent- ontrol. om •2101 Potshop Lane •Norristown, PA 19403 •888-265-5632
USER MANUAL
ACS Series
Multi-jet Dry Type Plasti Body
Water Meters with Conta t Output
•ACS-NM-062-R •ACS-NM-075-R
•ACS-NM-100-R •ACS-NM-150-R
www.a ent- ontrol. om •2101 Potshop Lane •Norristown, PA 19403 •888-265-5632
Multi-jet Dry Type Plasti Body
Water Meters with Conta t Output
ACS-NM-062R-150R
Internal Parts Repla ement
All the internal parts of the meter lift out as a unit,
after the top has been unscrewed. The lens can then
be removed and the internal assembly lifted out. If
necessary, turn the meter upside down and tap one
end lightly on a countertop to loosen the internals.
The assembly can be separated by hand.
improper installation, frost/freeze damage or using the
meter outside of it’s specific operating parameters
(especially temperature and flow ranges).
In no event shall Accent Control Systems be liable
for incidental or consequential damages of any kind,
including but not limited to loss of profits or revenue,
loss of use, cost of capital, cost of substitute equipment,
facilities or services, downtime costs, delays and claims
of customers of the customer or other third parties.
Warranty
ACS water meters are warranted to perform to AWWA
new meter accuracy standards, and to be free from defects
in materials and workmanship for a period of 12 months
from date of shipment. If a meter does not perform as
warranted, Accent Control Systems will repair it free of
charge subject to the terms of this warranty.
Accent Control Systems liability under this performance
warranty is expressly limited to the repair or replacement
of the meter upon the customer’s returning the complete
meter prepaid to:
A ent Control Systems
Repair Department
2101 Potshop Lane
Norristown, PA 19403
This performance guarantee shall not be applicable to
meters which have been damaged by aggressive water
conditions, foreign matter in media, mis-application,
willful misconduct, negligence, vandalism, act of God,
This manual suits for next models
4
Other Accent Measuring Instrument manuals
Popular Measuring Instrument manuals by other brands

Major tech
Major tech MT 770 instruction manual

DHC
DHC BT900 owner's manual

Endress+Hauser
Endress+Hauser Prothermo NMT532 operating instructions

RS PRO
RS PRO LCR-6000 Series instruction manual

Endress+Hauser
Endress+Hauser Cerabar S PMC71 Brief operating instructions

MICRO-EPSILON
MICRO-EPSILON interferoMETER IMS5400-DS Quick manual

Ambco
Ambco 1000+P user manual

Hanna Instruments
Hanna Instruments HI839800 Quick reference guide

R&S
R&S DVMS1 Getting started

Psiber Data Systems
Psiber Data Systems NetXpert 1400 user manual

Landis+Gyr
Landis+Gyr 750 Installation, commissioning and maintenance manual

Feltest
Feltest Caliper Profiler instruction manual