AccessPRO Superior AccessPRO4 Guide

2.InstallationEquipment
AccessPRO4 I nstallation and C onnection G uide
Select two of the elliptical holes on Hang the equipment on the upper
edge of the rear iron cover, and
then press the equipment down.
Push the equipment backward to hang
the entire equipment onto the rear cover.
on the surface for fixing (Which may
be on a distribution cabinet, ceiling
or other weatherproof position).
123
1.Cautions
1)The access controller provides lock control output. For a lock which should be open when being energized and be closed
Unlock at power off
Unlock at power on
+
+
-
-
Enlar ged diag ram
NC
NO
COM
when being de-energized, the “COM” and “ NO” terminals should be used. For a lock which should be open when being
de-energized and be closed when being energized, the “COM” and “ NC” terminals should be used.
Diode
Diode
L ock
L ock
+
+
-
-
FR107
FR107
3.Lock Connection
External power supply for electronic lock
p
q
RS-485 EXTWIEGAND3IN5IN6OUT5OUT6WIEGAND4IN7IN8OUT7OUT81
3
1
3
1
2
1
21
10
1
3
1
3
1
2
12
1
10
1
6
WIEGAND1IN1IN2 OUT1OUT2WIEGAND2IN3IN4OUT3OUT4
13
POWER
15110 121 2 1313110 1 2 1213
Reset
PC
TCP/IP Ethernet
RS485 Ports
Card Reader
1# Controller
2# Controller
n# Controller
p
q
RS-485 EXT WIEGAND3IN5IN6 OUT5 OUT6 WIEGAND4IN7 IN8 OUT7 OUT81
3
1
3
1
2
1
2
1
10
1
3
1
3
121
2
1
10
1
6
WIEGAND1IN1 IN2OUT1 OUT2 WIEGAND2IN3IN4OUT3 OUT4
13
POWER
15110 1 2 1 2 1313110 1 2 1 2 13
Reset
p
q
RS-485EXT WIEGAND3IN5IN6 OUT5OUT6 WIEGAND4IN7 IN8 OUT7OUT81
3
1
3
1
2
1
2
1
10
1
3
1
3
1212
1
10
1
6
WIEGAND 1IN1 IN2OUT1 OUT2 WIEGAND 2IN3 IN4 OUT3OUT4
13
POWER
15110 121 21313110 1 2 1213
Reset
p
q
RS-485EXTWIEGAND 3IN5IN6OUT5 OUT6 WIEGAND 4IN7 IN8OUT7OUT81
3
1
3
1
2
1
2
1
10
1
3
1
3
121
2
1
10
1
6
WIEGAND 1IN1 IN2 OUT1 OUT2 WIEGAND2IN3IN4OUT3 OUT4
13
POWER
15110 121 21313110 1 2 1 2 13
Reset
1) TCP/IP Mode:
2) RS485 Mode:
3) The recommended bus length of RS485 communication is less than 600 meters.
4.Equipment Communication
485-
485+
G ND
485-485-
485- 485+485+
485+ G NDG ND
G ND
Serial Bus
4 3 2 1
4 3 2 1
4 3 2 1
8# Controller
2# Controller
1# Controller
p
q
RS-485EXT WIEGAND 3IN5IN6 OUT5OUT6WIEGAND4IN7 IN8OUT7OUT81
3
1
3
1
2
1
21
10
1
3
1
3
1212
1
10
1
6
WIEGAND 1IN1 IN2 OUT1 OUT2 WIEGAND2IN3 IN4 OUT3 OUT4
13
POWER
1511012 1 2 13131101 2 1213
Reset
p
q
RS-485EXT WIEGAND3IN5 IN6OUT5OUT6 WIEGAND 4IN7 IN8 OUT7 OUT81
3
1
3
1
2
1
2
1
10
1
3
1
3
1
212
1
10
1
6
WIEGAND 1IN1 IN2 OUT1 OUT2 WIEGAND2IN3 IN4 OUT3 OUT4
13
POWER
15110 1 2 12 1 313110 121213
Reset
p
q
RS-485 EXTWIEGAND 3 IN5IN6 OUT5 OUT6WIEGAND 4IN7 IN8OUT7OUT81
3
1
3
1
2
1
2
1
10
1
3
1
3
1212
1
10
1
6
WIEGAND 1IN1 IN2 OUT1 OUT2 WIEGAND2IN3IN4 OUT3 OUT4
13
POWER
15110 12 1 21313110 1 2 1213
Reset
Notes:
L ock Power
+
+
-
-
L ock Power
3) Each relay may work under the wet mode or dry mode by setting the jumper terminal. If the 12V power
1 2 3 4
supply inside the access controller uses external power supply, the output of each relay is under the “wet mode”.
OUT4
R elay
R elay
Jumper terminals
Jumper terminals
wet mode:
OUT8
OUT7
R elay
R elay
OUT3
1
1
2
2
3
3
dry mode:
IN
8
IN
4
J24 Enlargement
Factory default
Terminal resistance setting
Terminal resistance setting diagram (The first layer of PCB)
11
22 33
RS485
J24
Please notice the following cautions. Mis-operation may lead to personal injury or
1) Do not energize the system before installation is complete. Never carry out installation
Vision:1.0.1 Date: July, 2011
2) All peripheral devices must be grounded.
Switch
4) When the bus is longer than 300 m, to enhance the stability of communication, it is necessary
activities when the system is energized.
the rear iron cover. Drill two holes
2) If the electrical lock is connected to the access control system, you need to parallel one FR107 diode (Equipped
in the package) to prevent the self-inductance EMF affect the system, do not reverse the polarities.
If the external power supply uses potential free contacts, the “dry mode” should be used. please refer to
Instructions for Hardware of C4-200/400 Access Controller.
* It is recommended to short 2-3 ports, the output use the “dry mode”, the electronic lock use the external power supply.
of lock ports
The PC software communicate with the system through two protocols (RS485 and TCP/IP)
for data exchange and remote management. The communication cable should be away
from high-voltage lines as far as possible. Do not keep the communication cable in parallel
with power cords or bind them together.
RS 485 Convertor
1) Internationally accepted RVSP (shielded twisted-pair) wires should be used for communication
to RS485 communication wires should be connected by meanseffectively avoid interference.
of bus cascade connection.
2) Theoretically, in RS485 communication, one bus may be connected with 64 access controllers.
to change J24 on the first layer of PCB (see the figure below) inthe first and the last units (see
unit 8# as shown in the figure above) to short pins 2-3. This method is equivalent to connect
equipment failure:
R elay output por ts a nd j umper ter mi nals setti ng (The second layer of PCB)
4 3 2 1 1 2 3 4
1 2 3 4 1 2 3 4
1 2 3 4
1 2 3 4
PC
It is recommended to conenct with no more than 16 devices.
with a resistance of 120 ohm.
Jumping
Terminals
Distribution
diagram of the
factory default
jumper cap:
1
234
3) It is recommended that all wires run through casing pipes which may by PVC or galvanized
5) It is recommended that card readers and buttons should be installed at height of 1.4m-1.5m
6) It is recommended to use the power supply in case for control panel, and external power
4) It is strongly recommended that the length of exposed part of any connection cable
should not be longer than 4 mm. avoidProfessional clamping tools may be used to
unintentional contact of exposed wires to avoid short-circuit or communication failure.
supply for each lock.
ones.
above ground.

1) The auxiliary input may be connected to infrared body detectors, smoke detectors, gas detectors, window magnetic alarms, wireless exit switches, etc.
2) The auxiliary output may be connected to locks, monitors, alarms, door bells, etc.
3) The auxiliary input and the auxiliary output is set with iAccess4.0.
support for ordering machines with GPRS and WiFi functions.
A. Use 2-conducotor power cord
5) Recommend use of wires
B.
C. Use 2-conducotor lock power cord (RVV 2*0.75mm)
D. Use 2-conducotor switch or magnetic power cord (RVV 2*0.5mm)
5. ConnectionTerminals
Notes:
4) GPRS, WiFi and the following items indicated with "* " are optional. Please contact our business representatives or pre-sale technical
Data_Tx-
Data_Tx+
GND
Data_RxTx-
Data_RxTx+
Shield
+12V
GND
Shield
AC Fail
Battery Fail
VCC 12V
GND
D0
D1
Shield
LED_G
LED_R
BEEP
Hold
Card_present
VCC 12V
GND
D0
D1
Shield
LED_G
LED_R
BEEP
Hold
Card_present
Card_present
Hold
BEEP
LED_R
LED_G
Shield
D1
D0
GND
VCC 12V
Card_present
Hold
BEEP
LED_R
LED_G
Shield
D1
D0
GND
VCC 12V
GND
Analog_input
GND
Analog_input
GND
Analog_input
GND
Analog_input
Analog_input
GND
Analog_input
GND
Analog_input
GND
Analog_input
GND
NO
COM
NC
NO
COM
NC
NO
COM
NC
NO
COM
NC
NC
COM
NO
NC
COM
NO
NC
COM
NO
NC
COM
NO
Lock 2
Auxiliary Output
Lock 1
Lock 3
Lock 4
Auliliary Output
Auxiliary Output
Auliliary Output
Magnet 3
Magnet 4
Magnet 3
Magnet 1
Door Switch 3
Door Switch 1
Door Switch 3
Door Switch 4
12V Power Input
Shield Wire
AC Fail Detection
Battery Fail Detection
12VPower Output
12VPower Out
12VPower Output
12VPower Output
Wiegand Input
Wiegand Input
Wiegand Input
Wiegand Input
Shield Wire
Sheild Wire
Shield Wire
Shield Wire
Green
Green
Red
Red
Red
Red
Green
Green
Beep
Beep
Beep
Beep
Controlled Reader Hold
Controlled Reader Hold
Controlled Reader Hold
Card Present
Card Present
Card Present
Card Present
{
{
{
{
{
{
{
{
{
{
{
{
{
{
{
Shield Wire
}
}
}
}
}
}
}
}
}
}
}
}
RS 422 Send
}
RS422 Receive
or RS485 Comm.
}
Controlled Reader Hold
Output
Output
Output
*
*
*
*
*
*
*
p
q
RS-485 EXT WIEGAND 3 IN5 IN6 OUT5 OUT6 WIEGAND 4IN7 IN8 OUT7 OUT8 1
3
1
3
1
2
1
2
1
10
1
3
1
3
1
2
1
2
1
10
1
6
WIEGAND 1IN1 IN2 OUT1 OUT2 WIEGAND 2IN3 IN4 OUT3 OUT4
13
POWER
15110 1 2 1 2 1 313110 1 2 1 2 13
Reset
Fr ont V iew Fr ont Side V iew
RS-232
IN9 OUT9
IN12IN11
IN10 OUT10 RS-485
1313
12
121 2
12
14
14
Output
*
*
*
*
*
TXD232
RXD232
/
GND
Shield
RS 485-
RS 485+
GND
USB
TCP/IP
Analog_input
GND
Analog_input
GND
Analog_input
GND
Analog_input
GND
NO
COM
NC
NO
COM
NC
U Disk
TCP/IP Comm.
RS 232 Send
Auxiliary Input
Auxiliary Input
Auxiliary Input
Auxiliary Input
Auxiliary Output
Auxiliary Output
Shield Wire
RS485 Comm.
RS485 Ground
RS 232 Receive
Idle
RS 232 Ground
*
*
*
*
*
*
A
B
B
B
B
C
C
C
C
C
C
C
C
C
C
D
D
D
D
D
D
D
D
D
D
D
D
*
*
}}
According to the port you connected, choose such as 8,10 conductor cord communication twisted-pair sensor cable (RVVP 8*0.5mm)
Other AccessPRO Control Panel manuals
Popular Control Panel manuals by other brands

Servotronix
Servotronix CDHD2 manual

Amplicon
Amplicon EX213 instruction manual

Bosch
Bosch Rexroth IndraControl VCP 05 Project planning manual

oventrop
oventrop Regtronic EM Installation and operating instructions

AV-GAD
AV-GAD EasyLoader AV-2004 Installation and operation manual

ADEMCO
ADEMCO Vista-20HWSE/SE quick guide