
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com
Page 4
Version: 7.0
I0000584
SECOND METHOD
The other way to calibrate the actuator is to drive the output to 0% and 100% of selected input range.
Depending the direction and amount of developed error, it may be necessary to repeat this process. This
calibration process should be done at a time when the large changes in the actuator position will not cause
problems with the environment it is controlling. When power is applied to terminals +24V and (-), the
“POWER” LED will light. When the AFP is not powered on terminals +24v and (-), both relays are open.
Tranzorbs are incorporated in the output circuit of the AFP.
TROUBLESHOOTING & TESTING
1.) Make sure the input and oset jumper and output timing switches 3 and 4.
2.) Apply 24 VAC/VDC to the 24 (+) and (-) terminals, conrm the power LED is on and measure
voltage to conrm proper voltage. A DC voltage can be measured from the Vout (+) terminal to the
24 (-) terminal. This voltage will vary depending on the supply voltage supplied. Voltage ranges will
be from 21 to 25 VDC. Please note supply and Vout voltages if unit is not functioning properly.
Contact technical support at ACI.
3.) Y2 will drive the actuator down 105% of selected range (200% on Version 2, 105% up on Ver 7) if
power is removed and reapplied. This is to assure the device being controlled is at 0% when
command voltage is applied. Output will return to commanded position after this calibration
process.
TESTING THE OUTPUT
Note: Output is contact closure only.
Placing J4 or J5 in the H position will close the corresponding contacts or the output. Never place both at
the same time. Conrm the resistance operation of meter and connect meter only to the corresponding
output terminal. “G” terminal is common for both. Resistance can be measured now. A “dead” or “near
dead” short should be measured when the output has been placed in the “H” position. Conrm the
appropriate LED it lit. Contact tech support if the output is not functioning.
TEST PROCEDURE (Version 1, 2, 3, 5, 6, 7 & 8)
Set the input jumpers to the required input signal settings. Set all the output switches to OFF. Place jumper
J6 CD/CE in the center position or remove (do not discard or lose jumper). With power and input only
connected, ramp input signal from 0 to 100% or in steps of 20%. Y2 will turn on from 25 – 49% of set range.
Y1 will turn on and Y2 will turn o from 50 – 73% of set range. Both relays will be on at 74% or greater. This
test conrms the unit is functional and operating correctly. Reset timing switches to desired range and J6
to the CD position. Reconnect input and output connections and retry application. Contact tech support
if application problems still exist.
TEST PROCEDURE (Version 4 ONLY)
Set the input jumpers to the required input signal settings. Set all the output switches to OFF. Place jumper
J6 CD/CE in the center position or remove (do not discard or lose jumper). With power and input only
connected, ramp input signal from 0 to 100% or in steps of 20%. Both relays will be on at 0-25%.Y1 will turn
on from 25 – 49% of set range. Y2 will turn on and Y1 will turn o from 50 – 73% of set range. Both relays
will be o at 74% or greater. This test conrms the unit is functional and operating correctly. Reset timing
switches to desired range and J6 to the CD position. Reconnect input and output connections and retry
application. Contact tech support if application problems still exist.
INPUT SIGNAL JUMPERS
Refer to the input signal range and oset jumper settings shown in the diagram on page 1.
Voltage Input
Connect the “+” or positive wire to the “UP/A+” terminal. Connect the common to the “24V-“ terminal.
Apply a voltage from control source. Measure the voltage at the input terminals. If the commanded
voltage is not present, remove the“+”or positive wire and measure from + wire to the“24V-“ terminal. If no
voltage is measured, check wiring from controller. If voltage disappears or is reduced when connected to
the AFP. Conrm input jumper is set to voltage mode and remove input wires. Remove power from unit
and measure the resistance from “Vout+” to “24V-“ terminals. Resistance in the voltage modes will be
around 10K Ohms and greater. If input is shorted contact tech support at ACI. If not shorted remove the
controller input common and connect power only to AFP. NOTE: Place meter in voltage mode and
measure VAC and VDC from analog input common wire to power supply common. If any voltage is
measured in DC or AC, a ground loop most likely exists. Use a separate 24V transformer for the AFP and let
common oat.
Current Input
Conrm the input jumper is in the 20mA mode. Measured input resistance is around 250 Ohms. Connect
“+” or positive wire to “UP/A+”and input “-“ or common to“24V-“. Apply mA signal. Place meter in voltage
and measure voltage across“UP/A+” and “24V-“. 4mA is equal to 1 volt and 20mA is equal to 5 volts. Use
Ohms Law to nd voltage from current. Current x 250 Ohms = Volts.
Example: 12mA (or 0.012) x 250 Ohms = 3 Volts. If no voltage is present, check wiring for open. Current
cannot exist without voltage present unless the input is dead shorted. If problem still persist see the“Note”
in voltage section.