aci WPR2 Series User manual

Installation and Operation Instructions
WPR2 Series (Max. Line Pressure < 300 PSI)
Wet to Wet Differential Pressure
Version : 17.0
I0000756
Page 1 of 5
Figure 1: WPR2 Dimensions and Hardware
Precautions
REMOVE
POWER
BEFORE
WIRING.
NEVER
CONNECT
OR
DISCONNECT
WIRING
WITH
THE
POWER
APPLIED.
DO
NOT
ALLOW
LIVE
WIRES
TO
TOUCH
THE
CIRCUIT
BOARD.
AN
ISOLATION
TRANSFORMER
IS
RECOMMENDED
WHEN
POWERING
THE
DEVICE
WITH
24VAC.
DO
NOT
RUN
THE
WIRING
IN
ANY
CONDUIT
WITH
LINE
VOLTAGE.
FAILURE
TO
WIRE
DEVICES
WITH
THE
CORRECT
POLARITY
WHEN
USING
A
SHARED
TRANSFORMER
MAY
RESULT
IN
DAMAGE
TO
ANY
DEVICE
POWERED
BY
THE
SHARED
TRANSFORMER.
DO
NOT
SWITCH
PRESSURE
RANGE
AND
OUTPUT
MODE
WHEN
POWER
IS
ON.
MAKE
SURE
TO
POWER
OFF
THE
UNIT
FIRST,
THEN
MOVE
JUMPERS
TO
THE
RIGHT
POSITIONS
AND
THEN
POWER
ON
THE
TRANSMITTER.
DO
NOT
APPLY
ANY
EXTERNAL
VOLTAGE
TO
ZERO
TERMINALS.
DO
NOT
REPLACE
PRESSURE
SENSORS
WITH
ANY
OTHER
SENSORS.
DO
NOT
INTERCHANGE
THE
HIGH
AND
LOW
SENSORS.
THE
HIGH
AND
LOW
SENSORS
ARE
SPECIFICALLY
CALIBRATED
TO
THE
WPR2
UNIT.
ANY
CHANGES
TO
THE
SENSORS
WILL
VOID
THE
PRODUCT
WARRANTY
2.60"
5.47"
3.00"
4.47"
5.28"
Ø0.200"

Version : 17.0
I0000756
Page 2 of 5
Wiring
Shielded cable with 16 to 22AWG conductors is recommended. Each WPR2 unit can be configured to three
output modes: 4-20mA, 0-5V and 0-10V. Use the Wiring Connections table below to determine the proper
wiring for your application. See Figure 1 below for Output Mode and Output Signal switch positions.
Note: The WPR2 units are shipped from the factory set up with a 0-10 VDC output.
Output Mode
(SW8)
Output Signal
(SW7 Position 2)
Supply
Voltage
Wire Connections
Vout 0-5 VDC (5V) VAC/VDC V+ COM VOU
T
Vout 0-10 VDC (10V) VAC/VDC V+ COM VOU
T
mA 4-20 mA VDC V+ IOU
T
Table 1: Wiring Connections
WPR2 Terminals
V+ IOUT VOUT COM ZERO
VDC/VAC
Power Supply
Voltage
Meter
Relay
Com
Com
+
+
WPR2 Terminals
V+ IOUT VOUT COM ZERO
VDC
Power Supply
Current
Meter
Relay
Com
Com
+
+
AUTO ZERO
The WPR2 unit should be “ZEROED” before the pressure transducers are installed on the pipes.
The Auto zero button and remote zero are both used to cancel out the offsets caused by installation and sensor
drift.
NOTE: Make sure a minimum of 10 minutes of warm-up time before adjustment to the ZERO.
The Auto Zero adjustment should only be performed with NO pressure applied to both sensors.
Shut off your main pressure valve and open a shutoff valve with hose drain to equalize the pressure in
the line to your atmosphere.
Remove the sensors from the system to remove pressure from each sensor to achieve equal pressure.
Push “ZERO” button or “SHORT ZERO PIN” for 2 seconds to “COM PIN” before installation or
when it is necessary.
For units with LCD display:
“ZERO” icon will be on when the push button is released. If auto zero is successful, “ZERO” icon will flash
twice, otherwise “ERROR” and “OVR” icons will flash twice.
Pressure Connections
The WPR2 Series have 1/4"-18NPT male fittings. The sensors are labeled “SENSOR HIGH” and “SENSOR
LOW”; MAKE SURE THE SENSORS ARE WIRED TO THE CORRESPONDING TERMINAL
BLOCK INSIDE THE HOUSING. Otherwise ACI will not guarantee the accuracy specifications. DO NOT
REPLACE SENSORS WITH ANY OTHER SENSORS. THE WPR2 UNITS ARE CALIBRATED WITH
THE HIGH AND LOW SENSORS SUPPLIED WITH THE UNIT.
All WPR2 units can handle a proof pressure of 3X THE MAXIMUM LINE PRESSURE for both HIGH and
LOW pressure sensors. If after connecting the pipe, the unit outputs out-of-range signal OVR on display only,

Version : 17.0
I0000756
Page 3 of 5
turn off the unit, disconnect the pipe or shut down the valves immediately and check the pressure input with a
gauge or other test instrument.
A Pressure Snubber is included with each sensor to dampen pressure surges. A pigtail siphon should be used to
lower the media temperature below 230°F (110°C) to prevent damage to the pressure sensor.
Pump
WPR2
Power High Low
Direction of
Water Flow
Direction of
Water Flow
Return Water Line (55 PSI)
Supply Water Line (60 PSI)
Pressure Snubber
Supplied by ACI
Shut Off Valve
Pressure
Transducer
Pressure Snubber
Supplied by ACI
Shut Off Valve
Pressure
Transducer
Supply Voltage & Control Signal
ACI/WPR2
Installation
INPUT RANGE ADJUSTMENT
DO NOT SWITCH PRESSURE RANGE AND OUTPUT MODE WHEN POWER IS ON.
o MAKE SURE POWER TO THE UNIT IS OFF. FAILURE TO DO SO WILL NOT ALLOW ANY NEW
SWITCH SETTINGS TO TAKE PLACE.
CHOOSE DIFFERENTIAL RANGE BASED ON THE EXPECTED DIFFERENTIAL PRESSURE IN YOUR
APPLICATION.
o MOVE SWITCHES TO THE CORRECT POSITIONS AND THEN POWER ON THE TRANSMITTER.
MAXIMUM LINE PRESSURE
ACI/Part No. Maximum Line Pressure
WPR2-30 30 PSI
WPR2-100 100 PSI
The WPR2 can operate in either unidirectional mode (0 – X PSI) or bidirectional mode (± X PSI). The unit will
set at unidirectional mode after factory calibration.
Unidirectional Mode
DIP switch SW7 position 1 set at UNI side.
DIP switch SW7 positions 4 and 5 are for Range Selection
ACI/Part No. SW7 Position 5: 1 SW7 Position 5: 2
Position 4: A Position 4: B Position 4: A Position 4: B
A/WPR2-30 0-30 PSI 0-15 PSI 0-7.5 PSI 0-3 PSI
A/WPR2-100 0-100 PSI 0-50 PSI 0-25 PSI 0-10 PSI
Bidirectional Mode
DIP switch SW7 position 1 set at BI side.
DIP switch SW7 positions 4 and 5 are for Range Selection

Version : 17.0
I0000756
Page 4 of 5
Note: In Bidirectional mode, a value of 0 PSID will have an output equal to 50% of the full output range.
ACI/Part No. SW7 Position 5: 1 SW7 Position 5: 2
Position 4: A Position 4: B Position 4: A Position 4: B
A/WPR2-30 ±30 PSI ±15 PSI ±7.5 PSI ±3 PSI
A/WPR2-100 ±100 PSI ±50 PSI ±25 PSI ±10 PSI
134
25
ON
Figure 1
ENGINEERING UNITS ADJUSTMENT
This option is ONLY for units with LCD display. Switch DIP switch SW7 position 3 to select PSI or BAR.
Advanced Features
For units with LCD display:
“ERROR” icon will be on when differential pressure is out of range.
“OVR” icon will be on when gage pressure is out of range on either the high or low port.
Trouble Shooting
Problem Trouble Shooting Steps
“ERROR” icon on Display will be on
when differential pressure is out of range.
The differential pressure could be lower or
higher than the selected range.
“OVR” icon on Display will be on when
the input pressure is > than Max Line
Pressure. Check pressure input with a
gauge or other test instrument. The
WPR2-300 Series is available for
pressures over 100 PSI.
1. Verify the HIGH Sensor Voltage is between
0.5 VDC (0 PSI) and 4.5 VDC (Max. Line Pressure)
When measuring from the HIGH Sensor terminal
Block “GND” to “OUT”. If out of range call ACI for
Technical support.
2. Verify the LOW Sensor Voltage is between
0.5 VDC (0 PSI) and 4.5 VDC (Max. Line Pressure)
When measuring from the LOW Sensor terminal
Block “GND” to “OUT”. If out of range call ACI for
Technical support.
3. Verify in Uni-Directional Mode that the HIGH Sensor
Voltage is ≥ the LOW Sensor Voltage. If voltage is
anything different call ACI for Technical support.
Output reading @ 4mA or 0 VDC
all the time
1. Verify proper Supply Voltage at the transducer meets the
Product Specifications.
2. Verify 5 VDC Reference voltage across “VIN” to “GND”
terminals for both the HIGH & LOW Sensor
terminal blocks. If voltage is anything different than
5VDC call ACI for Technical support.
Erroneous Readings 1. Bleed Air from System.
2. Repeat the Auto Zero calibration on page 2.

Version : 17.0
I0000756
Page 5 of 5
Product Specifications
Supply Voltage 4-20mA Output: 250 Ohm Load 16-36 VDC
4-20mA Output: 500 Ohm Load 20-36 VDC
0-5 VDC Output: 16-36 VDC / 24VAC (+/-10%)
0-10 VDC Output: 16-36 VDC / 24VAC (+/-10%)
Supply Current 24mA minimum
Output 2-wire, 4 to 20mA DC Current (500 Ohm Load Max.)
or 3-wire, 0-5 or 0-10VDC (5K Ohm Min.)
Sensor Accuracy1 +/- 1.5% FSO for 0-10PSI and 0-30PSI ranges
+/- 1% FSO for all other ranges
Output Update Rate 1 Second Interval
Response Time (0-100%) 8 Seconds
Operating Temperature Range Sensor: -40 to 230
°
F (-40 to 110
°
C)
Enclosure: 5 to 176°F(-15 to 80°C)
Sensor Cable: 0 to +75°C (32 to 167°F)
Compensated Temperature Range 32 to 140
°
F (0 to 60°C)
Humidity 10 to 90% RH, non-condensing
Thermal Effects2 +/-2%FSO (0 to 60°C)
Proof Pressure 3 x F.S. for WPR2 Series
Burst Pressure 1500 PSI
Media Gases, refrigerants, ammonia and water-based fluids *
Features Depluggable terminal blocks
Push button/Remote Auto Zero
DIP switch selectable ranges and output modes
Out-Of-Range Diagnostic Output
Enclosure IP66 Rated (Mounting Flanges & Screws Included)
Approvals RoHS
Display Optional LCD display
Note 1: Accuracy includes linearity,
hysteresis and repeatability.
Note 2: Shift is relative to 77°F
(25°C).
*Please contact ACI for petrol chemical compatible versions.
Table 2: Product Specifications
Warranty Specification
The ACI WPR2 Series is covered by ACI’s Five (5) Year Limited Warranty, which is located in the front of
ACI’S SENSORS & TRANSMITTERS CATALOG or can be found on ACI’s web site:
This manual suits for next models
2
Table of contents
Other aci Transducer manuals
Popular Transducer manuals by other brands

Oppermann Regelgeräte
Oppermann Regelgeräte CO2TRH manual

Soundmask
Soundmask SM-T-1200 operating manual

Setra Systems
Setra Systems Multi-Sense 260 Series installation guide

halstrup-walcher
halstrup-walcher PS11 instruction manual

novotechnik
novotechnik LS1 Series manual

Balluff
Balluff BTL7-A M Series user guide