
3
ACL 5100 COMES
COMPLETE WITH
MOUNTING
POWER
CONNECTION
SOLENOID
OUTPUTS
The ACL 5100 can be mounted in a Class I, Div 2 area; usually close to the
burner. The 10’ of high voltage lead, (longer lengths are not recommended) must
be run in the non- metallic flex (provided) or free air. If the high voltage lead is
run in the non-metallic flex, a conduit seal (provided) must be installed. Note:
Lead lengths in excess of 10’ or use of metal or metallic sheathed conduit may
result in a diminished ignitor rod voltage. A ground wire (also supplied) must be
connected between the ground lug on the burner assembly and the bonding
ground terminal on the main circuit board. Note: If the controller must be
mounted farther away from the burner assembly, the ignition module, which is
mounted on the main circuit board, may be mounted in or near the burner
housing using the optional, CSA approved, ACL 5000R remote mount kit. Do not
coil excess high voltage lead inside controller enclosure. High voltage magnetic
field may damage sensitive components. Electronic components and cables in
close proximity to the ignition module and ignition cable may be affected by high
voltage noise.
The ACL 5100 is available in 12/24 VDC and 120/240 VAC. Voltage
requirements must be specified when ordering. The supply voltage of each unit is
clearly marked inside the door on the specification label and on the circuit board
beside its respective terminal. Incorrect polarity on 12/24 VDC units may result in
damage to circuit board components. The terminal marked ground is for supply
or system ground and the terminal marked bonding ground is strictly for the
ground wire to the burner assembly. It is important that a ground wire (supplied)
be connected between the bonding ground terminal and the burner assembly to
provide an uninterrupted path for the flame acknowledgment current.
There are two solenoid output terminals on the main circuit board marked pilot
solenoid and main solenoid. The output voltage at these terminals is always the
same as the controller supply voltage. The pilot solenoid output connects to the
pilot or low fire solenoid and is energized when a start is initiated. Main solenoid,
(main burner) energizes only after the pilot or low fire flame has been proven.
The time delay between proof of flame and energizing of main output is factory
set at 20 seconds. Available in all three voltages).
ACL 5100 controller c/w mounting hardware
ACL M-50A pilot mixer & nozzle
10’ ground wire
10’ high voltage wire complete with connectors
6.5’ non-metallic flex complete with connectors
Ignitor/flame rod complete with mounting hardware
Speed control valve
½”conduit seal
Flame current test leads
Operator’s manual
INSTALLATION
ACL 5100 Combustion Safety ControllerACL 5100 Combustion Safety ControllerACL 5100 Combustion Safety Controller