WARNING
ACL isnotresponsibleforthemisuseorincorrectapplicationofthisproduct.
Thismanualmustbereadinitsentiretybeforeinstallationofthiscontroller.
Installationmustbeperformedbyaqualifiedtechnicianandmustadheretothe
standardssetbythelocalregulatoryauthorities.
INSTALLATION
MANUAL
ACL CSC200
CombustionSafety
Control
FOR

4
6
ManufacturingInc.
ACL
ACL CSC200CombustionSafetyControl

1ManufacturingInc.
ACL
ACL CSC200CombustionSafetyControl
FEATURES •
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
I
NoProgramming
CSA approvedforClass ,Div2location
Operationalambienttemperatureof-40°to+60°Celsius
CSA approvedC22.2No199-M89.Combustionsafety
controlsandsolid-stateIgnitorsforGas&Oilburning
equipment
CSA B149.3-10compliant,meetsNFPA standards
Type4xenclosure,corrosiveresistantandweatherproof
100%failsafedesign
Safetylockoutforhightemperaturesetting
Onboardsolenoiddriverforpowerreductiontosolenoidsandpeak-holdsolenoids
TwoadjustabletypeKthermocoupleinputsformonitoringtwo
separatetemperaturepoints(processtemp.&hightemp.)
Pilotlessburnercontrolselectable.Singleanddualstage,LowfireandHighfire
Shutdowninput(ie.Lowlevelshutdown,pressureshutdown)
2Selectablethermocouplerangesof-60°Cto1100°Cor0°Cto500°C(-75°Fto
2012°For32°Fto932°F)
Adjustabledeadbandfrom1,2,3and5degreesCor2,4,6and10degreesF
°C °F
The ACL CSC200isdesignedtobeusedinconjunctionwiththe ACL combustion
moduleforacompletesafetycombustiondevice. The ACL CSC200providesburner
ignitionandflamefail,aswellasmonitoringoftwoseparatethermocoupleinputswhich
canbeutilizedfortemperaturecontrolinprocessapplicationssuchastanks,line
heaters,re-boilersoranyotherapplicationwhereaccuratetemperaturemonitoringor
controlisrequired. Thesystemisdesignedtooperatewithorwithoutacontinuous
pilot.
Thetwoindependenttemperaturesetpointscanbeadjustedwiththethreemembrane
pushbuttonsonthefaceofthecontrollerwithLEDindicationof Temp1or Temp2.
Initialsetupfortemperatureranges,displayanddeadbandcanbeobtainedthroughdip
switchselectionsforvarioususerpreferences.
EasytoreadfourdigitsevensegmentLEDdisplay
LEDindicationofthermocouple1or2valuesdisplayed
or readout
12/24VDCandsolar
Lowpowerconsumption(Powersavemodeoperatesaslowas1.2Watts)
On/Offcontrol
“THISEQUIPMENTISSUITABLEFORUSEINCLASSIDIVISION2,GROUPSA,B,C,&DORNONHAZARDOUS
LOCATIONSONLY”
“WARNING-EXPLOSIONHAZARD-SUBSTITUTIONOFCOMPONENTSMAYIMPAIRTHESUITABILITYFOR
CLASSIDIVISION2”
DESCRIPTION

Supply12/24VDCtoControllerasperdrawingonpage7.Displaywillturnonand
indicateeither Temp1or Temp2whicheverwasselectedby½pushbutton. The
arrowsupanddownselectthetemperaturesetpoint.Onceselected,theignition
controllercanbeturnedtotheOnposition. Thiswillinitiateignitioncontroller,if
callingforheatandallshutdowninputsareclear.Iftheprocessisabovethe
temperaturesettings,itwillnotinitiatelightingoftheburner,butwillturnononce
processdropsbelowsetpointinthepilotlessmode(I).
Whentheignitionswitchisturnedonandthecontrolleriscallingforheat,the
controllerwillattemptignitionandthepilotoutputwillprovidevoltagetothe
solenoidtoallowpilotgasforignition.Shutdowns,POCandremoteon/offmustbe
inapermissivestateforthistooccur.Pilotoutputwillceaseifthereisafailureto
lightwithin5secondsandaFFwillappearonthedisplay.Whenusingasingle
trialmodule,thecontrollerwilllockoutandhavetobereset.Whenusinga3try
module,thecontrollerwillattempt2moreadditionaltriesbeforelockingout. This
canbereseteitherbythelocalon/offswitchortheremoteon/offswitch.Whether
theI(pilotlessorintermittent)selectionorC(continuospilot)selectionisused,the
controllerwillperformasaboveexceptthecontinuouspilotwillbeinitiatedbyon/off
aswellastemperaturedemandswitch,andremainonregardlessoftemperatures
setting.
The ACL CSC200CombustionSafetyControloperatesinavoltagerangebetween
10-30VoltsDC. Theterminalsare#19positive,#20negative,and#22ground.
POWER
CONNECTION
OPERATION
ACL CSC200CombustionSafetyControl
ManufacturingInc.
ACL
INPUTCONNECTIONS
THERMO-
COUPLE
INPUT
ON/OFF
ThecontrolleracceptstwotypeK(ungrounded)thermocouplesonterminals1,2,3
and4. Theyareclearlymarkedontheboardforeachthermocoupleandpolarity
(Seewiringdiagram). Thetemperaturerangecanbeselectedviathedipswitches
onthemaincircuitboardlocatedinthetoprightcorner.Rangescanbeselected
independentlyforeachthermocoupleinput,eitherhighorlow.Highrangeis-60 C
to1100 C(-76 Fto2012 F)orlowrange,0 Cto500 C(-32 Fto932 F).
Theswitchonthesideofthecontrollerisinternallywiredtoterminals5and6.
Thisturnsonandofftheignitionmoduleprovidedtheshutdowninputandremote
resetinputsareclosedandtemperaturevaluesforboththermocouplesareina
permissiverange. TheOn/Offswitchalsoactsasaresettoclearanylatchedshut
downsthatmayhavetrippedthencleared.
o
o o o oo o o
2

3ManufacturingInc.
ACL
REMOTE
ON/OFF
ALARM
STATUS
PROOFOF
CLOSURE
IGNITION
MODULE
CONNECTION
S/D
SHUTDOWN
ACL CSC200CombustionSafetyControl
Theremoteon/offterminals7and8,whenopenedwillturnofftheignitionmodule
andvalveoutputswhenopenedandresetanylatchedshutdownthatmayhave
trippedthencleared.Controllerwillnotresetunlessshutdownshavecleared.
Theseterminalsmustbewiredtodrycontactsofaremoteswitchorrelaywhen
used. A jumpermustremainacross7and8whennotinuse.Whenremoteon/off
isopened, willappearondisplay.
Theshutdownterminals9and10areusedtoturnofftheignitionmodulewhen
opened. Theseterminalsarewiredtodrycontactshutdownssuchaslevel
switches,pressureswitches,oranyothertypeofauxiliaryshutdowndevice.If
morethanoneshutdownswitchisused,theymustbewiredinseries.Openingof
anyswitchconnectedtoshutdownterminals9and10willshutofftheignition
moduleandde-energizeall3valveoutputs. Theseterminalscanbeselectedto
latchorunlatchwhenshutdownisclearedviathedipswitchsettings(Seedip
switchdiagram).Unlatchallowsthemoduletorestartignitionwhencleared,latch
locksoutarestartuntilamanualresetoftheOn/Offswitchisturnedoffthenonor
theremoteresetswitchisopenedthenclosed.
ThealarmstatusprovidesforremoteindicationofwhethertheCSC200isina
normaloperatingmodeorifitisinashutdownstate,orturnedoffeitherremotely
orlocally. Alarmstatusterminals11and12areadrysetofcontacts.Whenpower
tocontrollerisoff,thecontactsareopen.Contactsarealsoopenwhencontroller
isinashutdownstate(ie.Powerfailureorshutdownisopen).Thisprovidesfora
completefailsafeindicationofthestatusofthecontroller.
ThePOC(ProofofClosure)terminals13and14areusedwhenaproofofclosure
safetyshutdownvalveisused. ThispreventsthestartingofanyignitionifthePOC
switchisopened. Thissafetyfeatureeliminatestheriskofignitingaburnerifthe
valveispartiallyopenandproofofclosureswitchindicatesopen. Thisisalsoa
failsafeinputasitwillnotallowignitiontoinitiateifwireisbrokenordisconnected.
willappearonthedisplay. A jumpermustbeinstalledbetween13and14if
thisfeatureisnotused.
Theterminals15,16,17and18aretobewireddirectlytothe ACL ignitionmodule.
Thisprovidescommunicationbetweenthetwo,allowingforacompletecombustion
safetycontrolandignitionofburner(Seewiringdiagram).
Rr
POC

4
6
4
ManufacturingInc.
ACL
PILOT Theterminals27&28providepowertothepilotsolenoidvalvetoallowgasfor
initialignitionandflamesensing. Thevoltagetothisoutputisthesamevoltage
suppliedtothecontroller. Thisoutputhasalowpowerfeatureforthesolenoids
providedbyanonboardsolenoiddrivercircuit. Thiscircuitcanreducepower
consumptionofsolenoidsasmuchas80%powerreduction. Thiscircuitalsohelps
eliminateanynoisethatmaybeproducedbysomesolenoids,andhelpsextend
thelifeofthesolenoids. Toutilizeonboardsolenoiddriver,seedipswitchsettings.
Theterminals25and26providepowertothemainsolenoidvalves.Powerto
theseterminalsarepresentonly10secondsafterpilotflameispresentand
shutdownsaresatisfied. Thisoutputalsohasthesamelowpowerfeatureofthe
onboardsolenoiddriver.
Theterminals23and24providespowertothemainsolenoidsthroughthe
temperature1setting. Thisallowsforanindividualtemperaturecontrolofoneof
themainsolenoidseliminatingunnecessarystrokingofthemainsafetyshutdown
valvestocontrolmaingastotheburnerfortemperaturecontrol. Thisoutputalso
hasthelowpowerfeatureoftheonboardsolenoiddriver.
T-MAIN
INTERMITTENT
PILOT (Pilotless)
MAIN
OUTPUTCONNECTIONS
The ACL CSC200controllerprovidesthisfeatureforapplicationswherea
continuouspilotmaynotbedesirable. Thepilotoutputisonlyenergizedwhenthe
controlleriscallingforheat.Inthiscase,thepilotturnson,thenafter10seconds
themainand T mainoutputsbecomeenergized. Thisallowsforalowfirestart
throughthemainburnersorapilot/mainstartwhereanindividualpilotandmain
areused. Thisisonlyinitiatediftheon/offswitchisintheonpositionandall
shutdownsandPOCareclosed.
Whencontinuouspilot(C)isselectedvia(dipswitchsettings)thepilotoutput
becomesenergizedwhentheon/offswitchisturnedtoon,andallshutdownsand
POCareclearandpermissive,regardlessofwhetherthecontrolleriscallingfor
heat.
Intermittentpilot(I)orContinuouspilot(C)featurescanbeaccessedthroughthe
dipswitchsettings.Seedipswitchdiagram,indicatedbyI/C.
PILOTLESSORCONTINUOUSPILOTFEATURE
CONTINUOUS
PILOT
ACL CSC200CombustionSafetyControl

5ManufacturingInc.
ACL
INSTALLATION
ADJUSTINGSETPOINTS
12
Selectstemperatureinput1or2ondisplay
Temp1-Bathorprocesstemperature
Temp2-Hightemperatureshutdown
Displaysandincreasestemperature
setpoint-Holdbuttondowntoscroll
todesiredsetpointthenrelease.
Displaywillthenreturntoactual
temperaturereading
Displaysanddecreasestemperature
setpoint.Holdbuttondowntoscroll
todesiredsetpointthenrelease.
Displaywillthenreturntoactual
temperaturereading.
Ifleftwithnobuttonspushedthedisplaywillrevertbacktoshowtheactualthermocoupletemperature
readingaccordingtotheLEDindication(Temp1or Temp2).
Displaywillshow(----)whenthermocouplesarenotenabledthroughthedesignateddipswitchsetting
or(OPEN)ifthethermocouplesarenotconnectedorfailedopen.
ACL CSC200CombustionSafetyControl
PowerFailure-Indicationiflossof
powertocontrolleroccurs.
FlameFail-Indicatesthatpilothas
goneoutandfailedtore-light.
Processtemperatureindicationof
either TC-1or TC-2,whicheveris
selected.
Indicatesswitchhasbeenturnedoff
toignition.
RemoteReset
Shutdown-Indicatesanopenswitch
orshutdownwhichistiedinto
terminals9&10.
Indicates TC-2temperatureisator
abovesetpointwhichwillshutdown
controllervalveoutputs.
ProofofClosure-IndicatesthePOC
switchterminalsareinanopenstate.
Jumpershouldbeinplacewhennotusing
ProofofClosurevalve.
Indicates TC-2disabled.Maybe
selectedwithdipswitch.
Indicatesanopenthermocouple
conditiononeitherthermocouple1or
2.Controllervalveoutputsbecome
de-energized.
CONTROLLERDISPLAYCODES

4
6
6ManufacturingInc.
ACL
DipSwitchOptionChart
Switch#1
Switch#2
Switch#3
Switch#4
Switch#5
Switch#6
Switch#7
Switch#8
Switch#9
Switch#10
Switch#11
Switch#12
Selectsdisplaytemperaturetoreadineither Cor F.
Deadbandsetting.(seechart)
Deadbandsetting.(seechart)
Disablesorenablesupanddownbuttonsfor TC2settings.
Thermocouple1highandlowtemperaturerangesetting.-H(-60 Cto1100 Cor-76 Fto2012 F)-L(0 Cto
500 Cor-32 Fto932 F)
Thermocouple2disablewhennotinuseandenablewheninuse.
Thermocouple2highandlowtemperaturerangesetting.- to to to
to
Powersavemodeldisplayautomaticallydimsafter2minuteswhennobuttonsarepressed.
Continuouspilotmode(C)whenselectedorpilotlessmode(intermittent)(I)whenselected.
Latchestheshutdownandlockscontrollerfromrestartingwhenshutdownclears.Whensettooff,controller
ignitionresumesautomaticallyifshutdownclearsandcontrollercallsforheat.
Latchestemp#2andlockscontrollerfromrestartingwhentemperatureclearsbelowsetpoint.Whensetto
off,controllerignitionresumesautomaticallyiftemperaturefallsbelowsetpoint,andallshutdownsareclear.
Ifpowerfailuretocontrolleroccurs,thepowerfaillatchsettingdoesn’tallowcontrollertorestartignitionwhen
powerreturns.Whensettooff,controllerignitionresumesautomaticallywhenpowerreturns.
00
00 0 0 0
0 0 0
H(-60 C 1100 Cor-76 F 2012 F)-L(0 C
500 Cor-32 F 932 F)
0 0 0 0 0
0 0 0
124
3
12
11
10
9
8
7
6
5
4
3
2
1
SW3
SW2
0C
0F
ON ON OFF OFF
ON
1
2
OFF
2
4
ON
3
6
OFF
5
10
PWRFAIL LATCH
HIGH TEMP LATCH
S/DLATCH
I/CPILOT
PWRSAVE
TC2H/L
TC2D/E
TC1H/L
BTND/E
DBAND2
DBAND1
00
C/ F
40 20 10
DEADBAND
SETTINGS
OFF/ON
SOLENOIDDRIVER
DIP SWITCHES
ACL CSC200CombustionSafetyControl
Selectingdipswitch1,2,or3or
anycombinationwillprovidea
percentageofcycletimefor
thesolenoidoutputsforpower
saving.
(Ie.)Switch1(40%)and
Switch3(10%)whenselected
willprovide50%cycletime.
0C0000
0
000

7
ManufacturingInc.
ACL
ACL CSC200CombustionSafetyControl
Yel l ow
Red
Alarm
contact
POC (Jumper when not used)
+
-
+12/24VDC
-12/24VDC
+
+
-
-
TC-1
TC-2
Type K
Thermocouple
inputs
Ignition
ON/OFF
CSC 200
Remote Mount Kit
ACL Combustion
Safety Control
Ignition Module
High Voltage
Ignition Wire
To I gni t or / Fl ame
Rod on Burner
P
G
V
(TC-1)
(TC-2)
Remote reset
S/D (Jumper when not used)
A
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
25
26
27
28
P
A
G
V
Yel l ow
Red
AUX LLSD PSD
Shutdowns
Proof of closure +
+
-
+
-
Main
Pilot
+
-
+
-
+
-
Pilot solenoid
Main solenoid
Temper at ur e cont r ol l e d
main solenoid
(dry contacts)
To gr o und l u g
on pilot or burner
22
T-Main
-
24
23

Voltage
Current
(max)
Controller Only
Current
(power save mode)
Controller Only
Power
(max)
Controller Only
Power
(power save mode)
Controller Only
Relay Contact
Max Allowed Operating Temp.
12 VDC .500A .10A 6W 1.2W 2ampPerOutput -40Cto60C
24 VDC .250A .05A 6W 1.2W 2ampPerOutput -40Cto60C
SPECIFICATIONSCHART
CSA StandardC22.2No.0-10-GeneralRequirements-CanadianElectricalCodePartII
CAN/CSA-C22.2No.0.4-04-BondingofElectricalEquipment
CSA StandardC22.2No.94-M91-SpecialPurposeEnclosures
CSA StandardC22.2No.142-M1987-ProcessControlEquipment
CSA C22.2No.199-M89-CombustionSafetyControlsandSolid-StateIgnitorsforGasandOilBurning
Equipment
CSA StandardC22.2No.213-M1987-Non-IncendiveElectricalEquipmentforUseinClass ,Division2
HazardousLocations
UL Standard50,12thEdition-IndustrialControlEquipmentforUseinHazardous(Classified)Locations
UL746C,6thEdition-StandardforPolymericMaterials-UseinElectricalEquipmentEvaluations
UL 508,17thEdition-IndustrialControlEquipment
ANSI/UL 69813thEdition-IndustrialControlEquipmentforuseinHazardous(Classified)Locations
ANSIZ21.20-2005- AutomaticGasIgnitionSystemsandComponents
ANSIISA 12.12.01-2007-NonIncendiveElectricalEquipmentforUseinClass and ,Division2andClass
,Divisions1and2Hazardous(Classified)Locations
I
I II
III
*NOTE:Maximumcurrentnottoexceed5A total
ACL
ManufacturingInc.
ACL CSC200CombustionSafetyControl
8
APPLICABLESTANDARD&
CODEREQUIREMENTS

NOTES
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
4
6
9ManufacturingInc.
ACL
ACL CSC200CombustionSafetyControl

805Main AveWest-Box2002Sundre, AlbertaT0M1X0
Phone:(877)638-5234-Fax:(403)638-4973
E-mail:[email protected]
ACL
ManufacturingInc.
Website:www.aclmfg.com
LimitedWarranty
LiabilityStatement
Seller warrants that the product hereby purchased is, upon delivery, free from defects
in material and workmanship and that any product which is found to be defective in
such workmanship or material will be repaired or replaced by Seller for a period of one
year from purchase date. Warranty of such items do not include shipping, installation
or set-up.
ACL Manufacturing Inc. Shall not be liable for any special, indirect, consequential or
other damages of a like general nature, including, without limitation, loss of profits or
production, or loss of expenses of any nature incurred by the buyer or any third party.
Table of contents
Other ACL Controllers manuals