Acowa SPIDER User manual

1
User manual
ACOWA SPIDER / ACOWA ZOO
August 2019

2
Table of Contents
Content
Table of Contents .............................................................................................................................................. 2
SPIDER................................................................................................................................................................ 4
About SPIDER................................................................................................................................................. 4
Funktions ....................................................................................................................................................... 4
Installation..................................................................................................................................................... 5
Power supply ............................................................................................................................................. 5
Physical measurements............................................................................................................................. 5
Installation environments.......................................................................................................................... 5
Build-in power supply................................................................................................................................ 5
Analog input .............................................................................................................................................. 6
Digital input with the option of 0-10V analog........................................................................................... 6
Digital output............................................................................................................................................. 6
Operation....................................................................................................................................................... 7
Overview.................................................................................................................................................... 7
The red button........................................................................................................................................... 7
SPIDER diodes............................................................................................................................................ 8
Menu structure for the 2,4” OLED Display................................................................................................ 9
HMI display................................................................................................................................................ 9
I/O module................................................................................................................................................... 10
ACOWA ZOO Configuration Tool..................................................................................................................... 11
Connecting to a PC ...................................................................................................................................... 11
USB connection ....................................................................................................................................... 11
TCP Connection ....................................................................................................................................... 11
ACOWA ZOO Installation............................................................................................................................. 11
Driver installation .................................................................................................................................... 11
Program installation ................................................................................................................................ 11
ACOWA ZOO................................................................................................................................................ 13
Overview.................................................................................................................................................. 13
Function buttons ..................................................................................................................................... 13
Settings selection..................................................................................................................................... 14
SPIDER details.......................................................................................................................................... 15
Input and output Settings............................................................................................................................ 15
Analog Input (AI1).................................................................................................................................... 15

3
Digital Inputs (I1–I6) ................................................................................................................................ 17
Digital output............................................................................................................................................... 19
Device settings / advanced settings ............................................................................................................ 22
Reports and alarms:................................................................................................................................. 22
Reverse Comm:........................................................................................................................................ 22
Show Status ................................................................................................................................................. 24
Online status............................................................................................................................................ 24
Applications................................................................................................................................................. 25
Pump control:.......................................................................................................................................... 25
Flow interface:......................................................................................................................................... 25
Additional Options:.................................................................................................................................. 26
Ground water lowering: .......................................................................................................................... 26
Monitoring:.............................................................................................................................................. 27
Compressor control:................................................................................................................................ 27
Register list quick-guide .............................................................................................................................. 28

4
SPIDER
About SPIDER
SPIDER is a universal control with functions for pump control, data collection, alarm management,
groundwater lowering etc.
SPIDER is developed and produced in Denmark. SPIDER complies with all specifications regarding
placement of electronic components in harsh environments.
Funktions
•Advanced 1 and 2 pump control with empty/fill function and internal pump alternation.
•Build-in GSM/GPRS Modem.
•Multi-protocol: Modbus RTU/TCP & COMLI. SPIDER auto-detects the protocol used by the SCADA
system.
•Click connection for a joystick-equipped graphic 2,4” OLED display directly onto SPIDER.
•Possibility to connect a 7” color touch-sensitive display via a serial HMI interface.
•Validated flow calculation where the pumps capacity is dynamically calculated.
•Status words function that can take a failed pump out of operation.
•Emergency control function via a float switch when a pressure transmitter fails.
•Indication of required pump service where SPIDER informs that a pump has reduced capacity.
•Built-in power bank that maintains control during power failures and sends an alarm to SCADA.
•Daily running of pumps so they do not seize after long idle periods.
•Daily depth pumping to avoid top sediment layer.
•Choice of various start levels to prevent sediment accumulation at liquid entrance point.
•Configuration of SPIDER via ACOWA ZOO software, both locally (Micro USB cable) or via server setup.

5
Installation
Power supply
SPIDER must be connected to a supply voltage according to the specifications below.
Voltage supply
230 VAC +10% / -20%
Frequency
50/60Hz
Input current consumption
0,004 -> 0,06A
Startup current
<10A
Own consumption
Max. 10W
Fuse
≤250mAT
SPIDER is equipped with a built-in Power bank and can send voltage
failure alarms when the primary power supply disappears.
The SPIDER Power bank (the two green high capacity capacitors) is
located on the bottom of the top print.
WARNING! Do not disassemble device until Power bank is turned off.
Physical measurements
For the installation of the SPIDER controller, the following specifications may be required.
SPIDER can be mounted on a standard 35mm DIN-rail.
Dimensions
L = 87mm x H = 90mm x W = 62mm
Weight
250g
Cable connection
0.5 –2,5 mm2
Vibrations (sinus shaped)
10-500Hz, 1G
Installation environments
SPIDER must not be installed in direct sunlight
Humidity
10% - 95% non-condensing
Operation temperature
-20°C to +50°C
Storage temperature
-20°C to +60°C
Maximum operation elevation
Max. 2000m above sea level
Free fall drop
30cm
Enclosure class
IP20
Start-up time total
20-120 sec. (depending on the GSM network)
Build-in power supply
SPIDER has an internal power supply designed for supplying sensors and input and output signals. Power
supply output + V:
Output voltage
24 V DC
Output current
Max. 100mA
Tolerance
+ / - 20%

6
Analog input
SPIDER is designed with one analog input 0 ... 20 mA / 4 … 20 mA.
Numbers of analog mA inputs
1
Electrically isolated
No
Measuring range
0 / 4 –20mA
Input impedance
Approx. 100 Ω
Measuring accuracy
+/- 1% af FS
Signal area
0-24mA / 0 –30 V DC
Signal frequence
Max. 100 Hz
Kabel / signal lenght
Max. 100m
Digital input with the option of 0-10V analog
SPIDER has 6 digital inputs, all of which can be selected as 0-10V analog voltage inputs.
Numbers of digital inputs
6
Electrically inslated
No
Digital signal
Low < 5 V / < 1 mA
High> 12 V / > 4 mA
Analog measuring range
0 –10 V DC
Analog signal impedance
Approx. 20KΩ
Measuring accuracy
+/- 1% of FS
Signal range (min / max)
0 –30 V DC
Signal f frequence
Max. 100 Hz
Kabel / signal lenght
Max. 100m
Digital output
SPIDER is equipped with 4 digital relay outputs.
Numbers of digital outputs
4
Electrically isolated
Yes
Insulation voltage
4 KV
Relay type
Relay output
Kabel / signal lenght
Max. 100m
Relay NO #11 og #21
Constant load
max. 10 A @ 230Vac - AC1
max. 500 W @ 230Vac - AC3
max. 1 A @ 48 VDC
max. 10 A @ 24 VDC
Minimum current
5 mA @ 10 V
Max. Start-up current
18A
Switch speed
Max. 1 Hz
Relay NO #31 og #41
Constant load
max. 2 A @ 230Vac - AC1
max. 100 W @ 230Vac - AC3
max. 1 A @ 30 VDC
Minimum current
5 mA @ 10 V
Max. Start-up current
6A or 10A @ 20 ms
Switch speed
Max. 10 Hz

7
Operation
Overview
The red button
SPIDER has a red button on the print next to the SIM card where it is possible to restart / reset SPIDER.
The red button on the top print has the following functions:
The number of
activations within
a 5 sec. range.
Function
1
Reset modem
3
Enable / disable display interface
(baud rate 57600 bps)
5
Enable HMI interface
(baud rate to 38400 bps)
Hold the button
in for 10 sec.
SPIDER restarts. Used in connection
with firmware-update or similar.
Digital Inputs
Digital outputs
Analog inputs
USB connection
Power supply

8
SPIDER diodes
Status
Flashes every 5 seconds: status to
indicate that the device is working.
Double flash means that the HMI
interface / oled display is enabled.
Net-status
Flashing fast (2 times per second):
modem is not connected to the GSM
mast.
Flashes slowly (once per second) and is
connected to the GSM mast.
Modem-status flashes when a modem is connected to the GSM mast and a signal strength is detected.
Display
SPIDER comes with two different types of displays but can also work without a display.
Display for direct mounting on SPIDER is a 2.4 "OLED display. The display has different screen settings and
can be operated with the joystick on the right side.
There is a pause screen which disables the normal screen display after 5 minutes. After this it goes to the
screen saver picture where level is displayed in different places on screen.

9
Menu structure for the 2,4” OLED Display
HMI display
SPIDER can also be delivered with a larger 7” HMI display where a larger graphic image can be designed. It
is possible to design customized graphics.
A serial overprint is required. This is easily clicked on the SPIDER as well as cable sets and HMI display.
SPIDER HMI kit incl. cable sets, SPIDER serial print incl. 1.5m cable set

10
I/O module
For connections of further signals, it is possible to connect an I/O module with multiple digital and analog
inputs.

11
ACOWA ZOO Configuration Tool
Connecting to a PC
USB connection
SPIDER connects to the PC via a Micro-USB connector on the side of the device. The ACOWA ZOO will then
connect to the device for configuration. When the ACOWA ZOO program starts, it will continuously try to
establish contact with a SPIDER device via USB connection.
TCP Connection
To connect to ACOWA ZOO via TCP, it must first be set to the correct TCP settings (IP Address, Port, APN).
This is done in the ACOWA ZOO via the USB port. Once the SPIDER is configured correctly, then it can be
accessed from the ACOWA ZOO via TCP.
ACOWA ZOO Installation
Driver installation
Before installing ACOWA ZOO on a computer running Windows 7 or Windows 8, an additional driver file for
communication via the USB port must be installed.
Right-click on the file "fsl_ucwxp.inf" and select "install". Windows will ask for permission to install. The file
is located in the "driver" folder under the " ACOWA ZOO " folder.
Program installation
ACOWA ZOO can be installed on computers running Windows 7, 8, or 10 or newer. Run the program
"AcowaZooSetup.exe" ("AcowaZooSetup _32bit.exe" on 32-bit operating systems) and follow the on-
screen instructions:
Choose if you want to create a desktop shortcut
Then choose ”Next”

12
Choose ”Install”
Choose whether to start ACOWA ZOO-Tool after
installation.
Then choose ”Finish”

13
ACOWA ZOO
Overview
Function buttons
Functions associated with writing and reading from SPIDER and disk, as well as contact with SPIDER via TCP.
Load Config from Device.
Load settings from the connected SPIDER device.
Write Config to Device.
Writes the current settings to the connected SPIDER Device
Establish TCP connection to the Device
Establishes TCP communication with a SPIDER device (With the 2G SPIDER version it
disconnects any USB connection)
Toggle Graphical and Schematic view
Toggle between displaying graphical menu settings and displaying schematic settings
(overview of ModBus registers in SPIDER device)
In and output settings
(see page 15)
Function buttons (see below)
Settings selection
(see page 14)
SPIDER details
(see page 15)

14
Open Local Config File
Load configuration from hard drive, usb drive, etc.
Save Local Config File
Save configuration on hard drive, usb drive, etc.
Load Default Configuration
Select and load a typical SPIDER configuration (control of 1 or 2 pumps, groundwater
lowering, etc.)
Backup operations
Mirrors the counters etc. in the SPIDER controller. (Is used for updating or replacement of
the modem)
Device settings
Advanced settings. (Further description on page 22.)
Show status.
Supervison and status bits. (Further description on page 24.)
New AcowaZoo version available.
Update AcowaZoo firmware (Is only shown when a newer version is available)
Settings selection
Here you select which part of the SPIDER device's settings
to display in the settings window on the right.
AI1:
Analog Input settings.
I1 - I6:
Input Settings 1-6
Output 1-4: Output Settings 1-4

15
SPIDER details
Here you are notified if a SPIDER is connected and what
types of connection are involved:
•USB on COM port
•TCP at Ip address / port
At the same time, details of the SPIDER device name and
location are displayed/set, as well as communication
settings.
•APN
•TCP-port
Input and output Settings
This section describes the settings for inputs and outputs as well as other logic in the SPIDER unit. The
individual pages are selected in Settings selection (see above)
Analog Input (AI1)
The analog input in the SPIDER is a standard 0-20 / 4-20 mA input to which a pressure transmitter or other
measuring equipment can be connected.
The input functions can be set in ACOWA ZOO when AI1 is selected in the Settings selection. AI 1 contains
the following settings:

16
AI 1 Settings
Functions
Description
0-20 mA or 4-20 mA
Scaling input defined by measurement equipment
Minimum scaling
Minimum measurement reading value
With 2 decimals (500 = 5,00)
Maximum scaling
Maximum measurement reading value
With 2 decimals (500 = 5,00)
High limit in use
Activates high limet functions
0=disabled, 1=actiivated
High limit label
Naming the high limit value
Used in alarm list and SMS
High limit Set point
Defines high limit value
High limit delay in secs.
Signal delay
Stated in seconds
High limit alarm call
Activates alarm signal
0=Local signal, 1=alarm signal
Low limit in use
Activates low limit functions
0=disabled, 1=actiivated
Low limit label
Naming the low limit value
Used in alarm list and SMS
Low limit Set point
Defines low limit value
Low limit delay in secs.
Signal delay
Stated in seconds
Low limit alarm call
Activates alarm signal
0=Local signal, 1=alarm signal
The scaling of AI1
It is possible to choose between 2 types of mA measurements. Either "0-20 mA" or the most common "4-20
mA". Min./Max. scaling points is entered at the desired resolution. For example, if a pressure transmitter
with a measuring range of 0-5m is used, and you need to read the level in cm. Enter min. = 0 and max. =
500.
Limit relay values
Limit relay values can be configured for high/low limit levels. For both types of limits the function can be
activated/deactivated, and the limit relay can be named with a label used as text in an alarm list and in SMS
alerting.
Values can be set to which level the high/low limit relays are activated, and a delay can be attached, so that
a limit value must be exceeded for a given time before the signal is registered as active. It is possible to
choose whether to send the signal as an alarm or to act as a local alarm.

17
Digital Inputs (I1–I6)
The I1-6 inputs on the SPIDER are standard 0-10 V inputs, or standard digital inputs where “0” is <5V and
“1”> 12V.
The input functions can be set in ACOWA ZOO
when I1-6 is selected in the Settings selection. I1-
6 contains the following settings:
DI/VI 1-6 Settings
Functions
Remarks
Signal label
Name of the signal
Used in alarm list and SMS
Input 1/6 - function
Selection of predefined functions
normally open / closed
The polarity of the signal
Delay for ON-state in secs.
Signal delay
Stated in seconds
Delay for OFF-state in secs.
Signal delay
Not in use
alarm signal
Activates alarm signal
0=Local signal, 1=alarm signal
VI settings
minimum scaling
Minimum measurement reading value
With 1 decimal. (20 = 2,0)
maximum scaling
Maximum measurement reading value
With 1 decimal. (20 = 2,0)
Midling in seconds
midling of the measurement reading value
High limit in use
Activates high limet functions
0=disabled, 1=actiivated
High limit label
Naming the high limit value
Used in alarm list and SMS
High limit Set point
Defines high limit value
High limit delay in secs.
Signal delay
Stated in seconds
High limit alarm call
Activates alarm signal
0=Local signal, 1=alarm signal
High alarm limit in use
Activates high Alarm limet functions
0=disabled, 1=actiivated
High alarm limit label
Naming the high limit alarm
Used in alarm list and SMS
High alarm limit Set point
Defines high limit alarm value
High alarm limit delay in secs.
signal delay
0=Local signal, 1=alarm signal

18
DI/VI 1-6 Settings
Functions
Remarks
High alarm limit alarm call
Activates alarm signal
0=Local signal, 1=alarm signal
Low limit in use
Activates low limit functions
0=disabled, 1=actiivated
Low limit label
Naming the low limit value
Used in alarm list and SMS
Low limit Set point
Defines low limit value
Low limit delay in secs.
Signal delay
Stated in seconds
Low limit alarm call
Activates alarm signal
0=Local signal, 1=alarm signal
Low alarm limit in use
Activates low limit alarm functions
0=disabled, 1=actiivated
Low alarm limit label
Naming the low limit alarm value
Used in alarm list and SMS
Low alarm limit Set point
Defines low limit alarm value
Low alarm limit delay in secs.
Signal delay
Stated in seconds
Low alarm limit alarm call
Activates low limit alarm signal
0=Local signal, 1=alarm signal
Functions for I1-6:
Standard DI function: Can be used to count pulses or check the state of a desired digital signal.
Standard VI function (0-10V): Can be scaled, the scaled value can be displayed. High/low limits are
attached to the signal, which can trigger an alarm if the limits are exceeded.
Klixon for P1/P2: Used in connection with pump control where the input can be configured as an alarm
signal that stops the faulty pump. The state of Klixon can be read in the Pump Status word on bit 2.
Thermal error P1 / P2: Used in connection with pump control, where the input can be configured as an
alarm signal that stops the faulty pump. The state of the Thermo relay can be read in the Pump Status word
bit 1.
High-level switch: Used as a start signal for emergency control of the pumps in case of faulty level
transmitter. The state of the high-level switch can be read on the Spider status word bit 26.
Pump running P1/P2: used as feedback signal for the pump control. If the corresponding output on SPIDER
is drawn, but the operating signal fails for more than 1 min. the pump is stopped. The state of the operating
signal can be read in the pump status word at bit 0.
Power measurement P1/P2: Used as an operating feedback. If the corresponding output on SPIDER is
drawn, but "low limit" is still indicated for more than 1 min. the pump is stopped. The state of the operating
signal can be read in the pump status word at bit 0.
Manual mode P1/P2: Disables the auto function for the pump when the signal is active. The signal typically
comes from an “Auto-0-Man” switch. The condition of “out of auto” can be read on the pump status word
bit 3.
IO expansion: Can only be used on I1 and I2, thus increasing the number of digital inputs up to 12. On the
additional Digital inputs, the following functions can be selected: Standard DI, Klixon, Thermal error, pump
running, manual mode and high-level switch.
Intensity: used in relation to rain gauges, where you can read the following values: Total counts of pulses,
today counter and yesterday counter. The values can be read on reg. adr. 256, 258, 260. At each pulse on
the input, the value increases with the entered value for VI settings - Maximum Scaling.
PIR: stands for Passive InfraRed sensor. This feature is typically used with a digital output that has the “Fan”
function. When the PIR input is activated, the fan starts up and runs for a specified time.

19
Heat sensor: Typically used with a digital output that has the function "Heat control". The input typically
has a heat sensor fitted which gives a 0-10V output signal. The input is scaled according to what 0V and 10V
correspond to. This defines a low limit at which the heat control must be activated and a high limit at which
heat control is deactivated.
Valve opened: Used with a digital output that has the function "Open valve", the function is used with
another set of DI/DO, where you can open and close a valve that stops the supply to the pump well,
whereby the inlet pipes can be used as reservoirs in case of increased inflow/rain event etc.
Valve closed: Used in conjunction with a digital output that has the "Close valve" function. Read the
description above.
General stop: Used as a general stop function. If the digital goes high it stops the pumps. Can be used in
case of “dry running”of pumps, where a mechanical stop is activated and stops the pumps.
Digital output
DO 1-2 are relay outputs dedicated to pump control, where DO 3-4 is used for specialized functions.
To configure DO 1-4 click on the button shown below the
Spider image.
DO 1 and 2 settings
Functions
Description
Constant or timed
Choose if DO should be activated for a given period
of time
Can be used for timely
operations
ON-timer in secs.
If timed is chosen, state the wanted period of time
On-timer stated in seconds.
Delay for ON-state in secs.
Signal delay
Delay stated in seconds.
DO 3 and 4 settings
Functions
Description
function
Additional functions
Could be alarm, Washing
pump etc.
Constant or timed
Choose if DO should be activated for a given period
of time
Can be used for timely
operations
ON-timer in secs.
If timed is chosen, state the wanted period of time
On-timer stated in seconds.

20
DO 3 and 4 settings
Functions
Description
Delay for ON-state in secs.
Signal delay
Delay stated in seconds.
Functions for DO 3-4:
Not used: The digital output has no function associated, so the output can be used freely and can be
controlled from SCADA.
Pump 1 (mirror): The output is triggered when P1 is running but is subject to its own delay, if selected, on-
timer.
Pump 1 error: The output is high if P1 is faulty.
Pump 2 (mirror): The output is triggered when P2 is running but is subject to its own delay, if selected, on-
timer.
Pump 2 error: The output is high if P2 is faulty.
General alarm: The output is high if an active alarm is registered in the SPIDER.
Compressor function: The output can be configured to activate a compressor after the pump run has
ended, and it can be selected whether the compressor should run intermittent operation or whether it
should only be activated once after the pump run has ended.
For interval operation, enter the interval in address 2776. The unit is in seconds. If the value is 0, the
compressor will run only once after the one-shot pump run. The operating time of the compressor is
written in address 2777. This unit is also in seconds.
Washing-pump: When the output is set to washing pump function, the output will go high when pump 1 or
2 is running and the level is decreasing.
The washing pump has its own start/stop levels which are located at the following addresses:
Initial level of washing pump is approx. 2785, the unit is the same as for level measurement on AI1.
Stop level for flush pump is approx. 2786, the unit is the same as for level measurement on AI1.
The washing pump function is only activated when the level has been above the starting level and then falls
below the starting level. If the level rises to more than 10% of the start level of the washing pump, it stops
again and awaits a level below the start level
Dosage-pump: When pump 1 or pump 2 is running, the output will pulse, the time between each pulse is
set in the parameter "Delay before ON in seconds" and the ON time of the pulse is set in the parameter
"on-time by time control in seconds".
Aumagear: This function is yet to be implemented
Bassin-PST: This feature requires that a VI6 level sensor is fitted to the SPIDER. The level sensor has its own
start/stop levels set in addresses 2785 and 2786. If the level in the pump sump detects a high limit of the
level, the basin pump will stop. When the high limit in the pump sump disappears, a pause of xx seconds is
held. This value is located at address 2776.
NOTE: The start/stop registers for basin control are also used as levels for the washing-pump function, so
be aware when using basin control and washing-pump on the same SPIDER controller.
This manual suits for next models
1
Table of contents