The low limit (FS-38) should be wired to
the “LL” terminals on the control panel
(remove jumper). The compressor will
shut off when low limit trips out.
The high limit (HL-170-HP) should be
wired to the “HL” terminals on the panel
(remove jumper). The compressor, auxil-
iary heat and emergency heat will shut
off when the high limit trips out.
A 40 VA transformer will power the con-
trol panel and up to four (4) dampers.
A 75 VA transformer will power the con-
trol panel and up to seven (7) dampers.
Up to three (3) dampers can be connected
in parallel. A total of no more than seven
(7) dampers may be connected to the sys-
tem. A system may be a single panel or
multiple panels.
If more than three zones are required, two
additional control panels can be used to
control up to a total of nine (9) zones. T5
terminal strip is used only when more
than three zones are required.
Label the dampers, damper wires and
thermostat wires with the zone number
and the area they serve.
Manual Changeover
Installation Notes:
To install the panel, first slide the PC
board out of its base and screw the base
to a flat surface next to the HVAC
equipment. The PC board should be
reinstalled by centering it over the base
and pushing firmly.
Connect only 24Vac to Control Panel.
The zone control panel requires a sepa-
rate 24 Volt transformer.
No special wire is required.
The thermostats and motorized dampers
may be located up to 300 feet from the
control panel when using 18 gauge ther-
mostat wire.
Fuse F1 (4 Amp) protects the relay con-
tacts. Fuse F2 (4 Amp) protects the
printed circuit board.
Zone dampers are powered closed /
spring return open.
If the heat pump is not equipped with
short cycle protection, a short cycle pro-
tection timer (TD-5) should be installed.
Specifications:
Panel Dimensions:
Height: 5.0 inches
Width: 10.0 inches
Depth: 2.0 inches
Mounting:
2 back plate screws
Operating Ambient Temperature:
-20º to 160º F
Power Supply:
24 Vac 40VA / 75VA transformer
Terminal Designations:
W = Auxiliary Heat
EH = Emergency Heat
Y = Compressor
G = Fan
O = Changeover Valve
R = Hot 24 Volt
X = Common
D = Damper
LL = Freeze Stat
HL = High Limit
H = Hot 24 Volt
G = Ground or Common
Comfort System™
Wiring Diagram For Z-300-HP Heat Pump Zone Control Panel
05-13-05
www.jacksonsystems.com
[email protected]
When green zone LED’s
are on, those zones are
calling for heating or
cooling.
If the thermostat does not
have an “EH” terminal,
disregard “EH” on the
zone panel.
All thermostats must
be set in the same
mode.
Website:
E-mail: 888.652.9663
317.227.1034
Toll-Free:
Fax:
Comfort System™
Z-300-HP Heat Pump Zone Control Panel
05-13-05
5418 Elmwood Avenue
Indianapolis, IN 46203
www.jacksonsystems.com
[email protected]
Website:
E-mail: 888.652.9663
317.227.1034
Toll-Free:
Fax:
Sequence Of Operation
Comfort System™ is a residential / light commer-
cial zone control system that allows a single
HVAC unit to have up to three separate zones
(nine if three panels are connected together). Each
zone is controlled by its own space thermostat and
motorized zone damper. If any of the zone
thermostats call for heating or cooling, the zones
not calling will have their dampers powered
closed, and the zone(s) calling will have its (their)
damper(s) remain open. The heating or cooling
equipment will also be brought on at the same
time. When all zone thermostats are satisfied, the
heating or cooling equipment turns off and all zone
dampers return to the open position to allow for
continuous air circulation. This is a manual
changeover zone control panel.
Thermostats
The Z-300-HP works with standard, heat pump
thermostats. All thermostats must be set in the
same mode. Thermostats must not be set in the
auto changeover mode.
Typical System
Verify that all wires have been connected to the
proper terminals and are secure.
Verify that the jumper across the “LL” and “HL”
terminals were removed before connecting the
high and low limit stats.
The low limit (FS-38) should be connected to the
“LL” terminals on the zone control panel. The
high limit (HL-170-HP) should be connected to the
“HL” terminals on the zone control panel.
Zone dampers are powered closed and spring
return open. There will be no power at the panel
damper terminals marked “D” when the damper is
in the open position.
When a green zone LED is on, that zone is calling
for heating or cooling.
To check the system for proper operation, pull the
disconnect for the condensing unit to prevent short
cycling. Next, place all the zone thermostat mode
switches in heat mode and turn down all
thermostat set points. Go to each zone thermostat,
one at a time, and call for heat to verify that the
proper zone dampers are open (and the rest are
closed). Turn the zone thermostat back down
before checking the next zone.
System Checkout
Zone #1
Stat
Zone #2
Stat
24 Volt 40VA
Transformer
Zone Control
Panel
Zone #1 Damper
Might Serve
Living Area
Zone #2 Damper
Might Serve
Bedroom Area

Other Jackson Systems Control Panel manuals

Jackson Systems Comfort System Z-300-HC User manual

Jackson Systems

Jackson Systems Comfort System Z-300-HC User manual

Jackson Systems The Green Zone Z-200-HC User manual

Jackson Systems

Jackson Systems The Green Zone Z-200-HC User manual

Jackson Systems The Green Zone Z-300-HPS User manual

Jackson Systems

Jackson Systems The Green Zone Z-300-HPS User manual

Popular Control Panel manuals by other brands

elsner elektronik WS1000 Style manual

elsner elektronik

elsner elektronik WS1000 Style manual

Automationdirect.com OP-440 manual

Automationdirect.com

Automationdirect.com OP-440 manual

CAME ZLJ24 installation manual

CAME

CAME ZLJ24 installation manual

Elmes Electronic CB32 Installation and operation manual

Elmes Electronic

Elmes Electronic CB32 Installation and operation manual

Jung FP 701 CT operating instructions

Jung

Jung FP 701 CT operating instructions

Siemens FC361 Series Technical manual

Siemens

Siemens FC361 Series Technical manual

Tylo H2 User and installation guide

Tylo

Tylo H2 User and installation guide

Energenie EG-PWC-PSWRC-01 user manual

Energenie

Energenie EG-PWC-PSWRC-01 user manual

Seresco CommandCenter manual

Seresco

Seresco CommandCenter manual

Interlogix Simon XT installation guide

Interlogix

Interlogix Simon XT installation guide

Zephyr GU4/MR11 user guide

Zephyr

Zephyr GU4/MR11 user guide

HORNER EXL10 OCS user manual

HORNER

HORNER EXL10 OCS user manual

Kidde TM0058 user guide

Kidde

Kidde TM0058 user guide

Murphy iGUARD overview

Murphy

Murphy iGUARD overview

Siemens SINAMICS IOP Getting started guide

Siemens

Siemens SINAMICS IOP Getting started guide

FireClass FC500 Pc programming manual

FireClass

FireClass FC500 Pc programming manual

Detection Systems abacus 6R user guide

Detection Systems

Detection Systems abacus 6R user guide

SALUPO INVERTER PLUS 3 Instruction and installation manual

SALUPO

SALUPO INVERTER PLUS 3 Instruction and installation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.