MX2820 23 INCH CHASSIS JOBAID
MX2820
23 INCH
CHASSIS
CLEI: M3M1W00B_ _
DESCRIPTION
The MX2820 chassis houses multiple M13 multiplexers that consolidate T1/E1 signals
into T3 circuits. The MX2820 (P/N 1186001L2) houses nine redundant M13 multiplexers.
The MX2820 chassis also houses a single SCU that provides management capabilities to
the MX2820 system.
Features of the MX2820 include:
■1:1 redundancy
■Hot-swappable MUX cards
■Embedded SNMP and Telnet management
■Simplified configuration through the VT100 terminal menu structure
■Meets the requirements for NEBS Level 3 compliance
TURN-UP STEPS
1. Attach mounting ears.
2. If necessary at this point, attach cable tie bar.
3. Mount chassis in rack.
Warning: Care should be taken not to upset the stability of the equipment rack.
4. Remove appropriate fuses from fuse panel.
5. Remove metal cover from the right side of the back panel.
Note: Silkscreen on cover references the following connections:
6. Wire wrap CHAIN posts and MIN alarm relay posts and route wire downward.
7. If STS-1, wire wrap CLKB and CLKA posts and route wire downward.
8. Wire wrap ACO posts and route wire downward.
9. Wire wrap AUX3, AUX2, and AUX1 alarm input posts and route wire downward.
10. Wire wrap MAJ and CRIT alarm posts and route wire downward.
11. Connect frame ground on barrier strip.
Caution: Per GR-1089-CORE October 2002, Section 9, MX2820 system is designed and
intended only for installation in a DC-C (common) bonding and grounding
system. The chassis ground wire must be of equal or greater ampacity than the
wire connected to the VDC return.
The MX2820 system is not intended or designed for installation in a DC-I
(isolated) bonding and grounding system.
Note: A readily accessible disconnect device, such as a rackmount fuse and alarm panel
that is suitably approved and rated should be incorporated in the fixed wiring.
Note: Connect to a reliably grounded VDC source, which is electrically isolated
from the AC source.
12. Connect RET B, PWR B, RET A, and PWR A on barrier strip.
Note: PWR = Respective –48 VDC or ±24 VDC source, RET = respective return
13. Insert appropriate fuses into fuse panel.
14. Using a voltmeter, verify that the operating voltage is within specifications
for A & B power.
15. Remove appropriate fuses from panel and replace the metal cover that was
removed in step 5.
16. Insert appropriate fuses into panel, and if not done in step 2, attach cable
tie bar.
17. Connect 10/100BaseT Ethernet and NTWK MGMT X.25 interfaces.
18. Route DSX-3 coax and tie to upper tie bar.
19. Route DSX-1 IN cables below upper tie bar and tie to upper tie bar.
20. Route DSX-1 OUT cables beneath lower tie bar and tie to lower tie bar.
OPERATIONAL SPECIFICATIONS
■Operates from A or B input voltage power feeds:
–48 VDC Systems: –42 VDC to –56 VDC
–24 VDC Systems: –22 VDC to –27 VDC
+24 VDC Systems: +22 VDC to +27 VDC
■Operates over extended temperature range of –40ºC to +50ºC without fans, and
–40ºC to +65ºC with fans.
■Storage –40ºC to +85ºC. Relative humidity to 95 percent, noncondensing.
COMPLIANCE
■The MX2820 chassis complies with UL 60950, NEBS Level 3, and
GR-1089-CORE.
■The MX2820 chassis is intended for installation in Restricted Access Areas only.
■This device complies with Part 15 of the FCC rules. Operation is subject to the
following two conditions: (1) This device may not cause harmful interference,
and (2) this device must accept any interference received, including interfer-
ence that may cause undesired operation.
■The DSX-1, DS3, and 10/100BaseT Ethernet circuits are not to be connected to
outside plant facilities.
■Changes or modifications not
expressly approved by ADTRAN
could void the user’s authority
to operate this equipment.
C A U T I O N
C A U T I O N
!
SUBJECT TO ELECTROSTATIC DAMAGE
OR DECREASE IN RELIABILITY.
HANDLING PRECAUTIONS REQUIRED.
61186001L2-22E
0403
Code Input Output
Power Code (PC) F C
Telecommunication Code (TC) – –
Installation Code (IC) A –
Amp Champ Pinout for All Future Bus to Amp Cable Assemblies
Conductor Color Code for All Future Bus to Stub Cable Assemblies
Pair # Wire Color – Tip Wire Color – Ring Pair # Wire Color – Tip Wire Color – Ring
1 WHT/BLU BLU/WHT 15 BLK/SLT SLT/BLK
2 WHT/ORG ORG/WHT 16 YEL/BLU BLU/YEL
3 WHT/GRN GRN/WHT 17 YEL/ORG ORG/YEL
4 WHT/BRN BRN/WHT 18 YEL/GRN GRN/YEL
5 WHT/SLT SLT/WHT 19 YEL/BRN BRN/YEL
6 RED/BLU BLU/RED 20 YEL/SLT SLT/YEL
7 RED/ORG ORG/RED 21 VOL/BLU BLU/VOL
8 RED/GRN GRN/RED 22 VOL/ORG ORG/VOL
9 RED/BRN BRN/RED 23 VOL/GRN GRN/VOL
10 RED/SLT SLT/RED 24 VOL/BRN BRN/VOL
11 BLK/BLU BLU/BLK 25 VOL/SLT SLT/VOL
12 BLK/ORG ORG/BLK 26 WHT/BLU BLU/WHT
13 BLK/GRN GRN/BLK 27 WHT/ORG ORG/WHT
14 BLK/BRN BRN/BLK 28 WHT/GRN GRN/WHT
Note: Bold indicates a blue binder group. Pairs 1–25 do not use a binder.
MX2820 23 INCH CHASSIS
PRICING AND AVAILABILITY 800.827.0807
TECHNICAL SUPPORT 800.726.8663
RETURN FOR REPAIR 256.963.8722
www.adtran.com
61186001L2-22E
Pin Function Pin
1 Ring 1 Tip 1 33
2 Ring 2 Tip 2 34
3 Ring 3 Tip 3 35
4 Ring 4 Tip 4 36
5 Ring 5 Tip 5 37
6 Ring 6 Tip 6 38
7 Ring 7 Tip 7 39
8 Ring 8 Tip 8 40
9 Ring 9 Tip 9 41
10 Ring 10 Tip 10 42
11 Ring 11 Tip 11 43
12 Ring 12 Tip 12 44
13 Ring 13 Tip 13 45
14 Ring 14 Tip 14 46
15 Ring 15 Tip 15 47
16 Ring 16 Tip 16 48
Pin Function Pin
17 Ring 17 Tip 17 49
18 Ring 18 Tip 18 50
19 Ring 19 Tip 19 51
20 Ring 20 Tip 20 52
21 Ring 21 Tip 21 53
22 Ring 22 Tip 22 54
23 Ring 23 Tip 23 55
24 Ring 24 Tip 24 56
25 Ring 25 Tip 25 57
26 Ring 26 Tip 26 58
27 Ring 27 Tip 27 59
28 Ring 28 Tip 28 60
29 61
30 62
31 63
32 FGND 64
MX2820 CABLE ASSEMBLY INSERTION ORIENTATION
When facing the backplane, the black locking tab or locking screw should be facing to the left as the
connector is inserted into the backplane.
Cable Part Numbers
DSX-1 Patch Cable Description Future Bus with Locking Tab Future Bus with Locking Screw
3 ft. Future Bus to Female 64-Pin Amp 1186020L1 1186020L2
6 ft. Future Bus to Male 64-Pin Amp 1186021L1 1186021L2
15 ft. Future Bus to Female 64-Pin Amp 1186022L1 1186022L2
25 ft. Future Bus to Stub 1186025L1 1186025L2
50 ft. Future Bus to Stub 1186050L1 1186050L2
100 ft. Future Bus to Stub 1186100L1 1186100L2
150 ft. Future Bus to Stub 1186150L1 1186150L2
WARRANTY
ADTRAN will replace or repair this product within the warranty period if it does not meet its
published specifications or fails while in service. Warranty information can be found at
www.adtran.com/warranty. U.S and Canada customer Faxback: 877-457-5007, Document 414.
6 OUT
(T1/R1)
6 OUT
(T1/R1)

Other manuals for MX2820

6

Other ADTRAN Chassis manuals

ADTRAN 1181001L1 Instruction Manual

ADTRAN

ADTRAN 1181001L1 Instruction Manual

ADTRAN OPTI-3 WMC User manual

ADTRAN

ADTRAN OPTI-3 WMC User manual

ADTRAN MX2820 M13 MUX User manual

ADTRAN

ADTRAN MX2820 M13 MUX User manual

ADTRAN Total Access 1500 Chassis 1180001L1 Instruction Manual

ADTRAN

ADTRAN Total Access 1500 Chassis 1180001L1 Instruction Manual

ADTRAN Total Access 850 Instruction Manual

ADTRAN

ADTRAN Total Access 850 Instruction Manual

ADTRAN OPTI-6100 LMX User manual

ADTRAN

ADTRAN OPTI-6100 LMX User manual

ADTRAN MX2820 User manual

ADTRAN

ADTRAN MX2820 User manual

Popular Chassis manuals by other brands

Solid State Logic MYNX installation guide

Solid State Logic

Solid State Logic MYNX installation guide

Hisense MT5659DUHT Service manual

Hisense

Hisense MT5659DUHT Service manual

CommScope Quareo 4000 installation instructions

CommScope

CommScope Quareo 4000 installation instructions

OWC Mercury Helios 2 Assembly manual & user guide

OWC

OWC Mercury Helios 2 Assembly manual & user guide

Keysight M9018A user guide

Keysight

Keysight M9018A user guide

3Com CoreBuilder 9000 Removal and Replacement Guide

3Com

3Com CoreBuilder 9000 Removal and Replacement Guide

Overland Storage SnapServer EXP E2000 Expansion Array manual

Overland Storage

Overland Storage SnapServer EXP E2000 Expansion Array manual

Advantech HPC-8104 user manual

Advantech

Advantech HPC-8104 user manual

Crestron DMF-CI-8 Supplemental guide

Crestron

Crestron DMF-CI-8 Supplemental guide

Supermicro SC732D4F-903B manual

Supermicro

Supermicro SC732D4F-903B manual

aculab GroomerII installation guide

aculab

aculab GroomerII installation guide

nMedia HTPC 3000B Quick installation guide

nMedia

nMedia HTPC 3000B Quick installation guide

StorCase Technology InfoStation user guide

StorCase Technology

StorCase Technology InfoStation user guide

Würth 1952 008 220 Translation of the original operating instructions

Würth

Würth 1952 008 220 Translation of the original operating instructions

NI cRIO-9101 User manual and specifications

NI

NI cRIO-9101 User manual and specifications

Advantech RMD-1150 user manual

Advantech

Advantech RMD-1150 user manual

Svive LUNA S100 manual

Svive

Svive LUNA S100 manual

StarTech.com 8STETCHS2U instruction manual

StarTech.com

StarTech.com 8STETCHS2U instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.